2.14 Thermistors
2.14.1 Refrigerant side thermistors
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a mechanical check of the specific thermistor
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
1
Locate the thermistor and remove the insulation if needed. Check that the
thermistor is correctly installed and that there is thermal contact between the
thermistor and the piping or ambient (for air thermistor).
Is the thermistor correctly installed
(thermal contact between the
thermistor and the piping)?
Action
Yes
Perform an electrical check of the
specific thermistor, see
No
Correctly install the thermistor, see
112].
To perform an electrical check of the specific thermistor
1
First perform a mechanical check of the thermistor, see
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2
Locate the thermistor.
INFORMATION
Remove the thermistor from its holder if not reachable with a contact thermometer.
3
Measure the temperature using a contact thermometer.
Name
Symbol
Location (PCB) Connector
(pins)
Type
Air thermistor
R1T
Main (O/U)
S90:1‑2
1
Heat
exchanger
thermistor
R2T
Main (O/U)
S90:3‑4
1
Discharge pipe
thermistor
R3T
Main (O/U)
S90:5‑6
1