24
English
Table 5
NOTE
1.
“Mode No.” setting is done in a batch for the group. To make or confirm settings for an individual unit, set
the Mode No. shown in parentheses.
2.
The figure of the ceiling height is for the all round outlet.
11-2 Setting of air direction
•
Refer the attached installation manual with the optional sealing member of air discharge outlet, for setting
of air direction (4-way with sealed corners, or 3-way).
(The setting position No. is 01 “Standard-All round” as factory setting.)
See the installation manual included with the sealing material of air discharge outlet kit, sold separately and
technical guide, for ceiling height settings for two and three-direction air discharge.
11-3 Setting of air volume when Thermostat Control is OFF
•
Before setting Thermostat Control, consult with the customer regarding whether that is responding to their
environment.
(SECOND CODE NO. is “02” at Cooling Thermostat OFF and others are “01” as factory setting.)
Table 6
NOTE
•
“Mode No.” setting is done in a batch for the group. To make or confirm settings for an individual unit, set the
Mode No. shown in parentheses.
11-4 Setting air filter sign
•
Remote controllers are equipped with liquid crystal display air filter signs to display the time to clean air fil-
ters.
•
Change the SECOND CODE NO. according to “Table 7” depending on the amount of dirt or dust in the
room.
(SECOND CODE NO. is factory set to “01” for filter contamination-light.)
Table 7
Setting
Ceiling height (m)
Mode No. *
FIRST CODE NO. SECOND CODE NO.
FCQG71EVEB
FCQG100·125·
140EVEB
13 (23)
0
01
Standard-All round
Less than 2.7 m
Less than 3.2m
High ceiling 1
More than 2.7 m;
3.0 m or less
More than 3.2m;
3.6m or less
02
High ceiling 2
More than 3.0 m;
3.5 m or less
More than 3.6m;
4.2m or less
03
Setting
Mode No. *
FIRST CODE NO. SECOND CODE NO.
Fan stops at Thermostat OFF
(Cooling/Heating)
Normal
11 (21)
2
01
Stop
02
Air volume at
Cooling Thermostat OFF
LL
12 (22)
6
01
Setup volume
02
Air volume at
Heating Thermostat OFF
LL
12 (22)
3
01
Setup volume
02
Setting
Spacing time of display air filter
sign (long life type)
Mode No. *
FIRST CODE
NO.
SECOND
CODE NO.
Air filter contamination-light
Approx. 2500 hrs
10 (20)
0
01
Air filter contamination-heavy
Approx. 1250 hrs
02
No display (Note 2)
3