background image

12 Special requirements for R32 units

Installation and operation manual

18

RXYSA4~6A7V/Y1B

VRV 5-S system air conditioner

4P600329-1E – 2023.02

For  installation  of  the  remote  controller,  please  refer  to  the
installation  and  operation  manual  delivered  with  the  remote
controller.  Each  indoor  unit  must  be  connected  with  a  R32  safety
system  compatible  remote  controller  (e.g.  BRC1H52/82*  or  later
type). These remote controllers have implemented safety measures
that will warn the user visually and audibly in case of a leak.

For installation of the remote controller, it is mandatory to follow the
requirements.

1

Only a safety system compatible remote controller can be used.
See technical data sheet for remote controller compatibility (e.g.
BRC1H52/82*).

2

Each  indoor  unit  must  be  connected  to  a  separate  remote
controller.  In  case  indoor  units  are  operating  under  group
control,  it  is  possible  to  use  only  one  remote  controller  per
room.

3

The remote controller put in the room served by the indoor unit
must  be  in  'fully  functional'  or  'alarm  only'  mode.  In  case  the
indoor  unit  is  serving  a  room  other  than  where  it  is  installed,  a
remote  controller  is  required  in  both  the  installed  and  served
room (some relaxations are possible, see examples below). For
details  about  the  different  remote  controller  modes  and  how  to
set  up,  please  check  the  note  below  or  refer  to  the  installation
and operation manual delivered with the remote controller.

4

For  buildings  where  sleeping  facilities  are  offered  (e.g.  hotel),
where  persons  are  restricted  in  their  movements  (e.g.
hospitals),  an  uncontrolled  number  of  persons  is  present  or
buildings where people are not aware of the safety precautions
it  is  mandatory  to  install  one  of  the  following  devices  at  a
location with 24-hour monitoring:

▪ a supervisor remote controller
▪ or  a  centralised  controller.  E.g.,  iTM  with  external  alarm  via

WAGO module, iTM with built-in alarm, …

Note: 

The  remote  controllers  with  built-in  alarm  will  generate  a

visible  and  audible  warning.  E.g.  the  BRC1H52/82*  remote
controllers  can  generate  an  alarm  of  65  dB  (sound  pressure,
measured at 1 m distance of the alarm). Sound data is available in
the technical data sheet of the remote controller. 

The alarm should

always be 15 dB louder than the background noise of the room.

A field supply external alarm with a sound output 15 dB louder than
the background noise of the room MUST be installed in the following
cases:

▪ The  sound  output  of  the  remote  controller  is  not  sufficient  to

guarantee  the  15  dB  difference.  This  alarm  can  be  connected  to
the  SVS

 

output  channel  of  the  outdoor  unit  or  to  the  optional

output  PCB  of  the  indoor  unit  of  that  specific  room.  The  outdoor
SVS will trigger for any R32 leak detected in the complete system.
For indoor units, the optional output is only triggered when its own
R32  sensor  detects  a  leak.  For  more  information  on  the  SVS
output  signal,  see 

"16.3  To  connect  the  electrical  wiring  to  the

outdoor  unit"

  [

4

  31].  For  more  information  on  the  optional  output

PCB  of  the  indoor  unit,  please  refer  to  the  installer  and  user
reference guide of the indoor unit.

▪ A centralised controller without built-in alarm is used, or the sound

output  of  the  centralised  controller  with  built-in  alarm  is  not
sufficient  to  guarantee  the  15  dB  difference.  Please  refer  to  the
installation  manual  of  the  centralised  controller  for  the  correct
procedure to install the external alarm.

Note: 

Depending  on  the  configuration,  the  remote  controller  is

operable  in  three  possible  modes.  Each  mode  offers  different
controller  functionality.  For  detailed  information  about  setting  the
operation mode of the remote controller and its function, please refer
to the installer and user reference guide of the remote controller.

Mode

Function

Fully functional

The controller is fully functional. All normal
functionality is available. 

This controller can

be master or slave.

Alarm only

The controller only acts as leak detection
alarm (for a single indoor unit). No
functionality is available. The remote
controller should always be put in the same
room as the indoor unit. 

This controller can

be master or slave.

Supervisor

The controller only acts as leak detection
alarm (for the whole system, i.e. multiple
indoor units and their respective controllers).
No other functionality is available. The remote
controller should be placed at a supervised
location. 

This remote controller can only

be the slave.

Note: 

In order to add a supervisor remote

controller to the system, a field setting should
be set on both remote controller and outdoor
unit.

Note: 

Incorrect use of remote controllers can result in occurrence of

error codes, non-operating system or system that is not compliant to
applicable legislation.

Note: 

Some  centralised  controllers  can  also  be  used  as  supervisor

remote  controller.  For  further  details  on  installation,  please  refer  to
the installation manual of the centralised controllers.

Examples

NOT OK

OK

Case

1

a

c

b

a

d

b

Remote controller is not R32 safety system
compatible

2

a

b

b

b

e

a

b

d

b

d

b

d

Indoor units without remote controller are not
allowed

Summary of Contents for VRV 5-S RXYSA4A7V1B

Page 1: ...llation and operation manual VRV 5 S system air conditioner English Installation and operation manual VRV 5 S system air conditioner RXYSA4A7V1B RXYSA5A7V1B RXYSA6A7V1B RXYSA4A7Y1B RXYSA5A7Y1B RXYSA6A...

Page 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Page 3: ...1 0 21 5 22 0 22 6 23 1 23 6 24 2 24 7 25 3 25 8 26 3 26 9 27 4 27 9 4 6 5 5 6 0 6 5 6 9 7 2 7 6 7 9 8 2 8 6 9 2 9 8 10 4 11 1 11 7 12 3 12 9 13 5 14 1 14 7 15 4 16 0 16 6 17 2 17 8 18 4 19 0 19 6 20...

Page 4: ...urs 15 8 2 14 Symptom The outdoor unit fan does not spin 16 8 2 15 Symptom The compressor in the outdoor unit does not stop after a short heating operation 16 8 2 16 Symptom The inside of an outdoor u...

Page 5: ...data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on https www daikin eu Use the search function to find your model Latest revisions...

Page 6: ...WARNING If the power supply has a missing or wrong N phase equipment might break down Establish proper earthing Do NOT earth the unit to a utility pipe surge absorber or telephone earth Incomplete ea...

Page 7: ...d excessive vibration or pulsation to refrigeration piping Protect the protection devices piping and fittings as much as possible against adverse environmental effects Provide space for expansion and...

Page 8: ...vironment and human health 3 2 Instructions for safe operation CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appli...

Page 9: ...ON NEVER expose little children plants or animals directly to the airflow WARNING The unit is equipped with a refrigerant leak detection system for safety To be effective the unit MUST be electrically...

Page 10: ...r interface whose display shows change over under centralised control refer to installation and operation manual of the user interface When the display change over under centralised control flashes re...

Page 11: ...to operation if the room temperature is low 20 C 6 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector button on the user interfa...

Page 12: ...the master user interface can select heating or cooling mode 6 5 2 To designate the master user interface 1 Press the operation mode selector button of the current master user interface for 4 seconds...

Page 13: ...l name of the unit The manufacturing number stated on the nameplate of the unit The installation date The symptoms or malfunction and details of the defect WARNING Do NOT modify disassemble remove rei...

Page 14: ...mistor malfunction indoor gas Suction air thermistor malfunction indoor Discharge air thermistor malfunction indoor Movement detector or floor temperature sensor malfunction indoor R32 sensor malfunct...

Page 15: ...g cooling operation If the interior of an indoor unit is extremely contaminated the temperature distribution inside a room becomes uneven It is necessary to clean the interior of the indoor unit Ask y...

Page 16: ...es hydrofluorocarbon Contact your dealer when discarding this unit It is required by law to collect transport and discard the refrigerant in accordance with the hydrofluorocarbon collection and destru...

Page 17: ...ected failure or disconnection of the R32 sensor located in the indoor unit For more information about the SVS output see 16 4 To connect the external outputs 432 Indoor unit installation NOTICE If on...

Page 18: ...t of the remote controller is not sufficient to guarantee the 15 dB difference This alarm can be connected to the SVS output channel of the outdoor unit or to the optional output PCB of the indoor uni...

Page 19: ...6 a b b d a b b b d Group control is allowed up to a maximum of 5 indoor units connected to different ports or connected to the same port At least one R32 safety system compatible remote controller s...

Page 20: ...Lowest underground floor Lowest underground floor c Effective installation height Effective installation height Determine the value for both the lowest underground floor AND the other floors The tota...

Page 21: ...System charge kg 16 0 Judgement a b b b b B D C A a Outdoor unit b Indoor unit A B C D Room A B C D Example 2 Room A B C D Area m 10 20 10 20 Installation height m 3 0 2 2 3 0 2 2 Lowest underground f...

Page 22: ...allation site WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an operating gas appliance or an operating electric heater 13 1 1 Inst...

Page 23: ...nit 13 3 1 To provide the installation structure Prepare 4 sets of anchor bolts nuts and washers field supply as follows mm 7 5 8 150 4 8 0 4 9 0 4 8 5 4 M12 a a Make sure not to cover the drain holes...

Page 24: ...cated in the following illustration field supply 2 Place the 2 cables over the outdoor unit 3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the pa...

Page 25: ...or unit Use the same diameters as the connections liquid gas on the indoor units The diameters of the indoor units are as follows Indoor unit capacity index Piping outer diameter size mm Gas pipe Liqu...

Page 26: ...panel Especially for the bottom and side connection be sure to protect the piping with suitable insulation to prevent it from coming into contact with the casing 1 Do the following Remove the service...

Page 27: ...es either horizontally or vertically Mount the refnet header so that it branches horizontally A B 3 0 a b c d a a Horizontal surface b Refnet joint mounted vertically c Refnet joint mounted horizontal...

Page 28: ...order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed within 12 minutes after the indoor and outdoor units are powered on the compressor w...

Page 29: ...ng If Then The determined additional refrigerant amount is reached Disconnect the manifold from the liquid line You do not have to perform the Charging refrigerant in manual additional refrigerant cha...

Page 30: ...Potential NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantit...

Page 31: ...ice 30 mA MUST comply with national wiring regulation a MCA Minimum circuit ampacity Stated values are maximum values see electrical data of combination with indoor units for exact values 16 3 To conn...

Page 32: ...sh c Nut d Frame e Tube 8 Route the cables out of the unit WARNING Avoid sharp edges when routing cables to the rear Make sure to route the cables through the left side of the accumulator foot when pa...

Page 33: ...75 mm For the SVEO connection it is recommended to use a shielded cable The cable shield must be earthed at the marked earthing point that is located on the support frame of the terminal Y1 V1 c a b c...

Page 34: ...ich can withstand a temperature of 120 C for gas piping Reinforce the insulation on the refrigerant piping according to the installation environment Ambient temperature Humidity Minimum thickness 30 C...

Page 35: ...ue and changing the current field setting value is possible In general normal operation can be resumed without special intervention after changing field settings Some field settings are used for speci...

Page 36: ...on Access Action Mode 1 Push BS1 one time 7 segment display indication changes to Push BS1 one more time to return to the default situation Mode 2 Push BS1 for at least 5 seconds 7 segment display ind...

Page 37: ...Note For an ESP level higher than 45 Pa level 0 is kept for reliability of the fan motor 2 18 Description 0 default Auto setting at commissioning mode and stand by mode 1 Auto setting at commissioning...

Page 38: ...ox and the inside of the unit for loose connections or damaged electrical components Pipe size and pipe insulation Be sure that correct pipe sizes are installed and that the insulation work is properl...

Page 39: ...rmality When the test operation is fully completed normal operation will be possible after 5 minutes 19 6 Correcting after abnormal completion of the test run The test operation is only completed if t...

Page 40: ...ring any excessive refrigerant with a refrigerant recovery machine Ambient temperature sensor malfunction R1T A1P X18A Check connection on PCB or actuator Discharge temperature sensor malfunction R21T...

Page 41: ...ce manual for more information WARNING The unit is equipped with a refrigerant leak detection system for safety To be effective the unit MUST be electrically powered at all times after installation ex...

Page 42: ...nimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and...

Page 43: ...ributor Refrigerant flow l Heat exchanger Cooling m Accumulator Heating n Muffler o Capillary tube p Compressor accumulator M1C Compressor M1F Fan motor HPS A High pressure switch automatic reset HPS...

Page 44: ...VT Y3E Electronic expansion valve main EVM2 Y4E Electronic expansion valve EVL Y5E Electronic expansion valve EVSL Y6E Electronic expansion valve EVSG Y1S Solenoid valve 4 way valve Y3S Error operatio...

Page 45: ...n EVM1 Y2E Electronic expansion valve EVT Y3E Electronic expansion valve main EVM2 Y4E Electronic expansion valve EVL Y5E Electronic expansion valve EVSL Y6E Electronic expansion valve EVSG Y1S Soleno...

Page 46: ......

Page 47: ......

Page 48: ...4P600329 1E 2023 02 Copyright 2020 Daikin 4P600329 1 E 0000000 Verantwortung f r Energie und Umwelt...

Reviews: