5.4.2 Condensate drain of the internal air coil
The condensate collection tray is provided with a male R 1" threaded pipe for connection.
Fig. 5 Connection to the condensate collection tray
On the condensate discharge pipe it must be installed a proper syphon in order to avoid that outdoor air may be
blown through it.
It is good practice to make a syphon straight after the connection to the tray.
H 80 mm
H
H
/2
Fig. 6 Syphon for condensate discharge pipe.
The pipe draining the condensate must never be connected to waste water drains or run-off water drains, only to
rainwater systems to prevent any foul smelling gases from being sucked back.
5.4.3 Condensate drain of the external air coil
The condensate collection tray is provided with a male R 1" threaded pipe for connection.
Fig. 7 Connection to the condensate collection tray
The condensate drain of the external air coil can be left free.
Any condensate pipework connected to the unit must be protected from freezing.
5.4.4 Connection to the humidifier
Refer to the section titled “Options and accessories” where a description of the humidifier installation procedure is
given.