7 Disposal

Installation manual

20

RZAG71~Y1

Sky Air Alpha-series

4P695306-1 – 2022.05

#

Action

Result

2

Press at least 4 seconds.

The Service Settings menu
is displayed.

3

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

4

Press.

Test Operation is
displayed on the home
menu.

Cool

Return

Setting

Test Operation

5

Press within 10 seconds.

Test run starts.

3

Check operation for 3 minutes.

4

Check  operation  of  the  airflow  direction  (only  applicable  for
indoor units with swing flaps).

#

Action

Result

1

Press.

Return 

Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Position 0

Low

2

Select Position 0.

Return 

Setting

Return

Setting

Air Volume/direction

Air Volume

Direction

Low

Position 0

3

Change the position.

If the airflow flap of the
indoor unit moves,
operation is OK.

If not, operation is not OK.

4

Press.

The home menu is
displayed.

5

Stop the test run.

#

Action

Result

1

Press at least 4 seconds.

The Service Settings menu
is displayed.

2

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

3

Press.

The unit returns to normal
operation, and the home
menu is displayed.

6.3

Error codes when performing a
test run

If  the  installation  of  the  outdoor  unit  has  NOT  been  done  correctly,
the following error codes may be displayed on the user interface:

Error code

Possible cause

Nothing displayed

(the currently set
temperature is not
displayed)

▪ The  wiring  is  disconnected  or  there  is  a

wiring  error  (between  power  supply  and
outdoor  unit,  between  outdoor  unit  and
indoor  units,  between  indoor  unit  and
user interface).

▪ The  fuse  on  the  outdoor  unit  PCB  has

blown out.

E3, E4 or L8

▪ The stop valves are closed.

▪ The air inlet or air outlet is blocked.

U1 or E7

There is a missing phase in case of three-
phase power supply units.

Note: 

Operation will be impossible. Turn

OFF the power, recheck the wiring, and
switch two of the three electrical wires.

L4

The air inlet or air outlet is blocked.

U0

The stop valves are closed.

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

6.4

Dedicated field settings for
technical cooling

In  case  the  system  is  used  for  technical  cooling,  please  apply  the
following remote controller settings:

Field setting

Description

2–57–2

See the service manual for the field setting
method.

7

Disposal

This  unit  uses  hydrofluorocarbon.  Contact  your  dealer  when
discarding  this  unit.  It  is  required  by  law  to  collect,  transport  and
discard  the  refrigerant  in  accordance  with  the  "hydrofluorocarbon
collection and destruction" regulations.

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Summary of Contents for Sky Air Alpha RZAG100N2V1B

Page 1: ...Installation manual Sky Air Alpha series English Installation manual Sky Air Alpha series RZAG71N2V1B RZAG100N2V1B RZAG125N2V1B RZAG140N2V1B RZAG71N2Y1B RZAG100N2Y1B RZAG125N2Y1B RZAG140N2Y1B...

Page 2: ...HD HU 200 1000 1000 500 HD HU A B C 200 1 300 1000 A B C E 200 1 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 250 1500 300 1500 B D E HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 50...

Page 3: ...na f r i henhold til bestemmelsene i noudattaen s nn ksi za dodr en ustanoven prema odredbama k veti a z zgodnie z postanowieniami urm nd prevederile 19 20 21 22 23 24 25 v skladu z dolo bami vastaval...

Page 4: ...la TS TSmin Alhaisin matalapainepuolen l mp tila L C TSmax Suurinta sallittua painetta PS vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuos...

Page 5: ...e Equipment Safety Regulations 2016 S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Reg...

Page 6: ...th the maximum allowable pressure PS M C Refrigerant N Setting of pressure safety device P bar Manufacturing number and manufacturing year refer to model nameplate K L M TSmin TSmax PS N P 41 5 30 70...

Page 7: ...iring diagram Outdoor unit 22 1 About this document Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on...

Page 8: ...installations NEVER install a drier to this unit to guarantee its lifetime The drying material may dissolve and damage the system CAUTION Install the refrigerant piping or components in a position whe...

Page 9: ...ion MUST comply with the applicable legislation WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazar...

Page 10: ...of the front cover INFORMATION The sound pressure level is less than 70 dBA CAUTION Appliance NOT accessible to the general public Install it in a secured area protected from easy access This unit is...

Page 11: ...usting NOTICE Precautions when making knockout holes Avoid damaging the casing and underlying piping After making the knockout holes we recommend to remove the burrs and paint the edges and areas arou...

Page 12: ...vent damage 3 Do the following Connect the liquid pipe a to the liquid stop valve Connect the gas pipe b to the gas stop valve a b 4 Do the following Insulate the liquid piping a and the gas piping b...

Page 13: ...stop valve to increase efficiency Make sure that the gas stop valve and liquid stop valve are firmly closed before performing the leak test or vacuum drying 1 Vacuum the system until the pressure on t...

Page 14: ...ve with service port gas Typical workflow Completely recharging refrigerant typically consists of the following stages 1 Determining how much refrigerant to charge 2 Charging refrigerant 3 Filling in...

Page 15: ...0 7 1 05 a 1 4 a a Only for RZAG100 140 To determine the additional refrigerant amount R in kg in case of twin triple and double twin 1 Determine G1 and G2 G1 m Total length of x liquid piping x 9 5 m...

Page 16: ...sh buttons BS on the PCB A1P and reading the feedback from the 7 segment displays Operate the switches and push buttons with an insulated stick such as a closed ball point pen to avoid touching of liv...

Page 17: ...ended to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded The unit may stop for several minutes during normal operation for defrosting the unit or when...

Page 18: ...the wiring to the frame at the knockout hole Routing through the frame Choose one of the 3 possibilities a a a 2 3 1 a Power supply cable Note Route the interconnection cable together with the refrige...

Page 19: ...unit decoration panel with infrared receiver is installed The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislatio...

Page 20: ...e Nothing displayed the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units bet...

Page 21: ...space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and the edge of...

Page 22: ...t Layout Front Front Back Back Position of compressor terminal Position of compressor terminal 3 Notes English Translation Notes Notes Connection X1M Indoor outdoor communication Earth wiring Field su...

Page 23: ...only Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger R5T Thermistor heat exchanger middle R6T Thermistor liquid R7T Thermistor fin R8 A1P V1 o...

Page 24: ...4P695306 1 2022 05 Copyright 2022 Daikin 4P695306 1 0000000R Verantwortung f r Energie und Umwelt...

Reviews: