6 Installation
Installer reference guide
20
250D7Y1B
Sky Air Advance-series
4P573383-1 – 2019.04
What
When
Completely recharging refrigerant
Example:
▪ When relocating the system.
▪ After a leak.
Charging additional refrigerant
Before charging additional refrigerant, make sure the outdoor unit's
external
refrigerant piping is checked (leak test, vacuum drying).
INFORMATION
Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.
Typical workflow – Charging additional refrigerant typically consists
of the following stages:
1 Determining if and how much you have to charge additionally.
2 If necessary, charging additional refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
Completely recharging refrigerant
Before completely recharging refrigerant, make sure the following is
done:
1 All refrigerant is recovered from the system.
2 The outdoor unit's
external
refrigerant piping is checked (leak
test, vacuum drying).
3 Vacuum drying on the outdoor unit's
internal
refrigerant piping is
performed.
NOTICE
Before completely recharging, perform vacuum drying on
the outdoor unit's
internal
refrigerant piping as well.
NOTICE
To perform vacuum drying or a complete recharge of the
outdoor unit’s internal refrigerant piping it is necessary to
activate the vacuum mode (see
22]) which will open
required valves in the refrigerant circuit so the vacuuming
process or recharge of refrigerant can be done properly.
▪ Before vacuum drying or recharging, activate field
setting "vacuum mode".
▪ After finishing vacuum drying or recharging, deactivate
field setting "vacuum mode".
WARNING
Some sections of the refrigerant circuit may be isolated
from other sections caused by components with specific
functions (e.g. valves). The refrigerant circuit therefore
features additional service ports for vacuuming, pressure
relief or pressurizing the circuit.
In case it is required to perform
brazing
on the unit, ensure
that there is no pressure remaining inside the unit. Internal
pressures need to be released with ALL the service ports
indicated on the figures below opened. The location is
depending on model type.
Location of service ports:
b
c
a
a
Internal service port
b
Stop valve with service port (liquid)
c
Stop valve with service port (gas)
Typical workflow – Completely recharging refrigerant typically
consists of the following stages:
1 Determining how much refrigerant to charge.
2 Charging refrigerant.
3 Filling in the fluorinated greenhouse gases label, and fixing it to
the inside of the outdoor unit.
6.7.2
About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
WARNING: FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
The appliance shall be stored in a room without
continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric
heater).
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.