background image

RZQG71~140L + RZQSG100~140L

Split system air conditioners

4P339538-1A – 2014.03

Installation manual

4

3.4.

Installation

For installation of the indoor unit(s), refer to the indoor unit 
installation manual.

Illustrations show RZQG125L outdoor unit type. Other types 
also follow this installation manual.

This outdoor unit requires the pipe branching kit (optional) when 
used as the outdoor unit for the simultaneous operation system. 
Refer to catalogues for details.

Never operate the unit with a damaged or disconnected 
discharge thermistor and suction thermistor, burning of the 
compressor may result.

Be sure to confirm the model name and the serial no. of the 
outer (front) plates when attaching/detaching the plates to avoid 
mistakes.

When closing the service panels, take care that the tightening 
torque does not exceed 4.1 N•m.

3.5.

Model identification

RZQG units include special equipment (insulation, optional bottom 
plate heater, ...) to ensure good operation in areas where low ambient 
temperature can occur together with high humidity conditions. In such 
conditions the RZQSG models may experience problems with severe 
ice build up on the air-cooled coil. If such conditions are expected, a 
RZQG unit must be installed instead. These models contain 
countermeasures (insulation, optional bottom plate heater, ...) to 
prevent freeze up.

4.

Accessories

Check if the following accessories are included with the unit:

See the figure below for the location of the accessories.

1

Installation manual

2

Clamp

3

Fluorinated greenhouse gases label

4

Energy label

4.1.

Handling

As shown in the figure, bring the unit slowly by grabbing the left and 
right grips.

Place your hands on the corner instead of holding the suction inlet in 
the side of the casing, otherwise the casing could be deformed.

5.

Selecting installation site

5.1.

General

Select an installation site where the following conditions are 
satisfied and that meets with your customer's approval.
- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and 

vibration and where the unit can be installed level.

- Places where there is no possibility of flammable gas or 

product leak.

- The equipment is not intended for use in a potentially 

explosive atmosphere.

- Places where servicing space can be well ensured.
- Places where the indoor and outdoor units' piping and wiring 

lengths come within the allowable ranges.

- Places where water leaking from the unit cannot cause 

damage to the location (e.g. in case of a blocked drain pipe).

- Places where the rain can be avoided as much as possible.
- Do not install the unit in places often used as work place.

In case of construction works (e.g. grinding works) where a 
lot of dust is created, the unit must be covered.

- Do not place any objects or equipment on top of the unit (top 

plate).

- Do not climb, sit or stand on top of the unit,
- Be sure that sufficient precautions are taken, in accordance 

with applicable legislation, in case of refrigerant leakage.

When installing the unit in a place exposed to strong wind, pay 
special attention to the following.
Strong winds of 5 m/sec or more blowing against the outdoor 
unit's air outlet causes short circuit (suction of discharge air), 
and this may have the following consequences:
- Deterioration of the operational capacity.
- Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the 

unit, the fan can start rotating very fast until it breaks.

Refer to the figures for installation of this unit in a place where 
the wind direction can be foreseen.

CAUTION

Take care not to let hands or objects come in contact with 
rear fins.

1x

1

2

3

4

ENERG

IJA

Y

IA

IE

ENERG

IJA

Y

IA

IE

WARNING

Be sure to provide for adequate measures in order to 
prevent that the outdoor unit be used as a shelter by 
small animals.

Small animals making contact with electrical parts can 
cause malfunctions, smoke or fire. Please instruct the 
customer to keep the area around the unit clean.

NOTICE

This is a class A product. In a domestic environment this 
product may cause radio interference in which case the 
user may be required to take adequate measures.

Summary of Contents for SkyAir RZQG140L7V1B

Page 1: ...L RZQG71L8V1B RZQG100L8V1B RZQG125L8V1B RZQG140L7V1B RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B RZQSG100L8V1B RZQSG125L8V1B RZQSG140L7V1B RZQSG100L8Y1B RZQSG125L8Y1B RZQSG140L7Y1B Split system...

Page 2: ...A B 1 2 4 5 H1 L3 L2 L3 L4 L2 L3 L4 L5 L6 L7 A C E B D H 1 2 3 1 50 Hz 220 240 V 3N 50 Hz 380 415 V V1 type Y1 type 1 2 4 5 A 1 A 2 100 100 100 100 1 1 2 H1 H1 H1 H2 H2 H2 L1 L1 L1 L1 L2 7 R410A R410...

Page 3: ...o com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet C 12 Merk som det fremkommer...

Page 4: ...15 3 Test run 18 15 4 Precautions regarding test runs 19 15 5 Failure diagnosis at the moment of first installation 19 16 Wiring diagram 20 Thank you for purchasing this product The original instruct...

Page 5: ...an withstand its weight Insufficient strength may result in the fall of equipment and causing injury Carry out the specified installation work in consideration of strong winds typhoons or earthquakes...

Page 6: ...is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit or...

Page 7: ...or neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibility of flammable gas or product leak The equipm...

Page 8: ...tdoor unit In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind 6 P...

Page 9: ...let space position the units with consideration to the space required for the onsite refrigerant piping work as well Consult your dealer if the work conditions do not match those in the drawings 7 1 P...

Page 10: ...ion shall comply with applicable legislation In Europe the EN378 is the application standard that shall be used NOTICE To persons in charge of piping work Be sure to open the stop valve after piping i...

Page 11: ...el 71 100 125 140 Maximum total one way piping length a a Parenthesized figure represents the equivalent length Pair L1 size down 10 m 10 m standard 50 m 70 m 75 m 90 m size up 25 m 35 m 35 m 45 m Twi...

Page 12: ...se using existing piping with deteriorated oil will cause compressor breakdown Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil checking...

Page 13: ...it will deteriorate the refrigerant oil 9 3 Stop valve operation Cautions on handling the stop valve Make sure to keep both stop valves open during operation The figure below shows the name of each pa...

Page 14: ...he edge and the surrounding end surfaces to prevent rusting When passing electrical wiring through the knock out holes remove any burrs from the knock out holes and wrap the wiring with protective tap...

Page 15: ...ks Use a 2 stage vacuum pump with a non return valve which can evacuate to a gauge pressure of 100 7 kPa 5 Torr absolute 755 mm Hg Connect the vacuum pump to both the service port of the gas stop valv...

Page 16: ...leak test and vacuum drying see 11 Leak test and vacuum drying on page 12 This unit requires additional charging of refrigerant according to the length of refrigerant piping connected at the site Mak...

Page 17: ...b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 Refrigerant...

Page 18: ...g on mode type RZQG71 RZQSG100 125 RZQG100 140 RZQSG140 Model Liquid piping Refrigerant piping length 5 10 m a b a For RZQG units only 3 10 m b For RZQG units only When piping length is less than 5 m...

Page 19: ...ring Secure the earth wire to the stop valve attachment plate so that it does not slide Secure the earth wire to the stop valve attachment plate one more time along with the electric wiring and the in...

Page 20: ...nsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circuit...

Page 21: ...wiring as mentioned on the wiring diagram Make sure no wiring has been forgotten and that there are no missing phases or reverse phases Is the unit properly grounded Is the wiring between units connec...

Page 22: ...or of this product only works during the initialisation stage after a power reset The reversed phase protection detector is designed to stop the product in case of an abnormality when the product is s...

Page 23: ...eat exchanger middle R6T Thermistor liquid R10T Thermistor fin RC V1B Signal receiver circuit S1PH High pressure switch TC V1B Signal transmission circuit V1R IGBT power module V1T V1B Insulated gate...

Page 24: ...4P339538 1A 2014 03 Copyright 2013 Daikin...

Reviews: