9.0 TROUBLE SHOOTING
PROBLEM
POSSIBLE CAUSE
ACTION
LACK OF COOLING EFECT
1. Faulty compressor or lack of
compression.
1. Check discharge pressure for
compression. Inspect compressor
and replace if necessary.
2. Temperature of air entering
evaporator too high.
2. Reduce load to design KW
value.
3. Fouled condenser and/or
evaporator tube surface.
3. Inspect surface and clean.
4. Low refrigerant charge.
4. Repair refrigerant leak, add
refrigerant.
5. Thermal expansion valve out of
adjustment or erratic.
5. Adjust superheat or replace
power element.
6. Improper air flow through
evaporator.
6. Determine flow and adjust
correctly belt tension.
7. Room thermostat not operating
properly.
7. Inspect thermostat and replace
if necessary.
TRIPPING OF
COMPRESSOR(S)
A. DUE TO LOW PRESSURE CUT OUT
1. Reduced air flow through
evaporator.
1. Inspect surface & clean, check
evaporator fan drive
2 Low refrigerant charge.
2. Repair refrigerant leak, add
refrigerant.
3. Broken expansion valve.
3. Replace expansion valve.
4. Restricted refrigerant line.
4. Determine the cause of
restriction and repair.
5. Faulty low pressure cut-out.
5. Replace.
B. DUE TO HIGH PRESSURE CUT-OUT
1. Air in refrigeration system.
1. Re-evacuate refrigeration
system and charge with new
refrigerant.
2. Excess refrigerant charge.
2. Bleed off excess refrigerant.
3. Faulty high-pressure cut-out.
5. Replace.
C. DUE TO COMPRESSOR OVERLOAD TRIPPING
1. Compressor over-current, under
voltage or single phasing.
1. Check electrical supply,
contactors, wiring, and rectify
fault.
2. Excessive discharge pressure.
2. See section B above.
3. Compressor over-heating due to
low refrigerant.
3. Check refrigerant charge (fix
leak), top up refrigerant if
necessary.
4. Compressor motor has a
winding shorted.
4. Replace compressor.
5. Liquid refrigerant in
compressor causing valve plate
damage and lack of compression.
5. Check that crankcase heater is
functioning properly.
6. Defective overload protector.
6. Replace protector.
EXCESSIVE BELT
"SCREAM" WHEN FAN(S)
START UP
1. Slipping belts.
1a. Apply belt dressing/belt
tensioning.
1b. Adjust belt tension correctly.
Summary of Contents for UCQ0060
Page 13: ...13 5 1 UNIT DIMENSION 5 1 1 Outline UCQ60A D L...
Page 14: ...14 5 1 2 Outline UCQ90A D L...
Page 15: ...15 5 1 3 Outline UCQ140A D L...
Page 16: ...16 5 1 4 Outline UCQ180A D L...
Page 17: ...17 5 1 5 Outline UCQ240A L...
Page 18: ...18 5 1 6 Outline UCQ280A L...
Page 19: ...19 5 1 7 Outline UCQ320A L...
Page 20: ...20 5 1 8 Outline UCQ360A L...
Page 21: ...21 5 1 9 Outline UCQ400 520A L...
Page 22: ...22 5 1 10 Outline UCQ570A L...
Page 23: ...23 5 1 11 Outline UCQ710A L...
Page 24: ...24 5 1 12 Outline UCQ870A L...
Page 25: ...25 5 1 13 Outline UCQ940A L...
Page 29: ...29 5 6 Fan Curve 5 6 1 Fan Curve AT 9 9 Model UCQ60 UCQ90...
Page 30: ...30 5 6 2 Fan Curve AT 15 15 Model UCQ140 UCQ180 UCQ240...
Page 31: ...31 5 6 3 Fan Curve AT 18 18 Model UCQ280...
Page 32: ...32 5 6 4 Fan Curve ADH 450 Model UCQ320 UCQ360 UCQ710...
Page 33: ...33 5 6 5 Fan Curve ADH 500 Model UCQ400 UCQ520 UCQ870 UCQ940...
Page 34: ...34 5 6 6 Fan Curve ADH 560 Model UCQ570...
Page 37: ...37 6 1 WIRING DIAGRAM 6 1 1 Wiring Diagram UCQ60AE UCQ90AE UCQ140AE UCQ180AE...
Page 38: ...38 6 1 2 Wiring Diagram UCQ240AE UCQ280AE...
Page 39: ...39 6 1 3 Wiring Diagram UCQ320AE UCQ360AE...
Page 40: ...40 6 1 4 Wiring Diagram UCQ400AE UCQ520AE...
Page 41: ...41 6 1 5 Wiring Diagram UCQ570AE...
Page 42: ...42 6 1 6 Wiring Diagram UCQ710AE UCQ870AE...