Service Diagnosis
21
A6
Description
Indoor Fan Motor Abnormality
Supposed Cause
1. Indoor fan motor winding short, or the motor lead wire broken.
2. Indoor PCB faulty.
Troubleshooting
Does it rotate?
Does it connect
properly?
No
Yes
Change fan motor.
Check fan motor connector
condition.
Yes
No
Change PCB and turn on
power.
Turn off power supply and
rotate fan by hand.
No
Connect correctly.
Change fan motor.
C4/C9
Description
Indoor Heat Exchanger Thermistor Abnormality
Indoor Room Thermistor Abnormality
Supposed Cause
1. Thermistor, connector faulty.
2. Indoor PCB faulty.
Troubleshooting
Normal?
No
Yes
Normal?
# Refer thermistor resistance table.
Replace indoor PCB.
Check thermistor resistance
value.
Check the thermistor connector
condition.
No
Replace indoor thermistor.
Correct the connection.
*Remark:
Refer Thermistor resistance check procedure in Appendix A (Item 1, page 32).