<Ceiling work>
(1-3)
Adjust the unit to the right position for installation.
(Refer to
“4. PREPARATIONS BEFORE INSTALLATION-
(1)”
.)
•
At this time, using the positioning jig for installation (15)
allows to confirm the position from under surface of the
unit to under surface of the ceiling.
(1-4)
Check the unit is horizontally level.
CAUTION
•
The indoor unit is equipped with a built-in drain pump and float
switch. Verify that it is level by using a level or a water-filled
vinyl tube.
(If the unit is tilted against condensate flow, the float switch may
malfunction and cause water to drip.)
(1-5)
Remove the washer fixing plate (7) used for preventing the
washer from falling and tighten the upper nut.
(1-6)
Remove the paper pattern for installation (5).
(2) For existing ceilings
(2-1)
Install the indoor unit temporarily.
•
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using nut and washer from
upper/lower sides of hanger bracket. If you use the washer fixing plate (7), it will prevent the falling of
the washer.
(2-2)
Adjust the height and position of the unit.
(Refer to “
4.PREPARATIONS BEFORE INSTALLATION-(1)”
.)
(2-3)
Perform steps (1-4), (1-5) in (1) For new ceilings.
Fit the shorter side
of the con
v
ex.
Underside of
the ceiling
Positioning jig for
installation (15)
(attached)
Underside
of the
u
nit
main
b
ody
Fig. 11
Level
Vinyl tube
[Maintaining horizontality]
Fig. 12
Field s
u
pply
W
asher (3) (attached)
[Sec
u
ring the hanger
b
racket]
Hanger
b
racket
Tighten (do
ub
le n
u
ts)
Fi
g
. 13
Insert
Washer fixing plate (7)
[Securing the washer]
(attached)
Fig. 14