Function Details
SiBE281013
36
Function and Control
3.2.7 Compressor Step
The compressor operation frequency is controlled in order to keep a constant evaporation
temperature in cooling and a constant condensing temperature in heating.
Cooling
∆
t cool = Remote controller set temperature - Indoor return air temperature.
Depending on
∆
t cool and the cooling load, the target evaporating temperature will be a value
between 2°C and 20°C.
Heating
∆
t heat = Indoor return air temperature - Remote controller set temperature.
Depending on
∆
t heat and the heating load, the target condensing temperature will be a value
between 42°C and 54°C. (for RZQG100-140LV1B : 42°C and 50°C)
: Maximum frequency in cooling
Step No.
Compressor operation frequency
RZQG71LV1B
RZQG100LV1B
RZQG125·140LV1B
1
—
30 Hz
30 Hz
2
—
33 Hz
33 Hz
3
57 Hz
36 Hz
36 Hz
4
61.5 Hz
40 Hz
40 Hz
5
66 Hz
44 Hz
44 Hz
6
72 Hz
48 Hz
48 Hz
7
78 Hz
52 Hz
52 Hz
8
85.5 Hz
56 Hz
56 Hz
9
93 Hz
60 Hz
60 Hz
10
102 Hz
65 Hz
65 Hz
11
109.5 Hz
70 Hz
70 Hz
12
118.5 Hz
76 Hz
76 Hz
13
127.5 Hz
82 Hz
82 Hz
14
136.5 Hz
89 Hz
89 Hz
15
145.5 Hz
96 Hz
96 Hz
16
151.5 Hz
104 Hz
104 Hz
17
154.5 Hz
112 Hz
112 Hz
18
174 Hz
121 Hz
121 Hz
19
183 Hz
129 Hz
129 Hz
20
192 Hz
137 Hz
137 Hz
21
201 Hz
144 Hz
144 Hz
22
211.5 Hz
—
151 Hz
23
222 Hz
—
159 Hz
24
232.5 Hz
—
167 Hz
25
243 Hz
—
175 Hz
26
253.5 Hz
—
180 Hz
27
265.5 Hz
—
—
28
277.5 Hz
—
—
29
289.5 Hz
—
—