R407C is a zeotropic refrigerant mixture which has zero 
ozone depletion potential and thus conformed to Montreal 
Protocol regulation. It requires Polyester oil (POE) oil 
for its compressor's lubricant. Its refrigerant capacity and 
performance are about the same as the refrigerant R22.

 

POE or PVE oil is used as lubricant for R407C compressor, 
which is different from the mineral oil used for R22 
compressor. During installation or servicing, extra precaution 
must be taken not to expose the R407C system too long 
to moist air. Residual POE or PVE oil in the piping and 
components can absorb moisture from the air.

 

Refrigerant R407C is more easily affected by dust of 
moisture compared with R22, make sure to temporarily 
cover the ends of the tubing prior to installation.

SERVICE OF THE FILTER

 Remove any dust adhering to the filter by using a vacuum cleaner or wash in lukewarm water (below 40°C) with a 
neutral cleaning detergent.
Rinse the filter well and dry before placing it back onto the unit.
Do not use gasoline, volatile substances or chemicals to clean the filter.
Clean the filter at least once every 2 weeks. Or more frequently if neccesary.

Filter Position

The 

fi

 lters are mounted in front of the indoor heat exchanger.

* (Air 

fi

 lter : special order or 

fi

 eld supply)



UAT(Y)(P)60, 80, 100, 120, 150, 200A

UAT(Y)(P)250, 300, 360, 420A

Filter

Filter

Filter cover

Filter cover

Service panel

removed when servicing
note: both side for unit 150, 200A

removed when servicing

SPECIAL PRECAUTIONS WHEN DEALING WITH R407C UNIT

SERVICE AND MAINTENANCE

No additional charge of compressor oil is permitted.
No other refrigerant other than R407C.
 Tools specifically for R407C only (must not be used for 
R22 or other refrigerant)

Manifold gauge and charging hose
Gas leak detector 
Refrigerant cylinder / charging cylinder
Vacuum pump c/w adaptor
Flare tools
Refrigerant recovery machine

 

Filter-dryer must be installed along the liquid line for 
all R407C air conditioners. This is to minimise the 
contamination of moisture and dirt in the refrigerant 
system. Filter-dryer must be of molecular sieve type. For 
a heat-pump system, install a two-way flow filter-dryer 
along the liquide line.



i)
ii)
iii)
iv)
v)
vi)

Note is valid for Turkey only: The lifetime of our products is ten (10) years

1 IM-RTA-0612(4)DK-EN.indd   11

1 IM-RTA-0612(4)DK-EN.indd   11

6/26/14   3:18:18 PM

6/26/14   3:18:18 PM

Summary of Contents for UAT100A

Page 1: ...Package Units Manuel D installation Conditionneurs D air En Toiture Installationshandbuch Kompaktanlage F r Dachmontage Manuale Di Installazione Unit A Pacchetto Per Installazione Sul Tetto Manual De...

Page 2: ...CVR IM RTA 0612 4 DK EN indd 2 CVR IM RTA 0612 4 DK EN indd 2 6 26 14 3 05 50 PM 6 26 14 3 05 50 PM...

Page 3: ...0 150 150 20 668 24 125 125 24 208 224 208 668 224 208 224 60 150 150 150 150 150 150 60 1020 10 Supply air duct flange 21 3 Holes 51 1300 51 173 1020 107 265 265 1000 4 15X25 Mtg holes B 1342 1300 13...

Page 4: ...T80 100A only 9 9 C A 2 Down flow A B C O 1670 1200 H P 1800 1330 1990 1744 123 51 123 51 46 25 1990 2032 2082 235 235 4 15X25 Mtg holes 46 25 B B 25 25 2032 15 72 200 200 200 200 200 200 200 200 72 1...

Page 5: ...2 1990 264 294 51 51 46 25 25 15 91 10 1990 2032 2082 46 25 1782 2032 235 235 25 25 15 2032 25 200 200 200 200 200 200 200 200 91 10 10 46 46 140140 372 359 120120 59 5 59 5 86 10 180 180 180 180 180...

Page 6: ...SER AIR INLET 3180 3100 3148 80 100 660 1974 1650 210 2252 782 SUPPLY AIR 62 892 526 RETURN AIR DRAIN 1 RETURN AIR SUPPLY AIR 516 1220 516 DETAIL A 27 5 15 22 5 A X Y 360 1730 1130 420 1800 1080 Y X C...

Page 7: ...ore turning off the power supply set the remote controller s ON OFF switch to the OFF position to prevent the nuisance tripping of the unit If this is not done the unit s fans will start turning autom...

Page 8: ...ocation For Installation Install the unit in such way that air distributed by the unit cannot be drawn in again as in the case of short circuit of discharge air Allow sufficient space for maintenance...

Page 9: ...m Spreader Bar Chain Lifting Holes for shackle 4 corners Chain Hanger Bracket A 70mm B 2C C 2X ESP INSTALLATION OF THE UNIT 1 5 Drain piping A 1 FPT condensate drain fitting is provided The drain pipe...

Page 10: ...ce Condenser inlet Condenser inlet min clearance 1500 1000 Electrical control circuit compressor service 300 300 700 1000 UAT Y P 150 200A 500 min clearance UAT Y P 250 300 360 420A Electrical control...

Page 11: ...Remove duct flange Remove duct flange Re install supply air cover Re install fan assy Remove Remove low cover Remove supply air cover 2 Additional casing leg Accessory parts 1 Additional side inlet co...

Page 12: ...H x THICKNESS mm 840 x 667 x 1 1370 x 735 x 1 860 x 505 600 x 4 HEAT PUMP R407C MODEL UATP60A UATP80A UATP100A UATP120A UATP150A REFRIGERANT R407C REFRIGERANT CHARGE kg 4 6 4 6 5 9 5 6 3 9 x 2 EVAPORA...

Page 13: ...RRENT LRA COMP A 81 x 2 118 x 2 174 x 2 175 215 215 x 2 HEAT PUMP R407C MODEL UATYP60A UATYP80A UATYP100A UATYP120A UATYP150A POWER SUPPLY V ph Hz 400 3N 50 VOLTAGE RANGE V 380 415 MAX CONTINUOUS CURR...

Page 14: ...NOTE While installing the circuit breaker onto the unit make sure that the screws do not damage the components e g coil inside of the unit The circuit breaker also can be installed without attaching t...

Page 15: ...F1 51F1 47 N T S R N T S R 52C 47 51F1 52F 51C2 TB2 3 52C2 52C1 51C1 X1 X2 PCB 52F2 52F3 TB1 47 F1 T1 51C TB1 F1 X1 X2 X3 Terminal Block for power supply wires Arrangement of terminal block for contro...

Page 16: ...g Only Unit Cooling Mode For Heat Pump Model Outdoor temp C DB Indoor temp C WB Indoor temp C WB 9 15 27 18 5 15 20 10 0 5 20 30 10 25 Indoor temp C DB Heat pump Heat Pump Unit Only Outdoor temp C WB...

Page 17: ...lean the filter at least once every 2 weeks Or more frequently if neccesary Filter Position The filters are mounted in front of the indoor heat exchanger Air filter special order or field supply UAT Y...

Page 18: ...r reset circuit breaker Power supply wiring phase incorrect Modify the wiring phase Compressor does not operate in 3 min after unit has started Protection against frequent starting Wait for 3 min for...

Page 19: ...CVR IM RTA 0612 4 DK EN indd 3 CVR IM RTA 0612 4 DK EN indd 3 6 26 14 3 05 50 PM 6 26 14 3 05 50 PM...

Page 20: ...ale Il fabbricante mantiene il diritto di cambiare qualsiasi specificazione e disegno contenuti qui senza precedente notifica En caso de conflicto en la interpretaci n de este manual y en su traducci...

Page 21: ...i Yakac k D 100 Kuzey Yanyol Caddesi No 49 1 2 Kartal stanbul Head office Umeda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan Tokyo office JR Shinagawa East Bldg 2 18 1 Konan Minato k...

Reviews: