background image

Installation manual

Sky Air Active-series

English

Installation manual

Sky Air Active-series

AZAS100MUV
AZAS125MUV
AZAS140MUV

AZAS100MUY
AZAS125MUY
AZAS140MUY

Summary of Contents for Sky Air Active Series

Page 1: ...Installation manual Sky Air Active series English Installation manual Sky Air Active series AZAS100MUV AZAS125MUV AZAS140MUV AZAS100MUY AZAS125MUY AZAS140MUY...

Page 2: ...A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB HU 300 1000 1000 500 HU HB HU 300 1250 1000 500 HB HU HB H...

Page 3: ...e Outdoor unit 17 11 2 Piping diagram Outdoor unit 18 11 3 Wiring diagram Outdoor unit 19 1 About this document Target audience Authorised installers INFORMATION This appliance is intended to be used...

Page 4: ...l the required fuses or circuit breakers Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping particularly on the high pressure side Do NOT...

Page 5: ...h the instructions from this manual See 9 Commissioning 415 3 About the box Keep the following in mind At delivery the unit MUST be checked for damage and completeness Any damage or missing parts MUST...

Page 6: ...rging refrigerant 412 1 3 If necessary remove the piping intake rear plate This is e g necessary in the following cases 5 1 Connecting the refrigerant piping 48 6 4 To connect the electrical wiring to...

Page 7: ...ly a 4 3 2 To install the outdoor unit 4 M12 4 3 3 To provide drainage INFORMATION If necessary you can use a drain plug kit field supply to prevent drain water from dripping NOTICE If drain holes of...

Page 8: ...ection d Rear connection 1 Remove the following plates For details see 4 2 1 To open the outdoor unit 46 Remove the service cover a and the piping intake front plate b In case the refrigerant piping i...

Page 9: ...the indoor unit cover the stop valves A B see above with sealing material to prevent condensed water on the stop valves from moving to the indoor unit NOTICE Any exposed piping might cause condensatio...

Page 10: ...eck the pressure for at least 1 hour 5 If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour do the following Check for leaks again Perform vacuum drying again NOTICE Make sur...

Page 11: ...a round crimp style terminal Details are described in Guidelines when connecting the electrical wiring in the installer reference guide 6 4 To connect the electrical wiring to the outdoor unit NOTICE...

Page 12: ...rging additional refrigerant typically consists of the following stages 1 Determining if and how much you have to charge additionally 2 If necessary charging additional refrigerant 3 Filling in the fl...

Page 13: ...accelerate the defrosting process other than those recommended by the manufacturer Be aware that the refrigerant inside the system is odourless 7 3 Completely recharging refrigerant 7 3 1 To determin...

Page 14: ...Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equival...

Page 15: ...e of the compressor is OK There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipe...

Page 16: ...ote Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three electrical wires L4 The air inlet or air outlet is blocked U0 The stop valves are closed U2 There is...

Page 17: ...rvice space between the unit and obstacles A B C D and E eB Maximum distance between the unit and the edge of obstacle E in the direction of obstacle B eD Maximum distance between the unit and the edg...

Page 18: ...ort Service port with 5 16 flare Stop valve Filter Check valve Solenoid valve Heat sink PCB Capillary tube Electronic expansion valve 4 way valve High pressure switch LPS Low pressure switch Compresso...

Page 19: ...l Optional Part n Part n Description Description A1P Printed circuit board main A2P Printed circuit board noise filter BS1 BS3 A1P Push button switch on PCB C A1P Y only Capacitor DS1 A1P Dipswitch E...

Page 20: ...11 Technical data Installation manual 20 AZAS100 140MUV Y Sky Air Active series 4P743507 1 2023 08 L L A L B NA NB E U V W X A A1P A2P Connector...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P743507 1 2023 08 Copyright 2023 Daikin 4P743507 1 0000000O Verantwortung f r Energie und Umwelt...

Reviews: