background image

44 

 

7.0 COMMISIONING 

 

PRE-STARTUP REQUIREMENTS 

1. Inspect the unit for shipping or installation damage. 

2. Verify the unit is completely and properly installed with ductwork connected. Verify that all construction debris is 
removed and filters are clean. 

3. With all electrical disconnects open, check all electrical connections to be sure they are tight. 

4. Visually check for refrigerant piping leaks. 

5. The compressor oil level should be maintained so that an oil level is visible in the sight glass. The oil level only 
can be ascertained when the compressor is running in stabilized conditions, ensuring there is no liquid refrigerant in 
the lower shell of the compressor. The oil level should be between ¼ and ¾ of the sight glass with compressor 
running. At shutdown, the oil level can fall to the bottom limit of the oil sight glass. 

7. Visually inspect field wiring (power and control). Wiring must meet local codes. 

10. Check the tightness of setscrews in bearings, drives, and fan wheels 

11. Verify the supply fan rotates freely. Verify proper drive alignment of the supply fan. 

12. Verify the unit condenser water connections and condensate drain connections have been piped & closed for the 
end which not been used. 

13. Verify that all mechanical and electrical inspections have been completed per local codes. 

14. Make sure the trap for the main evaporator drain pan has been primed by pouring water in the pan until water 
exits the condensate drain line. 

15. Connect wiring for water flow switch or remote switch by removing the jumper wire on the desired terminal 
(refer wiring diagram on the unit).  

15. Apply 3-phase power to the unit and verify that it falls within the specified voltage range. 

16. Check for voltage imbalance. Voltage imbalance should not exceed 2% of the average voltage. 

 

 

CRANKCASE HEATERS

 

The purpose of the crankcase heater is to prevent the migration of refrigerant to the crankcase during shutdown, to 
assure proper lubrication on the compressor during start-up. 

The  heater  is interlocked  with the  compressor  contactor  and is  not  controlled  directly  by  the  controller.  When  the 
compressor is OFF, a normally closed auxiliary contact on the compressor contactor closes the circuit and energize 
the crankcase heater. 

 

CAUTION! 

 

Do not bypass the high or low pressure switch during unit operation. 

 

Do not bypass compressor and fan overload protector.  

 

The crankcase heater must be turned on a minimum of 12 hours prior to start the compressor. 

 

The crankcase heater must be always energized when the unit is not running.  

 

Summary of Contents for UCQ0060

Page 1: ...1 WATER COOLED SELF CONTAINED AIR CONDITIONER INSTALLATION OPERATION MAINTENANCE IOM NO O WCP16 DEC20 1 Scan QR code to download the latest version of IOM...

Page 2: ...ble them to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any re...

Page 3: ...4 Specification UCQ60 940 9 Table 5 Performance Table UCQ60 940 11 5 1 UNIT DIMENSION 13 5 1 1 Outline UCQ60A D L 13 5 1 2 Outline UCQ90A D L 14 5 1 3 Outline UCQ140A D L 15 5 1 4 Outline UCQ180A D L...

Page 4: ...gram UCQ60AE UCQ90AE UCQ140AE UCQ180AE 37 6 1 2 Wiring Diagram UCQ240AE UCQ280AE 38 6 1 3 Wiring Diagram UCQ320AE UCQ360AE 39 6 1 4 Wiring Diagram UCQ400AE UCQ520AE 40 6 1 5 Wiring Diagram UCQ570AE 41...

Page 5: ...r free blow applications Each unit contains Single or multiples hermetic scroll compressors Water cooled condensers Single or multi circuit evaporator Thermal expansion valves Interconnecting refriger...

Page 6: ...ten request for inspection by the carrier s agent should be made at once 2 2 LOCATION AND CLEARANCES The following guidelines should be used to select a suitable location for the unit installation Ver...

Page 7: ...UCQ60A D 175 177 UCQ90A D 261 265 UCQ140A D 441 448 UCQ180A D 495 501 UCQ60A L 160 162 UCQ90A L 241 245 UCQ140A L 416 423 UCQ180A L 470 476 UCQ240A L 558 566 UCQ280A L 657 667 UCQ320A L 728 736 UCQ36...

Page 8: ...units factory has provided the internal vibration isolators for compressors If additional vibration isolation is desired neoprene is recommended under 4 corners of unit Care must be exercised to isol...

Page 9: ...SPZ 85 SPZ 100 SPZ 80 SPZ 112 SPZ 80 SPZ 95 SPA 125 1 1 4 male thread 1 side 3 14 595 X 595 4 290 X 595 2 Capacity Cooling 16 9 25 6 38 8 51 58 87 133 174 Dimension 1068 1118 1410 1460 1486 1536 1486...

Page 10: ...6 33 5 40 9 49 9 54 5 Pressure drop kPa 13 16 23 12 12 34 13 15 16 Pulley size mm SPA 236 SPA 250 SPA 315 SPA 400 SPA 224 SPA 355 SPA 315 1 1 1 1 1 1 2 2 2 Design speed RPM 817 843 843 801 834 657 86...

Page 11: ...8 113 4 13 20 144 4 107 8 14 73 73 87 26 7 19 4 184 9 126 8 11 20 173 9 119 5 13 35 166 0 119 8 14 80 32 23 204 9 136 3 11 32 184 7 126 8 13 53 181 3 126 3 14 90 UCQ0240 21 15 215 8 151 9 14 82 196 5...

Page 12: ...6 0 473 6 36 3 636 6 444 3 44 1 629 7 442 3 49 8 UCQ0710 21 15 670 5 515 2 46 2 610 6 481 0 56 7 571 6 465 6 61 2 79 99 26 7 19 4 745 1 545 6 47 4 700 7 524 3 57 6 668 7 514 7 62 5 32 23 882 0 626 1 4...

Page 13: ...13 5 1 UNIT DIMENSION 5 1 1 Outline UCQ60A D L...

Page 14: ...14 5 1 2 Outline UCQ90A D L...

Page 15: ...15 5 1 3 Outline UCQ140A D L...

Page 16: ...16 5 1 4 Outline UCQ180A D L...

Page 17: ...17 5 1 5 Outline UCQ240A L...

Page 18: ...18 5 1 6 Outline UCQ280A L...

Page 19: ...19 5 1 7 Outline UCQ320A L...

Page 20: ...20 5 1 8 Outline UCQ360A L...

Page 21: ...21 5 1 9 Outline UCQ400 520A L...

Page 22: ...22 5 1 10 Outline UCQ570A L...

Page 23: ...23 5 1 11 Outline UCQ710A L...

Page 24: ...24 5 1 12 Outline UCQ870A L...

Page 25: ...25 5 1 13 Outline UCQ940A L...

Page 26: ...to follow the recommendations of local authorities They can supply the installer with the proper building and safety codes required for a safe and proper installation The water piping should be insta...

Page 27: ...per foot The drain pan and the trap should be kept clean through periodic cleaning A clean out should be installed as standard as part of the trap assembly to aid in cleaning Condensate Drain Insulati...

Page 28: ...ight duct having the same dimensions as the fan outlet be used This duct should be at least 3 equivalent duct diameters in length prior to installing any elbows or transition See the following Table 6...

Page 29: ...29 5 6 Fan Curve 5 6 1 Fan Curve AT 9 9 Model UCQ60 UCQ90...

Page 30: ...30 5 6 2 Fan Curve AT 15 15 Model UCQ140 UCQ180 UCQ240...

Page 31: ...31 5 6 3 Fan Curve AT 18 18 Model UCQ280...

Page 32: ...32 5 6 4 Fan Curve ADH 450 Model UCQ320 UCQ360 UCQ710...

Page 33: ...33 5 6 5 Fan Curve ADH 500 Model UCQ400 UCQ520 UCQ870 UCQ940...

Page 34: ...34 5 6 6 Fan Curve ADH 560 Model UCQ570...

Page 35: ...nd protect the unit The control system includes compressor and fan overload protection phase protection high and low pressure cutouts to guard against compressor damage due to high discharge pressure...

Page 36: ...1 UCQ280A L 260 31 56 1 10 7 7 5 1 81 137 UCQ320A L 158 16 7 31 2 14 2 10 1 84 115 UCQ360A L 197 20 7 36 2 20 5 15 1 102 138 UCQ400A L 147 15 8 28 3 20 5 15 1 112 140 UCQ520A L 197 20 7 36 3 20 5 15 1...

Page 37: ...37 6 1 WIRING DIAGRAM 6 1 1 Wiring Diagram UCQ60AE UCQ90AE UCQ140AE UCQ180AE...

Page 38: ...38 6 1 2 Wiring Diagram UCQ240AE UCQ280AE...

Page 39: ...39 6 1 3 Wiring Diagram UCQ320AE UCQ360AE...

Page 40: ...40 6 1 4 Wiring Diagram UCQ400AE UCQ520AE...

Page 41: ...41 6 1 5 Wiring Diagram UCQ570AE...

Page 42: ...42 6 1 6 Wiring Diagram UCQ710AE UCQ870AE...

Page 43: ...43 6 1 7 Wiring Diagram UCQ940AE...

Page 44: ...piped closed for the end which not been used 13 Verify that all mechanical and electrical inspections have been completed per local codes 14 Make sure the trap for the main evaporator drain pan has be...

Page 45: ...me in reverse direction will have no negative impact but prolonged running in reverse direction may cause premature failure UCQ60 90 140 180 320 360 400 520 E is supplied with external Supply Monitori...

Page 46: ...ed when the compressor is running in stabilized conditions to ensure that there is no liquid refrigerant in the lower shell of the compressor When the compressor is running in stabilized conditions th...

Page 47: ...ype Setting Force to Deflect Belt 15mm per Meter of Span Small Pulley Datum Diameter mm 1 3 x Basic Setting Force kgf Minimum Maximum SPZ 63 1 2 1 7 67 1 3 1 9 71 1 5 2 0 75 1 5 2 1 80 1 6 2 3 85 1 7...

Page 48: ...o control Total Alkalinity 300 ppm as CaCo3 Bleed off to control Chloride 120 ppm as CL Bleed off to control Fe value 2 5 ppm Add CWT 3753 to control Total Hardness 300 ppm as CaCo3 Bleed off to contr...

Page 49: ...erant 3 Broken expansion valve 3 Replace expansion valve 4 Restricted refrigerant line 4 Determine the cause of restriction and repair 5 Faulty low pressure cut out 5 Replace B DUE TO HIGH PRESSURE CU...

Page 50: ...essure or overload relay tripped manual reset 10 Comp 3 low pressure manual reset 11 Comp 4 high pressure or overload relay tripped manual reset 12 Comp 4 low pressure manual reset 13 Heater 1 failure...

Reviews: