17
|
Configuration
Installer and user reference guide
94
BS4~12A14AJV1B
VRV 5 branch selector unit
4P695527-1 – 2022.02
3
Push BS2 two times.
Result:
Mode 1 setting 2 is addressed:
4
Push BS3 one time. The displays shows the software version.
Result:
Mode 1 setting 2 is addressed and selected, return value is monitored
information.
5
Push BS1 one time to quit mode 1.
17.1.6 To use mode 2
Mode 2 is used to set field settings of the BS unit.
What
How
Changing and accessing the
setting in mode 2
▪
Push BS1 for more than 5 seconds to select
mode 2.
▪
Push BS2 to select the required setting.
▪
Push BS3 1 time to access the selected
setting's value.
To quit and return to the initial
status
Push BS1.
Changing the value of the
selected setting in mode 2
▪
Push BS1 for more than 5 seconds to select
mode 2.
▪
Push BS2 to select the required setting.
▪
Push BS3 1 time to access the selected
setting's value.
▪
Push BS2 to select the required value of the
selected setting.
▪
Push BS3 1 time to validate the change.
▪
Push BS3 again to start operation with the
chosen value.
Example
Checking the content of parameter [2‑7] (to enable or disable the ventilated
enclosure function).
[Mode‑Setting]=Value in this case is defined as: Mode=2; Setting=7; Value=the
value we want to know/change.
1
Make sure the 7‑segment display indication is in the default situation (normal
operation).
2
Push BS1 for more than five seconds.
Result:
Mode 2 is accessed:
3
Push BS2 seven times.
Result:
Mode 2 setting 7 is addressed: