VAM350~2000FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P415947-1A – 2017.08
Installation manual
16
Operating the HRV unit using the remote controller of the
VRV-system air conditioner
Please read the manual supplied with the remote controller for more
detailed instructions (optional controllers: BRC1D52 or BRC1E52).
BRC1D52: Remote controller for VRV
When the VRV-system air conditioner is connected with the HRV unit
with a direct duct, the remote controller of the air conditioner cannot
be used to select the VENTILATION mode. To use the HRV unit
without operating the air conditioner, set the air conditioner in the
FAN VENTILATION mode and select the low fan speed.
Independent system
When connecting to Remote controller for HRV
For raising the remote-controlled ventilation air flow rate from "High"
to "Ultra-High", connect the remote controller for the air-conditioner to
HRV and make settings on site.
(Refer to
"List of Settings" on page 13
.)
Keep the switch on the printed circuit board at the factory setting.
Wiring and connections in combination
with "VRV-SYSTEM"
Standard 1-group linked-control system
The remote control of the air conditioner can be used to control
up to 16 air conditioner indoor units and HRV units.
Initial settings can be made for the functions of the HRV units
(pre-cool/pre-heat, ventilation air flow, ventilation mode and
"Fresh-Up").
Use the remote controller of the air conditioner to make the initial
settings for the HRV units.
Refer to "Initial setting" under Item
"List of Settings" on page 13
"
Pre-cool/pre-heat function
When the pre-cool/pre-heat function is set, the HRV unit switches on
at the preset time (30, 45 or 60 minutes) after the VRV-system air
conditioner begins cooling or heating operation. The function is set
OFF at the factory. Therefore, to use this function, the initial setting
must be made using the remote controller of the air conditioner.
If the air conditioner is re-started within two hours after the operation
was stopped, this function does not operate.
1
Operation lamp
2
Operation/stop button
3
Fan speed icon
4
Air filter cleaning time icon
5
Element cleaning time icon
6
Air conditioner fan speed button
7
Air filter cleaning time icon reset button
8
Air conditioner operation mode
9
Inspection button
10
Air flow rate changeover button
11
See
"How to operate with timer" on page 15
12
13
14
Ventilation mode button
15
Operation mode display
16
Defrost/hotstart mode icon
17
Indication of centralized control
15
17
1
2
16
3
4
5
6
7
8
12
11
9
10
14
13
Factory settings:
Do NOT change the switch settings.
SS1 is a setting switch for special purposes. Changing the
settings will stop the unit from operating normally.
1
Master remote controller
4
Switch position: Slave
2
Slave remote controller
5
Remote controller for HRV
3
Switch position: Master
6
Maximum connection line length:
500 m
SS1
NOR
H
M
P1
P2
P1 P2
P1 P2
P1 P2
VRV
HRV
1
2
3
1
Remote controller for air conditioner
3
Maximum connection line length:
500 m
2
Remote controller for air conditioner