Troubleshooting
Installer and user reference guide
163
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Main
code
Sub code
Cause
Solution
SVEO
(a)
SVS
(b)
Master Slave 1
Electronic expansion valve
malfunction (upper heat
exchanger) (Y1E) – main PCB
(X21A)
Check connection on PCB or
actuator.
Electronic expansion valve
malfunction (inverter cooling)
(Y5E) – main PCB (X23A)
Check connection on PCB or
actuator.
Electronic expansion valve
malfunction (lower heat
exchanger) (Y3E) – main PCB
(X22A)
Check connection on PCB or
actuator
Electronic expansion valve
malfunction (receiver gas) (Y4E) –
main PCB (X25A)
Check connection on PCB or
actuator.
Electronic expansion valve
malfunction (subcool heat
exchanger) (Y2E) – main PCB
(X26A)
Check connection on PCB or
actuator.
Electronic expansion valve
malfunction (liquid injection)(Y7E)
- sub PCB (X9A)
Check connection on PCB or
actuator.
Discharge temperature too high
(R21T) – main PCB (X33A):
▪
Stop valve closed
▪
Refrigerant shortage
▪
Open stop valves.
▪
Check
refrigerant
amount
+recharge unit.
Compressor casing temperature
too high (R15T) – main PCB
(X33A):
▪
Stop valve closed
▪
Refrigerant shortage
▪
Open stop valves.
▪
Check
refrigerant
amount
+recharge unit.
▪
Refrigerant overcharge
▪
Stop valve closed
▪
Check
refrigerant
amount
+recharge unit.
▪
Open stop valves.
Ambient temperature sensor
malfunction (R1T) – main PCB
(X18A)
Check connection on PCB or
actuator.