Daikin Skyline IM 777-8 Installation And Maintenance Manual Download Page 32

IM 777-8 • Skyline Air Handler 32 www.DaikinApplied.com

s

ervICe

 

and

 M

aInTenanCe

 

s

ervICe

 

and

 M

aInTenanCe

 

Periodic Maintenance 

1.  Check all moving parts for wear every six months. 
2.  Check bearing collar, sheave, and wheel hub setscrews, 

sheave capscrews, and bearing hold-down bolts for 

tightness every six months. 

3.  Annually check and snug all electrical connections. 

Inspect for signs of water damage such as corrosion 

and repair if necessary. Check ground conductor and 

connection integrity. Service if needed. 

Ball Bearing Lubrication 

 

CAUTION

Bearing overheating potential. Can damage the equipment. 

Do not over-lubricate bearings. Use only a high grade mineral 

grease with a 200°F safe operating temperature. See below 

for specific recommended lubricants. 

Motor Bearings 

Supply and return fans—Supply and return fan motors should 

have grease added after every 2000 hours of operation. Using 

the following procedure, re-lubricate the bearings while the 

motor is warm, but not running. Use one of the greases shown 

in 

Table 24

NOTE: 

Direct Drive Class II fans that are supplied with TECO 

motors have double shielded bearings on frame sizes 

140T-280T. These bearings are pre-packed with a long 

life grease and are not re-greaseable. Larger frame 

size TECO motors are re-greaseable and follow the 

same lubrication recommendations as all other motors. 

1.  Remove and clean upper and lower grease plugs. 
2. 

Insert a grease fitting into the upper hole and add clean 

grease (

Table 24

) with a low pressure gun. 

3. 

Run the motor for five minutes before replacing the plugs. 

NOTE: 

Specific greasing instructions are located on a tag 

attached to the motor. If special lubrication instructions 

are on the motor, they supersede all other instructions. 

Table 24: Recommended Lubricants and Amounts for Fan 

Motor Bearings 

Mfr . Grease

 NEMA Size

Amount to Add 

(oz .)

Texaco, Polystar  

or  

Polyrex EM (Exxon Mobil)  

or  

Rykon Premium #2 

 

or  

Penzoil Pen 2 Lube

56 to 140

0.08

140

0.15

180

0.19

210

0.30

250

0.47

280

0.61

320

0.76

360

0.81

400

1.25

440

2.12

Fan Shaft Bearings 

Any good quality lithium or lithium complex base grease, using 

mineral oil, conforming to NLGI grade 2 consistency, and an oil 

viscosity of 455-1135 SUS at 100°F (100-200 cSt at 40°C) may 

be used for re-lubrication. 
Compatibility of grease is critical. Re-lubricatable bearings are 

supplied with grease fittings or zerks for ease of lubrication with 

hand or automatic grease guns. Always wipe the fitting and 

grease nozzle clean. 

 

CAUTION

For safety, stop rotating equipment. Add one half of the 

recommended amount shown in 

Table 24

. Start bearing, and 

run for a few minute Stop bearing and add the second half 

of the recommended amount. A temperature rise, sometimes 

30°F (1°C), after re-lubrication is normal. Bearing should 

operate at temperature less than 200°F (94°C) and should 

not exceed 225°F (107°C) for intermittent operation. For a re-

lubrication schedule, see 

Table 25

. For applications that are 

not in the range of the table, contact Daikin. 

 

CAUTION

The tables below state general lubrication recommendations 

based on our experience and are intended as suggested or 

starting  points  only.  For  best  results,  specific  applications 

should be monitored regularly and lubrication intervals and 

amounts adjusted accordingly. 

Table 25: Re-lubrication Intervals 

(Use NLGI #2 Lithium or Lithium Complex Grease)

Speed

Bearing 

Temperature

Cleanliness

Relub . intervals

100 rpm

Up to 120°F 

(50°C)

Clean

6 to 12 months

500 rpm

Up to 150°F 

(65°C)

Clean

2 to 6 months

1000 rpm

Up to 210°F 

(100°C)

Clean

2 weeks to 2 

months

1500 rpm

Over 210°F 

(100°C) to 250°F 

(120°C)

Clean

Weekly

Above 1500 rpm

Up to 150°F 

(65°C)

Dirty/wet

1 week to 1 month

Max catalog rating

Over 150°F 

(65°C) to 250°F 

(120°C)

Dirty/wet

Daily to 2 weeks

Above 250°F 

(120°C)

Contact Browning

Summary of Contents for Skyline IM 777-8

Page 1: ...Installation and Maintenance Manual IM 777 8 Group Applied Air Systems Part Number IM 777 Date March 2014 Skyline Outdoor Air Handler...

Page 2: ...s 14 Internal Isolation Assembly Adjustment 18 OSHPD Seismic Anchoring Mounting 20 Electrical Installation 21 Wiring 21 Operation Guidelines 22 Startup Checks 22 Before Starting the Unit 22 VFD Setup...

Page 3: ...el and are inspected thoroughly before leaving the factory Take care during installation to prevent damage to units 3 Take special care when handling the blower section All fans are dynamically balanc...

Page 4: ...on galvanized surfaces Belt driven fans Reduce belt tension by at least 50 or remove the belts Remove belts if they will be subjected to temperatures exceeding 85 F to avoid deterioration Remove belt...

Page 5: ...supplied with VFDs Figure 1 Servicing Space Requirements Figure 2 Service Clearance for Electrical Power Devices Rigging Skyline air handlers ship as separate sections completely assembled or in modu...

Page 6: ...nt attached on the leaving air side of the shipping section that seals against the frame channel on the entering air side of the adjoining The splice joint is insulated and provides an air tight seal...

Page 7: ...ping screw to secure the bases together f For certain Custom Air Handling units use the provided section joining plates to fasten sections together Space them as shown in Figure 9 Using the provided 1...

Page 8: ...he flat head Torx 30 fasteners in the corner of the frame channels Then pull the frame channel out the side Remove any panel screws that are within one inch of the of the frame since they are engaged...

Page 9: ...available inside the unit for conduit or pipe routing b Do not locate holes in a panel that provides access to key maintenance components such as filters and fan assemblies c Do not locate where the c...

Page 10: ...and does not interfere with other vital components Duct Connections Use flexible connectors on the outlet and inlet duct connections of all units Do not position down flow fans over air ducts that ar...

Page 11: ...shaft torque is 205 inches pound Greater rotation or torque can cause equipment damage Face and Bypass Section Mounting Internal and external face and bypass sections are mounted together using the i...

Page 12: ...ls WARNING Use all lifting points Improper lifting can cause severe personal injury and property damage CAUTION Lifting points may not be symmetrical to the center of gravity of the unit Ballast or un...

Page 13: ...M 777 8 Skyline Air Handler Figure 22 Typical Vestibule Figure 23 Caulking the Vestibule Roof Cap Figure 24 Detail of Mounting Screws Figure 25 Additional Caulking SHOWN SPLICE COLLAR DETAIL A UNIT TO...

Page 14: ...ply heat to the body of the expansion valve The thermostatic expansion valve must be the external equalizer tube type Connect the 1 4 inch diameter external equalizer tube provided on the coil to the...

Page 15: ...low Valves Do not use modulating steam valves on high pressure systems Properly size modulating valves Do not undersize Avoid freezing conditions entering air temperatures below 35 F Daikin strongly r...

Page 16: ...Pressure to 25 psi 5GA or 8GA coils Note that the addition of a vacuum breaker to permit the coil to drain during shutdown 5TA 8TA or 5HA coils Conden sate is lifted to overhead return main 5JA or 8J...

Page 17: ...o be heated by a hot water coil carefully design the system to provide thorough mixing before air enters the coil To prepare coils for winter operation See Winterizing Water Coils on page 39 Drain Pan...

Page 18: ...orz H Downblast H Upblast H Unit Sizes 003 035 1 3 75 3 75 4 25 2 4 25 3 75 4 25 3 4 25 3 75 4 25 4 3 75 3 75 4 25 Unit Sizes 040 090 1 6 00 6 75 6 75 2 6 50 6 75 6 75 3 6 50 6 75 6 75 4 6 00 6 75 6 7...

Page 19: ...Air Handler Figure 30 Removing Motor Behind Shipping Brackets Figure 31 Removing Motor Beside Shipping Brackets Figure 32 Plenum Fan Typical Shipping Brackets Shipping hold down nut and bolt Remove a...

Page 20: ...e are to be field drilled Any mounting hardware is to be field supplied Table 6 OSHPD Mounting Attachment Method SDS Attachment System by Others Spacing System Bolted attachment to steel Figure 33 1 9...

Page 21: ...self will be mounted on the drive side fan panel inside the fan cabinet The external junction box will provide loose wire connection to the VFD and to the motor An external mounted keypad display cont...

Page 22: ...quipment damage due to loose fasteners represents improper start up and equipment abuse It is not covered by the warranty 1 Check that the unit is completely and properly installed with ductwork conne...

Page 23: ...Hours of Operation 1 Disconnect and lock electrical power source 2 Check tightness of all bearing wheel and sheave setscrews or capscrews See Table 14 on page 26 3 Recheck belt tension and adjust if n...

Page 24: ...Funnel Relationship 13 to 36 Belt Drive Plenum Fan Wheel Funnel Parameters in mm Size in A B C 13 0 25 6 35 0 91 23 11 3 50 88 9 15 0 25 6 35 0 91 23 11 3 50 88 9 16 0 25 6 35 0 91 23 11 3 50 88 9 18...

Page 25: ...12 Wheel to Inlet Funnel Relationship Direct Drive Class II fans Fan Size in Overlap in mm 11 0 25 6 35 12 0 25 6 35 15 0 25 6 35 16 0 38 9 65 18 0 38 9 65 20 0 41 10 41 22 0 45 11 43 24 0 50 12 7 27...

Page 26: ...II Plenum Fans Only Fan Size Setscrew Size Torque ft lb Aluminum Steel 11 12 13 3 8 19 2 N A 15 3 8 19 2 N A 16 3 8 19 2 N A 18 3 8 19 2 N A 20 3 8 19 2 N A 22 3 8 19 2 N A 24 3 8 19 2 N A 27 3 8 19 2...

Page 27: ...or is replaced After fan and or motor replacement the block off plate is to be removed and stored outside of the air tunnel The Daikin Fan Array has an optional gravity actuated block off damper These...

Page 28: ...can be simplified by assuming standard density and assuming funnel dimensions match the drawing dimensions Table 17 shows the factor F for each fan size and type The equation then becomes the followin...

Page 29: ...ecure tubing to the fan assembly using cable tie mount DCX52 and Cable tie DCX54 as needed Make sure any tubing does not interfere with the fan wheel NOTE Never drill or screw through the inlet funnel...

Page 30: ...rpm Class I 2077 1875 1691 1479 1328 1209 1073 Maximum rpm Class Il 2703 2413 2199 1928 1730 1579 1401 Table 20 Operating Limits Belt Drive Plenum Fans Fan Operating Limits Belt Drive Plenum Fans Size...

Page 31: ...tributes to premature fan and motor bearing failure Monitor overall vibration levels every six months of operation An increase in levels is an indication of potential trouble Vibration Causes 1 Wheel...

Page 32: ...Motor Bearings Mfr Grease NEMA Size Amount to Add oz Texaco Polystar or Polyrex EM Exxon Mobil or Rykon Premium 2 or Penzoil Pen 2 Lube 56 to 140 0 08 140 0 15 180 0 19 210 0 30 250 0 47 280 0 61 320...

Page 33: ...59 3 to 3 7 16 75 80 0 85 24 10 3 1 2 to 4 85 105 1 5 42 53 Fan Drive WARNING Before servicing lock out and tag out all power to the unit Fans or belts cause severe personal injury or death WARNING D...

Page 34: ...djustment LVP Variable Speed Sheaves Mounting 1 Slide sheave on motor shaft so that the side of the sheave with setscrew A is next to the motor when setscrew A is in the hub or barrel of the sheave 2...

Page 35: ...f the driven sheave See Figure 49 2 Verify that all setscrews are torqued to the values shown in Table 28 before starting drive Check setscrew torque and belt tension after 24 hours of service Adjusti...

Page 36: ...lbs Seating torque in lbs Seating torque in lbs Seating torque in lbs Seating torque in lbs Length L in lbs Seating torque in lbs 1 4 20NC 150 12 5 100 87 7 3 3 16 50 5 16 11NC 305 25 4 200 165 13 8 1...

Page 37: ...cause slippage 5 Inspect V drive on a periodic basis Adjust tension if the belt is slipping Do not apply belt dressing This can damage the belt and cause early failure Tension Measurement Procedure 1...

Page 38: ...gauge is used the prefilters can be removed to check the pressure drop of the final filters Figure 53 Filter Gauge Table 30 Filter Pressure Drops Bag filters DriPak 2000 Efficiency 45 65 85 95 Rated...

Page 39: ...o prevent freeze up NOTE Carefully read instructions for mixing antifreeze solution used Some products have a higher freezing point in their natural state when mixed with water Daikin is not responsib...

Page 40: ...iping and remove the brass plugs for the vents and drains located in the connections 2 Remove all screws and remove the access panel 3 Remove the screws holding the coil in place 4 Lift and pull the c...

Page 41: ...he coil is in place bolt the coil to the section 4 Caulk the mounting surface of the steel plate and install the plate on the coils 5 Caulk the mounting surface of the drain trough and install the dra...

Page 42: ...turn Material Procedure Defective material may not be returned without permission of authorized factory service personnel of Daikin in Minneapolis Minnesota 763 553 5330 A Return Goods tag must be inc...

Page 43: ...____________ RF VFD model number __________________________________________________ Serial number __________________________ Circle Yes or No If not applicable to the type of unit circle N A I INITIAL...

Page 44: ...3 ___________ ____________ ____________ ___________ ___________ ____________ G FLA L1 ___________ L2____________ L3 ___________ H Operate electric heat with fans off Electric heat must cycle on high l...

Page 45: ...______________________ 2 How would you rate the overall appearance of the product i e paint fin damage etc Excellent Good Fair Poor 3 Did all sections of the unit fit together properly Yes No N A 4 Di...

Page 46: ...ndard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details Refer to Form 933 430285Y To find your local Daikin Applied...

Reviews: