Installation manual
7
VAM350~2000FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415947-1A – 2017.08
Electric wiring
Connection of wiring
Connect the wires in accordance with the diagram of each
system.
All wiring must be performed by an authorized electrician.
All field supplied parts and materials and electric works must
conform to local regulations.
Use copper wire only
Connection of wiring
A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with applicable legislation.
Do not turn on the main switch until all the wiring is completed.
A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
Fit the power supply wiring of each unit with a switch and fuse as
shown in the drawing.
Be sure to make the electric grounding (earth) connection.
Complete system example
Component electrical specifications
Specifications for field supplied fuses and wire
Precautions
1
Do not connect wires of different gauge to the same power
supply terminal. Looseness in the connection may cause
overheating or electric malfunction.
When connecting more than one wire to the power supply
wiring, use a 2 mm
2
(Ø1.6) gauge wire.
When using two power wires of a gauge greater than 2 mm
2
(Ø1.6), branch the line outside the terminal board of the unit in
accordance with electrical equipment standards.
The branch must be sheathed, so as to provide a degree of
insulation equal to or greater than the power supply wiring itself.
2
Keep total current of crossover wiring between indoor units less
than 12 A.
3
Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate
protection.
4
Keep the power supply wiring distant from other wires to prevent
noise.
5
For remote controller wiring, refer to the Installation manual of
the remote controller.
Before obtaining access to terminal devices, all power
supply circuits must be interrupted.
Power supply wiring
Transmission wiring
Switch
Fuse
1
Outdoor unit
2
Indoor unit
3
Power supply
4
Main switch
5
Remote controller
VRV
VRV
VRV
HRV
HRV
1
2
2
3
4
5
5
VAM
350F
500F
650F
800F
1000F
1500F
2000F
Power supply
(*)
(*) MCA: Min. Circuit Amps
MFA: Max. Fuse Amps
P:
Motor Rated Output
FLA: Full
Load
Amps
50 Hz
Power supply Max. 264 V/Min. 198 V
MCA
(A)
0.9
1.3
1.6
2.5
3.0
5.0
5.0
MFA
(A)
16
16
16
16
16
16
16
Fan motor
(*)
P
(kW)
0.08x2
0.08x2 0.106x2 0.21x2
0.21x2
0.21x4
0.21x4
FLA
(A)
0.4
0.6
0.7
1.1
1.3
2.2
2.2
NOTE
For details, refer to ELECTRICAL DATA.
VAM
350F
500F
650F
800F 1000F 1500F 2000F
Type
JVE, 5VE
JVE, 5VE, 7VE
Power supply wiring
Field supplied fuses
16 A
(*)
(*) VAM 1500/2000 requires 2 electrical supplies and fuses.
Wire
H05VV-U3G
Size
Wire size must comply with local regulations
Transmission wiring
Wire
Shield wire (2 wire)
Size
0.75-1.25 mm
2
Same gauge wires
Different gauge wires