background image

Preparation

Installation manual

6

RZAG71~Y1

Sky Air Alpha-series

4P573382-1 – 2019.04

3

Preparation

3.1

Preparing the installation site

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

3.1.1

Installation site requirements of the
outdoor unit

Mind the spacing guidelines. See the "Technical data" chapter, and
the figures on the inside of the front cover.

INFORMATION

The sound pressure level is less than 70 dBA.

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

4

Installation

4.1

Mounting the outdoor unit

4.1.1

To provide the installation structure

Prepare  4  sets  of  anchor  bolts,  nuts  and  washers  (field  supply)  as
follows:

(mm)

>150

758

485

(480-490)

4× M12

a

a

Make sure not to cover the drain holes of the bottom plate
of the unit.

INFORMATION

The  recommended  height  of  the  upper  protruding  part  of
the bolts is 20 mm.

20

NOTICE

Fix the outdoor unit to the foundation bolts using nuts with
resin  washers  (a).  If  the  coating  on  the  fastening  area  is
stripped off, the metal can rust easily.

a

4.1.2

To install the outdoor unit

4× M12

4.1.3

To provide drainage

INFORMATION

If  necessary,  you  can  use  a  drain  pan  (field  supply)  to
prevent drain water from dripping.

NOTICE

If  the  unit  CANNOT  be  installed  fully  level,  always  make
sure that the inclination is towards the backside of the unit.
This is required to guarantee proper drainage.

NOTICE

If drain holes of the outdoor unit are covered by a mounting
base  or  by  floor  surface,  raise  the  unit  to  provide  a  free
space of more than 150 mm under the outdoor unit.

≥150 mm

Drain holes (dimensions in mm)

A

134

206

758

43
48

288

451

613

776

408

414

349

214

111

(480~490)

107

B

B

C

D

 =

E

A

Discharge side

Summary of Contents for Sky Air Alpha RZAG71N7V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71N7V1B RZAG100N7V1B RZAG125N7V1B RZAG140N7V1B RZAG71N7Y1B RZAG100N7Y1B RZAG125N7Y1B RZAG140N7Y1B...

Page 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Page 3: ...onforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m...

Page 4: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 5: ...ressor 15 5 Commissioning 15 5 1 Checklist before commissioning 15 5 2 To perform a test run 15 5 3 Error codes when performing a test run 16 6 Disposal 16 7 Technical data 17 7 1 Service space Outdoo...

Page 6: ...s of anchor bolts nuts and washers field supply as follows mm 150 7 5 8 485 4 8 0 4 9 0 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended hei...

Page 7: ...ggest to install the optional bottom plate heater EKBPH140N7 when the unit is installed in cold climates 4 1 4 To prevent the outdoor unit from falling over In case the unit is installed in places whe...

Page 8: ...see above with sealing material to prevent condensed water on the stop valves from moving to the indoor unit NOTICE Any exposed piping might cause condensation 6 Reattach the service cover and the pi...

Page 9: ...tal liquid piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional r...

Page 10: ...er a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT...

Page 11: ...5 mm RZAG100 Case Twin standard liquid pipe size 1 G1 Total 9 5 G1 45 m G2 Total 6 4 G2 7 5 12 m 2 Case G1 40 m R1 Length G1 40 m 5 m R1 0 35 kg R2 Length G2 12 m R2 0 4 kg 3 R R R1 R2 0 35 0 4 0 75...

Page 12: ...deactivate vacuum mode 12 Press the BS1 button to leave the setting mode Make sure to reattach the electronic component box cover and to install the front cover after the job is finished NOTICE Make s...

Page 13: ...3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 4 5 2...

Page 14: ...iring to the frame at the knockout hole Routing through the frame Choose one of the 3 possibilities a a a 2 3 1 a Power supply cable Note Route the interconnection cable together with the refrigerant...

Page 15: ...e is used The indoor unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the a...

Page 16: ...ror codes when performing a test run If the installation of the outdoor unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Noth...

Page 17: ...stacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum dista...

Page 18: ...ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Position of compressor terminal 3 Notes English Translation Notes Notes Connection X1M Indoo...

Page 19: ...erload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle R6T Thermistor liquid...

Page 20: ...4P573382 1 2019 04 Copyright 2019 Daikin 4P573382 1 0000000Q...

Reviews: