RCN Configuration Table (Continued)
= WSHP Configuration
D4
Flash
Count
Function Selection
D3
Flash
Count
Description
Table 5 - Occupancy Timeout
5
2-Minute Delay
1
System responds to an unoccupied status condition within 2-minutes.
1-Hour Delay
2
System responds to an unoccupied status 1-hour after condition is sensed.
4-Hour Delay
3
System responds to an unoccupied status 4-hours after condition is sensed.
8-Hour Delay
4
System responds to an unoccupied status 8-hours after condition is sensed.
16-Hour Delay
5
System responds to an unoccupied status 16-hours after condition is sensed.
24-Hour Delay
6
System responds to an unoccupied status 24-hours after condition is sensed.
Table 6 - Reversing Valve Logic
6
B - Reversing Valve Logic
1
Heat Pump Control Mode: Reversing valve output active in call for HEATING.
O - Reversing Valve Logic
2
Heat Pump Control Mode: Reversing valve output active in call for COOLING.
Notes:
1.
The D5 LED will light during the short-cycle delay period.
2.
The D3 LED will flash when the RCN has gone into unoccupied status.
3.
This device should be powered with a Class 2, UL-listed transformer.
4.
The output from G1, G2, G3, W, O/B & Y switches is 24VAC (R terminal potential) @ 0.50 amps each, max.
5.
Speed-hunt: Automatically sets the fan speed based on departure from the set-point temperature. 1º from set-point = Fan 1, 2º from set-point = Fan 2, 3º from set-
point = Fan 3.