SiBE281013
Function Details
Function and Control
47
3.2.29 Simulated Operation Function
In case of a thermistor error, simulated operation is performed in two different ways as
shown below even while the error is detected.
A. Operation continues while the error code is displayed on the remote controller.
Applicable thermistors
· Outdoor air temperature thermistor
· Heat exchanger distribution pipe thermistor (in cooling)
· Intermediate heat exchanger thermistor (in heating)
· Liquid pipe thermistor
· Indoor suction air thermistor
· Indoor heat exchanger thermistor
B. Operation continues even the error is detected. The remote controller displays error code
only when the "Inspection/Test Run" button is pressed.
Applicable thermistors
· Remote controller thermistor
· Radiation fin thermistor
Note:
In case of a thermistor error other than A and B above, an abnormal stop is made and no
simulated operation is carried out.
Applicable thermistors
· Suction pipe thermistor
· Discharge pipe thermistor
· Heat exchanger distribution pipe thermistor (in heating)
· Intermediate heat exchanger thermistor (in cooling)