Service Diagnosis
20
A5
Description
Anti-freeze protection or High Pressure Control
Supposed Cause
1. Indoor air
fi
lter, heat exchanger block due to dust accumulation.
2. Indoor air short circuit.
3. Indoor coil thermistor faulty.
4. Indoor PCB faulty.
5. Fan blower dirty.
Troubleshooting
Any air short
circuit?
Does it confirm
to the thermistor
accuracy table?
Yes
No
Check indoor air flow.
Check intake air filter.
Check fan blower condition.
Change indoor thermistor.
Check the dust
accumulate indoor coil.
No
Yes
Change indoor PCB.
Provide sufficient air passage.
Is it very dirty?
Yes
No
Clean the air filter.
Check indoor coil
thermistor resistance.
Is it very dirty?
Yes
# Refer to thermistor resistance table.
No
Clean fan blower.
Is it very dirty?
Yes
No
Clean the indoor coil.