18
Advanced Setup
About Advanced Features & Operation
SET
NEXT
Press NEXT
to advance
RESET
FILTER
Press RESET
FILTER
Press and hold the
RESET FILTER button
to reset the filter
counter to 0 and
remove the
icon from the display.
Adjust the number of
hours the blower will
run before the
icon appears on the
display. 0 = off.
Slide the Program Switch to OFF or RUN to exit Advanced Setup.
CYCLES PER HOUR - The Cycles Per Hour setting (page 17)
monitors the number of times per hour your HVAC unit may
energize. For example, at a setting of 6 cycles per hour the HVAC
unit will only be allowed to energize once every 10 minutes. The
Cycles Per Hour limit may be temporarily overridden by pressing
the WARMER or COOLER button.
FILTER ICON - The
icon will appear after a set number
of hours for fan run time (see above) has been achieved. This
counter keeps track of the number of hours of fan run time
whether the fan is energized in the heating or cooling modes,
or in stand alone operation.
Actual hours of
fan operation