Configuration
Installer and user reference guide
97
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
[2-6]
Commissioning check
1
Completed
[2-7]
Setting to enable or disable the ventilated enclosure safety measure of the BS unit.
▪
Choose value "1" if the ventilated enclosure is a necessary safety measure.
▪
Choose value "0" if only an external alarm is required.
See
"13.3 To determine the required safety measures"
This setting only has to be configured on the leftmost main PCB (A1P) of the BS
unit.
[2-7]
Ventilated enclosure
0
Disable
1 (default)
Enable
[2-8]
Setting to assign an address value to the BS unit for the supervisor remote
controller.
In case supervisor remote controllers are used in the system, it is necessary to
assign an address value to the BS unit.
▪
Assign a different address to different BS units.
▪
Use address values that are NOT used in the system elsewhere (e.g. indoor
units).
▪
Do not use address 00. The supervisor remote controller does not display errors
from BS units with address 00.
This setting only has to be configured on the leftmost main PCB (A1P) of the BS
unit.
[2-8]
Description
00~FF (address in HEX
format)
Address for supervisor remote controller
Example
d
a
A3P
A2P
A1P
e
e e
A2P
A1P
e
e
b
c
A1P
e
A1P
Main PCB 1
A2P
Main PCB 2
A3P
Main PCB 3
a
Outdoor unit
b
BS8A unit
c
BS4A unit
d
BS12A unit
e
Address value for supervisor remote controller assigned to main PCB
Transmission wiring
The table below shows an example of address values assigned: