3-3. Wall embedded piping

• Insert the drain hose to this depth so it won’t be pulled out of the drain 

pipe.

Inner wall

Vinyl chloride 
drain pipe 
(VP-30)

Drain hose

1-15/16” (50mm) 
or more

Insert the drain 
hose to this depth 
so it won’t be pulled 
out of drain pipe.

Outer wall

4. 

Wiring

With a multi indoor unit

, install as described in the installation manual supplied with the Multi outdoor unit.

1) As shown in the illustration on the right-hand side, insert 

the wires including the ground wire into the conduit and 
secure them with lock nut onto the conduit mounting plate.

2) Insert the wires including the ground wire into       tube.
3) Strip wire ends (9/16 inch (15mm)).
4) Match wire colors with terminal numbers on indoor and 

outdoor unit’s terminal blocks and firmly screw wires to the 
corresponding terminals. 

5) Connect the ground wires to the corresponding terminals.
6) Pull the wires and check that the wires are securely fixed 

to the terminal block.

7) In case of connecting to an adapter system, run the 

remote controller cable and attach the S21. (Refer to P5 
when connecting to an HA system.)

8) Shape the wires so that the service lid fits securely, then 

close service lid.

1

2

3

1 2 3

GR

L

1

L

2

Conduit mounting 
plate

Lock nut

Back

Conduit 

Terminal block
Electrical component box

Use the specified wire type.

Wire retainer

Shape wires so that the 
service lid will fit securely.

Tube

J

Use AWG16 if the connection wire 
length is less than 32.8ft (10m), or 
AWG14 if it is 32.8ft (10m) or more.

Outdoor unit

Indoor 
unit

Use AWG 14 wires.

WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• When carrying out wiring connection, take care not to pull at the conduit.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

J

01_EN_3P297301-2.indd   9

10/18/2011   2:00:52 PM

Summary of Contents for SUPER MULTI NX FTXS15LVJU

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series English Français Español MODELS FTXS15LVJU FTXS18LVJU FTXS24LVJU 00_CV_3P297301 2 indd 1 10 18 2011 10 19 50 AM ...

Page 2: ... or lightning rods because lightning strikes could cause a severe shock hazard resulting in severe injury or death and to gas pipes because a gas leak could result in an explosion which could lead to severe injury or death WARNING Installation shall be left to the authorized dealer or another trained professional Improper installation may cause water leakage electrical shock fire or equipment dama...

Page 3: ... for a means of transportation It is dangerous Electrical work must be performed in accordance with the NEC CEC by authorized personnel only Accessories Indoor unit A M Mounting plate 1 Remote controller holder 1 Tube 1 Mounting plate fixing screw 3 16 1 M4 25mm 9 Fixing screw for remote controller holder 1 8 13 16 M3 20mm 2 Operation manual 1 Titanium apatite photocatalytic air purifying filter 2...

Page 4: ...6mm Screw cover 3 pcs M Wrap the thermal insulation pipe with the finishing tape from bottom to top Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe hole gap with putty The mounting plate should be installed on a wall which can support the weight of the indoor unit How to attach the indoor unit Ho...

Page 5: ...al method 1 Remove front panel to remove the air filter 2 Remove 6 screws from the front grille 3 In front of the mark of the front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand mark area 3 locations Upper hook Push down Upper hook When there is no work space because the unit is close to ceiling ...

Page 6: ...late electrical cover Main body HA connector S21 HA connector S21 Lay the HA cord as shown in the figure Refrigerant Piping Work With a multi indoor unit install as described in the installation manual supplied with the Multi outdoor unit 1 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the pipe 3 Put the...

Page 7: ... dust and moisture 2 All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no flare cap is available cover the flare mouth with tape to keep dirt or water out Be sure to place a cap Rain 2 2 Selection of copper and heat insulation materials When using commercial copper pipes and fittings observe the following 1 Insulation material Polyethylene foam Heat transfer rate 0...

Page 8: ... The removed pipe port cover can be kept in the mounting plate pocket Removed pipe port cover A Mounting plate ϕ3 1 8 ϕ80 ϕ3 1 8 ϕ80 Drain hose position 5 1 4 134 unit inch mm Use tape measure as shown Position the end of tape measure at 2 Boring a wall hole and installing wall embedded pipe For walls containing metal frame or metal board be sure to use a wall embedded pipe and wall cover in the f...

Page 9: ...et drain plug No gap Do not apply lubricating oil refrigeration oil when inserting Application of causes deterioration and drain leakage of the plug Insert a hexagonal wrench 3 16 4mm 4 Shape the refrigerant pipes along the pipe path marking on the mounting plate 5 Pass drain hose and refrigerant pipes through the wall hole then set the indoor unit on mounting plate hooks using the markings at the...

Page 10: ...xed to the terminal block 7 In case of connecting to an adapter system run the remote controller cable and attach the S21 Refer to P5 when connecting to an HA system 8 Shape the wires so that the service lid fits securely then close service lid 1 2 3 1 2 3 GR L1L2 Conduit mounting plate Lock nut Back Conduit Terminal block Electrical component box Use the specified wire type Wire retainer Shape wir...

Page 11: ...or section of the extension hose Indoor unit drain hose ϕ5 8 ϕ16mm Extension drain hose Heat insulation tube field supply 4 When connecting a rigid polyvinyl chloride pipe nominal diameter 1 2 inch 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use any commercially available drain socket nominal diameter 1 2 inch 13mm as a joint Drain hose supplied with the...

Page 12: ...he power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again Trial operation from remote controller 1 Press ON OFF button to turn on the system 2 Press TEMP button 2 locations and MODE button at the same time 3 Press MODE button twice T will appear on the display to indicate that trial operation mode is selected 4 Trial operation term...

Page 13: ...12 English MEMO 01_EN_3P297301 2 indd 12 10 18 2011 2 00 52 PM ...

Page 14: ...Two dimensional bar code is a code for manufacturing 3P297301 2 M11B120 1111 HT 00_CV_3P297301 2 indd 2 10 18 2011 10 19 50 AM ...

Reviews: