background image

12 Special requirements for R32 units

Installation and operation manual

17

BS4~12A14AJV1B
VRV 5 branch selector unit
4P670163-1 – 2022.02

The  information  in  the  table  below  must  be  taken  into  account  in
case a ventilated enclosure is used as a safety measure:

Ductwork

The evacuation ductwork MUST vent outside the
building.

Avoid that dirt, dust and small animals can enter
the ductwork and lead to an obstruction. 

Example:

Install a non-return valve, grill, filter or other
component in the evacuation duct.

Extraction fan

The extraction fan must have a CE marking and
can not act as an ignition source during normal
operation. 

Example: 

Brushed DC motors cause

sparks and are not allowed.

Fan power must be lower than 2.5 kVA.

Replacement
air

Make sure that sufficient replacement air is
available for the extraction of a refrigerant leak.
The extraction airflow rate must be maintained for
at least 6.5 hours. This is achieved by providing a
sufficiently large air volume around the BS unit or
by providing sufficient replacement air around the
BS unit (e.g. natural openings or a dedicated
opening in the false ceiling).

Maintenance

A periodic inspection of the unit is required, where
the test run is repeated (see 

"17.1 BS unit test

run"

 [

4

 38]).

Maintain the evacuation channel to avoid dust and
dirt from building up and obstructing the flow path
(see 

"6.2 Periodic check of the ventilated

enclosure"

 [

4

 11]).

One BS unit – one extraction fan

In the most simple configuration, each BS unit in the system has its
own evacuation channel and its own extraction fan.

a

b

c

a

BS unit

b

Ductwork

c

Extraction fan

An  extraction  fan  must  be  connected  to  the  BS  unit,  see 

"15.5  To

connect the external outputs"

 [

4

 34].

In order to size the fan, a calculation has to be performed to find the
pressure  capacity  required.  The  total  pressure  drop  in  the
evacuation  channel  consists  of  multiple  parts:  the  pressure  drop
generated  by  the  BS  unit  and  the  pressure  drop  generated  by  the
components of the ductwork.

Select  an  airflow  rate  for  the  evacuation  that  meets  the  legal
requirements.  This  means  that  the  airflow  rate  is  above  the  legally
required  minimum,  and  generates  sufficient  pressure  difference
inside  the  BS  unit,  when  compared  with  the  pressure  of  the
surroundings.  The  minimum  required  airflow  rate  (AFR

OUT

)  is

18.8  m³/h,  and  the  pressure  drop  generated  by  the  BS  unit  should
lead to a pressure inside the BS unit (P

internal

) that is more than 20 Pa

below the pressure of the surroundings.

a

P

internal

AFR

OUT

a

BS unit

AFR

OUT

Airflow

P

internal

Internal pressure

It is advised to take a safety margin on these minimum values when
designing the evacuation channel in order to account for tolerances
on  parts,  dirt  and  dust  building  up  in  the  evacuation  channel  over
time, etc.

Note: 

 The internal pressure of the BS unit should not be more than

350 Pa below the pressure of the surroundings.

With  the  selected  airflow  rate,  note  down  the  pressure  drop
generated by all the components in the evacuation channel. For the
BS  unit  this  means  using  the  curve  that  gives  the  pressure  at  the
outlet  (P

OUT

)  in  function  of  the  airflow  rate  (AFR

OUT

).  To  find  the

pressure  drop  curves  of  the  BS  unit,  see  the  latest  version  of  the
technical engineering data.

a

P

OUT

AFR

OUT

a

BS unit

AFR

OUT

Airflow

P

OUT

Outlet pressure

For  the  pressure  drop  caused  by  other  components  of  the
evacuation  channel  (ducts,  bends,  etc.),  use  the  curves  of  the
manufacturer.

Use  the  airflow  rate  and  the  sum  of  the  pressure  drops  to  select  a
suitable fan.

Example

a

b

d

f

g

i

h

e

c

a

BS unit

b~h

Ductwork (duct, bend, reducer, expander, non-return
valve, wall grill, etc.)

i

Extraction fan

In this example we use a BS12A unit. Use the curve of the internal
pressure  inside  the  BS  unit  (P

internal

)  in  function  of  the  airflow  rate

(AFR

OUT

). When an airflow rate of 115 m³/h is selected, the pressure

inside the BS unit is 42.9 Pa below the pressure of the surroundings.
So  this  airflow  rate  is  above  the  required  18.8  m³/h,  as  well  as  the
pressure inside the BS unit is within the range of 20~350 Pa below
the pressure of the surroundings. We use this 115 m³/h airflow rate
for further calculations.

- 42.9

115

P

INTERNAL

[Pa]

-300

-250

-200

-150

-100

0

0

50

100

150

200

250

300

-50

AFR

OUT

[m³/h]

Note: 

These curves are plotting the internal pressure of the BS unit

compared to an ambient pressure of 101325 Pa.

Use the curve of the outlet pressure (P

OUT

) in function of the airflow

rate  (AFR

OUT

)  for  the  BS  unit.  With  an  airflow  rate  of  115  m³/h,  the

resulting pressure drop generated by the BS unit is 47.5 Pa.

-300

-250

-200

-150

-100

0

0

50

100

150

200

250

300

-50

P

OUT

[Pa]

AFR

OUT

[m³/h]

- 47.5

115

Summary of Contents for VRV 5 BS4A14AJV1B

Page 1: ...Installation and operation manual VRV 5 branch selector unit English Installation and operation manual VRV 5 branch selector unit BS4A14AJV1B BS6A14AJV1B BS8A14AJV1B BS10A14AJV1B BS12A14AJV1B...

Page 2: ...measure c External alarm d m kg Amin m All other floors a All other floors a Lowest under ground floor b No safety measure c No safety measure c External alarm d 5 16 15 16 35 207 104 207 6 23 18 23...

Page 3: ...iai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo pred...

Page 4: ...he products are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the...

Page 5: ...3 4 3 To install the drain piping 24 13 5 Installing the ventilation ducting 24 13 5 1 To install the ducting field supply 24 13 5 2 To install the duct closing plate 25 13 5 3 To switch the air in an...

Page 6: ...approved by the manufacturer are used in the duct work WARNING Do NOT install operating ignition sources example open flames an operating gas appliance or an operating electric heater in the duct wor...

Page 7: ...wer supply cables WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard WARNING Use an all pole disc...

Page 8: ...enance purposes See 12 3 To determine the required safety measures 4 14 to check if your system meets the R32 safety requirements For the user 3 User safety instructions Always observe the following s...

Page 9: ...ways have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation WARNING This unit contains electrical and hot parts WARNING Before oper...

Page 10: ...structions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable...

Page 11: ...the unit by yourself Ask a qualified service person to perform this work 6 1 Precautions for maintenance and service CAUTION See 3 User safety instructions 48 to acknowledge all related safety instruc...

Page 12: ...ned malfunctions is evident investigate the system in accordance with the following procedures Malfunction Measure If a refrigerant leak occurs error code Actions will be taken by the system Do NOT tu...

Page 13: ...it and options 11 1 About combining units and options 11 1 1 Possible options for the BS unit INFORMATION All possible options are mentioned in the option list below For more information about an opti...

Page 14: ...he outdoor unit For installation of the indoor unit see the installation and operation manual delivered with the indoor unit For compatibility of indoor units see the latest version of the technical d...

Page 15: ...arm e Ventilated enclosure Ventilated enclosure Use the total amount of refrigerant in the system and the area of the room in which the BS unit is installed to check what is the safety measure that ne...

Page 16: ...ntrolled number of people are present accessible for persons not familiar with the necessary safety precautions To warn at a supervised location connect a supervisor remote controller to the system Th...

Page 17: ...hen compared with the pressure of the surroundings The minimum required airflow rate AFROUT is 18 8 m h and the pressure drop generated by the BS unit should lead to a pressure inside the BS unit Pint...

Page 18: ...parallel BS units are connected to a single extraction fan Each BS unit benefits from a direct airflow path to the extraction fan In case of a refrigerant leak in any BS unit the damper of that BS uni...

Page 19: ...t run that simulates a refrigerant leak See 17 1 BS unit test run 438 for more details Field settings Multiple BS units in series one extraction fan Code Description Value 2 0 Cluster indication 1 ena...

Page 20: ...ames an operating gas appliance or an operating electric heater 13 1 1 Installation site requirements of the unit CAUTION Appliance NOT accessible to the general public install it in a secured area pr...

Page 21: ...length Keep drain piping as short as possible Drain pipe size Keep the pipe size equal to or greater than that of the connecting pipe vinyl pipe of 20 mm nominal diameter and 26 mm outer diameter Bad...

Page 22: ...lt flow Ducting on both sides B Reversed flow Only ducting on the air outlet side B Reversed flow Ducting on both sides C No extraction ventilation installed 1 To extraction fan or another BS unit 2 F...

Page 23: ...pension bolt Leave enough space for maneuvering with the unit between the nut and double nut 3 Position the unit by hooking the hanger brackets of the unit around the suspension bolts in between the t...

Page 24: ...n hose Note Start on the screw part of the metal clamp work your way around the clamp and end overlapping your starting point 5 b a c d a Drain pipe connection attached to the unit b Drain hose access...

Page 25: ...der the field supply insulation Create an overlap of 50 mm If the entire outlet duct is thermally insulated from the unit to the outside wall the accessory sealing material is not necessary a d e d e...

Page 26: ...wire Store the screw in a safe place Cut the cable ties that fix the damper wire to the pipe and the one that bundles the damper wire a b b b a Damper wire b Cable ties 8 Remove the damper Remove the...

Page 27: ...his makes the connection airtight Attach the damper with 4 screws 4 PH2 SW8 3 2 N m a b b b b c 1 2 a Damper wire b Screw c Damper 15 Connect the damper wires a b c 1 PH2 1 7 N m a Connector b Earth w...

Page 28: ...a b c d BS4A a b b c d BS6 12A a Damper wire b Tie wrap to fix damper wire to piping field supply c Tie wrap to bundle the damper wire field supply d Leftmost wire fixing plate To re install the switc...

Page 29: ...6 Maximum number of indoor units connected to BS units in refrigerant flow through c 64 14 2 Preparing refrigerant piping 14 2 1 Refrigerant piping requirements NOTICE The piping and other pressure co...

Page 30: ...erant flow through with another BS unit and unused branch pipes when no indoor unit is connected to that branch pipe port 5 In case of stopper pipes install stopper pipe insulation tubes accessory Add...

Page 31: ...art from each other Transmission wiring and power supply wiring may cross but may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at l...

Page 32: ...e corresponding indoor unit multiple indoor units connected to the same branch the terminals F1 F2 Indoor unit X on the BS unit to the F1 F2 terminals on the first indoor unit Connect the F1 F2 termin...

Page 33: ...tape e Transmission wiring F1 F2 f Insulation 15 4 To set the DIP switches The DIP switches are located on the PCB s A1P A2P BS6 12A and A3P BS10 12A A1P A2P A3P A B C D E F G H I J K L A B C D E F G...

Page 34: ...MPLE a FAN output terminal b Relay c Extraction fan power supply d Extraction fan SVS output external alarm The SVS output is a potential free contact on terminal X6M that closes in case a leak is det...

Page 35: ...Value Example Description Default situation Mode 1 Mode 2 Description Setting 8 in mode 2 Value 4 in mode 2 16 1 4 To access mode 1 or 2 Initialisation default situation NOTICE Be sure to turn ON the...

Page 36: ...r more than 5 seconds Result Mode 2 is accessed 3 Push BS2 seven times Result Mode 2 setting 7 is addressed 4 Push BS3 1 time the value which is returned depending on the actual field situation is the...

Page 37: ...on the 7 segment display of the outdoor unit This setting must only be made on the leftmost main PCB A1P of each BS unit 2 6 Commissioning check 0 default Incomplete 1 Completed 2 7 Setting to enable...

Page 38: ...he BS unit test run The BS unit test run has to be performed on all BS units in the system before the test run of the outdoor unit The BS unit test run has to confirm that the required safety measures...

Page 39: ...e airflow rate at the air inlet damper of the BS unit Tip Use the duct connection kit EKBSDCK and an anemometer with a funnel to conduct the entire airflow through the anemometer Postrequisite Remove...

Page 40: ...uring BS unit test run Symptom The damper does not open Possible causes Corrective action Incorrect field settings Check if all field settings are made correctly When in parallel or series configurati...

Page 41: ...by your local dealer This chapter gives you an overview of the most possible error codes and their descriptions as they appear on the user interface INFORMATION See the service manual for The complet...

Page 42: ...PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth leak circuit breaker Q L Overload protector Symbol Meaning Q M Thermo switch Q R Residual current device R R...

Page 43: ...or for the product Authorised installer Technical skilled person who is qualified to install the product User Person who is owner of the product and or operates the product Applicable legislation All...

Page 44: ...4P670163 1 2022 02 Copyright 2022 Daikin 4P670163 1 0000000L Verantwortung f r Energie und Umwelt...

Reviews: