20
|
Electrical installation
Installer and user reference guide
126
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
20.7 To connect the external outputs
SVS and SVEO output
The SVS and SVEO outputs are contacts on terminal X2M.
The SVS output is a contact on terminal X2M that closes in case a leak is detected,
failure or disconnection of the R32 sensor (located in the BS unit or indoor unit).
The SVEO output is a contact on terminal X2M that closes in case of occurrence of
general errors. See
41] and
161] for errors that will trigger this output.
NOTICE
The outputs have a limited capacity of 220~240 V AC – 0.5 A.
Do NOT use the outputs as a power source. Instead, use each output to energize a
relay that controls the external circuit.
WHT
SVEO
SVS
BLK GRY PPL
b
a
c
X2M
a
SVEO output terminals (1 and 2)
b
SVS output terminals (1 and 2)
c
Cable to SVS output device (example)
Example:
X2M
(SVS)
a
1
2
c
b
d
a
SVS output terminal
b
Relay
c
AC power supply 220~240 V AC
d
External alarm
Cable routing
Route the SVEO or SVS output cable as indicated below.