13 Unit installation
Installation and operation manual
27
BS4~12A14AJV1B
VRV 5 branch selector unit
4P670163-1 – 2022.02
4×
PH2
SW8
To install the duct connection
12
Position the duct connection onto the other side of the unit.
13
Attach the duct connection with 4 screws.
4×
PH2
SW8
≤
3.2 N•m
To install the damper
14
Install the damper on the other side of the unit.
▪ Carefully guide the wires from the outside to the inside
through the small hole in the unit's metal plate. Take care
not to damage the connector and the earth wire connection.
▪ Position the damper onto the unit. Take care not to pinch
and damage the wires between the damper and the unit.
▪ Pull the wires through until the foam insulation fits properly in
the small hole in the unit's metal plate. This makes the
connection airtight.
▪ Attach the damper with 4 screws.
4×
PH2
SW8
≤
3.2 N•m
a
b
b
b
b
c
1
2
a
Damper wire
b
Screw
c
Damper
15
Connect the damper wires.
a
b
c
1×
PH2
≤
1.7 N•m
a
Connector
b
Earth wire screw
c
Damper earth wire
▪ Connect the damper wire to the intermediate connector.
▪ Position the damper earth wire and tighten the damper earth
wire screw.
16
Install the leftmost wire fixing plate. It holds the damper wire in
place.
▪ Restore the insulation of the wiring fixing plate by applying
the small accessory insulation piece on top of the old,
flattened insulation.
a
b
c
a
Wire fixing plate
b
Old insulation
c
New insulation (accessory)
▪ Position the wires as far down as possible in the opening on
top of which the wire fixing plate will be installed.
▪ Position the wire fixing plate over the screws and slide it in
place. Make sure the backside is aligned properly with the
insulation of the switch box, in order to make it airtight.
▪ Tighten the 2 screws.