background image

Installation

Installation manual

13

RZAG71~Y1
Sky Air Alpha-series
4P573382-1 – 2019.04

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Use  the  GWP  value  mentioned  on  the  refrigerant  charge
label.  That  GWP  is  based  on  the  current  legislation  on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.

2

Fix  the  label  on  the  inside  of  the  outdoor  unit.  There  is  a
dedicated place for it on the wiring diagram label.

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

CAUTION

For  use  of  units  in  applications  with  temperature  alarm
settings  it  is  recommended  to  foresee  a  delay  of  10
minutes  for  signalling  the  alarm  in  case  the  alarm
temperature  is  exceeded.  The  unit  may  stop  for  several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.

4.5.1

About electrical compliance

RZAG71~140N7V1B

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

4.5.2

Guidelines when connecting the electrical
wiring

Tightening torques

Item

Tightening torque (N•m)

M4 (X1M)

1.2~1.8

M4 (earth)

1.2~1.4

M5 (X1M)

2.0~3.0

M5 (earth)

2.4~2.9

NOTICE

If  limited  space  is  available  at  the  wire  terminal,  use
bended crimp-style ring terminals.

4.5.3

Specifications of standard wiring components

Component

V1

Y1

71

100

125~140

71

100

125

140

Power supply cable

MCA

(a)

18.8 A

23.3 A

28.8 A

12.3 A

15.4 A

15.7 A

15.4 A

Voltage range

220~240 V

380~415 V

Phase

1~

3N~

Frequency

50 Hz

Wire sizes

Must comply with applicable legislation

Interconnection cables

Minimum cable section of 2.5 mm² and applicable for 230 V

Recommended field fuse

20 A

32 A

16 A

Earth leakage circuit breaker

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).

4.5.4

To connect the electrical wiring on the
outdoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

1

Remove the service cover.

2

Connect  the  interconnection  cables  and  power  supply  as
follows:

Summary of Contents for Sky Air Alpha RZAG71N7V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71N7V1B RZAG100N7V1B RZAG125N7V1B RZAG140N7V1B RZAG71N7Y1B RZAG100N7Y1B RZAG125N7Y1B RZAG140N7Y1B...

Page 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Page 3: ...onforme altera o em 10 11 12 13 14 15 16 17 Direktiver med senere ndringer Direktiv med f retagna ndringar Direktiver med foretatte endringer Direktiivej sellaisina kuin ne ovat muutettuina v platn m...

Page 4: ...taava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS...

Page 5: ...ressor 15 5 Commissioning 15 5 1 Checklist before commissioning 15 5 2 To perform a test run 15 5 3 Error codes when performing a test run 16 6 Disposal 16 7 Technical data 17 7 1 Service space Outdoo...

Page 6: ...s of anchor bolts nuts and washers field supply as follows mm 150 7 5 8 485 4 8 0 4 9 0 4 M12 a a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended hei...

Page 7: ...ggest to install the optional bottom plate heater EKBPH140N7 when the unit is installed in cold climates 4 1 4 To prevent the outdoor unit from falling over In case the unit is installed in places whe...

Page 8: ...see above with sealing material to prevent condensed water on the stop valves from moving to the indoor unit NOTICE Any exposed piping might cause condensation 6 Reattach the service cover and the pi...

Page 9: ...tal liquid piping length is more than specified see later Completely recharging refrigerant Example When relocating the system After a leak Charging additional refrigerant Before charging additional r...

Page 10: ...er a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT...

Page 11: ...5 mm RZAG100 Case Twin standard liquid pipe size 1 G1 Total 9 5 G1 45 m G2 Total 6 4 G2 7 5 12 m 2 Case G1 40 m R1 Length G1 40 m 5 m R1 0 35 kg R2 Length G2 12 m R2 0 4 kg 3 R R R1 R2 0 35 0 4 0 75...

Page 12: ...deactivate vacuum mode 12 Press the BS1 button to leave the setting mode Make sure to reattach the electronic component box cover and to install the front cover after the job is finished NOTICE Make s...

Page 13: ...3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 4 5 2...

Page 14: ...iring to the frame at the knockout hole Routing through the frame Choose one of the 3 possibilities a a a 2 3 1 a Power supply cable Note Route the interconnection cable together with the refrigerant...

Page 15: ...e is used The indoor unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the a...

Page 16: ...ror codes when performing a test run If the installation of the outdoor unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Noth...

Page 17: ...stacle roof a b c d e Minimum service space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum dista...

Page 18: ...ON OFF OFF 2 Layout English Translation Layout Layout Front Front Back Back Position of compressor terminal Position of compressor terminal 3 Notes English Translation Notes Notes Connection X1M Indoo...

Page 19: ...erload protection R1 R8 A1P Y1 only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle R6T Thermistor liquid...

Page 20: ...4P573382 1 2019 04 Copyright 2019 Daikin 4P573382 1 0000000Q...

Reviews: