Installation manual

6

P

RECAUTIONS

 

ON

 

REFRIGERANT

 

PIPING

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

During tests never pressurize the appliances with a pressure
higher than the maximum allowable pressure (see unit name
plate: PS).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

R

EFRIGERANT

 

PIPING

Field pipes can be installed in four directions.

Figure - 

Field pipes in four directions

Cutting out the two slits makes it possible to install as shown in
the 

figure "Field pipes in four directions"

.

(Use a metal saw to cut out the slits.)

To install the connecting pipe to the unit in a downward direction,
make a knockout hole by penetrating the centre area around the
knockout hole using a 

Ø

6 mm drill. (See 

figure "Field pipes in

four directions"

.)

After knocking out the knock-out, it is recommended to apply
repair paint to the edge and the surrounding end surfaces to
prevent rusting.

Preventing foreign objects from entering

Plug the pipe through-holes with putty or insulating material
(procured locally) to stop up all gaps, as shown in the figure.

Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.

Cautions for handling stop valve

The stop valves for indoor-outdoor connecting piping are closed
at shipment from the factory.

The names of parts of the stop valve are shown in the figure.

Since the side boards may be deformed if only a torque wrench
is used when loosening or tightening flare nuts, always lock the
stop valve with a wrench and then use a torque wrench.
Do not place wrenches on the valve cover.

Applying an excessive torque may distort the interior stop valve
surface causing gas to leak inside the valve and causing the
flare nut to crack eventually.
Do not apply force on the valve cover, this may result in a
refrigerant leak.

For cooling operation under low ambient temperature or any
other operation under low pressure, apply silicon pad or similar
to prevent freezing of the gas stop valve flare nut (see figure).
Freezing of the flare nut may cause refrigerant leak.

Place

Installation period

Protection method

Outdoor unit

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Indoor unit

Regardless of the 

period

1

Drill

2

Centre area around knockout hole

3

Knockout hole

4

Slit

5

Connecting pipe

6

Bottom frame

7

Front plate

8

Pipe outlet plate

9

Screw front plate

10

Pipe outlet plate screw

A

Forward

B

Backward

C

Sideways

D

Downward

4

4

3

2

1

7

8

9

10

A

D

C

B

5

6

1

Putty or insulating material 
(produced locally)

Make sure to keep the valve open during operation.

1

Service port

2

stop valve

3

Field piping connection

4

Valve cover

1

Spanner

2

Torque wrench

Silicon sealing pad
(Make sure there is no gap)

1

3

4

1

2

2

Summary of Contents for Siesta AZQS100A7V1B

Page 1: ...INSTALLATION MANUAL AZQS71A2V1B AZQS100A7V1B AZQS125A7V1B AZQS140A7V1B AZQS100A7W1B AZQS125A7W1B AZQS140A7W1B Split System air conditioners ...

Page 2: ...50 Hz 220 240 V R410A 1 2 4 5 6 3 1 3 2 4 5 A B A E B C D H H1 L1 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 1 1 2 L1 L3 L2 L1 L3 L2 1 2 3 4 5 6 ...

Page 3: ...ıÂÙÈÎ fi ÙÔ B Û ÌÊˆÓ Ì ÙÔ ÈÛÙÔ ÔÈËÙÈÎfi C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkom...

Page 4: ...llation work may result in accidents due to fall of equipment Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installation manual using a separate circuit Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using ...

Page 5: ...vels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present Provide a logbook In accordance with the relevant national and international codes it may be necessary to provide a logbook with the equipment containing at least info on maintenance repair work results of tests stand by periodes etc In...

Page 6: ...strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the figures for installation of this unit in a place where the wind direction can be foreseen Turn the air outlet side toward the building s wall fence or screen Set the outlet side at a right angle to the direction of the wind 3 Prepare a water drainage channel around the foundatio...

Page 7: ...ipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical figures used in here represent the dimensions for the 71 100 125 140 class models Figures between indicate the dimensions for the 100 125 140 class models Unit mm Re...

Page 8: ... L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impossible Installation shall be done by a licensed refrigeration technician the choice of materials and installation shall comply with the applicable national and international codes In Europe EN378 is the applicable standard that shall be used To persons in charge of piping work Be sure to open the stop valve after piping installing and vacum...

Page 9: ...repair paint to the edge and the surrounding end surfaces to prevent rusting Preventing foreign objects from entering Plug the pipe through holes with putty or insulating material procured locally to stop up all gaps as shown in the figure Insects or small animals entering the outdoor unit may cause a short circuit in the electrical box Cautions for handling stop valve The stop valves for indoor o...

Page 10: ... material If the temperature is higher than 30 C and the humidity is higher than RH 80 then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing Be sure to insulate the liquid and gas side field piping and the refrigerant branch kit The highest temperature that the gas side piping can reach is around 120 C so be sure to use in...

Page 11: ...cedure for leak test Leak test must satisfy EN378 2 1 Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen Never pressurize more than 4 0 MPa 3 Conduct leak test by applying soap water etc to the connecting part of the pipes 4 Discharge nitrogen 5 Evacuate and check vacuum again 1 6 If the vacuum gauge no longer rises the st...

Page 12: ...s relate to the refrigerant piping length as in Maximum total one way piping length of the table in paragraph Allowable pipe length and height difference on page 5 Table 2 Total charging amount unit kg NOTE National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit Therefore an additional multilingu...

Page 13: ...side Make sure no external pressure is applied to the terminal connectors When installing the earth leakage breaker make sure that it is compatible with the inverter resistant to high frequency electrical noise to avoid unnecessary opening of the earth leakage breaker As this unit is equipped with an inverter installing a phase advancing capacitor not only will deteriorate power factor improvement...

Page 14: ...easons be sure to observe the following instruction Do not connect wires of different gauge to the same power supply terminal Looseness in the connection may cause overheating When connecting wires of the same gauge connect them according to the below figure Use the correct screwdriver to tighten the terminal screws Small screwdrivers can damage the screw head and prevent appropriate tightening Ov...

Page 15: ...e unit returns to normal operation 10 Check all functions according to the operation manual AZQS 71V1 100V1 125V1 140V1 100W1 125W1 140W1 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units for exact values 18 9 27 6 28 8 17 1 18 3 Recommended field fuse A 20 32 20 Wire type b b Only in protected pipes use H07RN F when protected pipes ...

Page 16: ...may have run out If the remote controller shows E3 E4 or L8 as an error code there is a possibility that either the stop valves are closed or that air inlet or air outlet are blocked If the error code U2 is displayed on the remote controller check for voltage imbalance If the error code U4 or UF is displayed on the remote controller check the inter unit branch wiring connection If the error code L...

Page 17: ...or discharge for V1 models only R3T Thermistor discharge pipe for W1 models only R3T Thermistor suction pipe for V1 models only R4T Thermistor suction pipe for W1 models only R4T Thermistor coil for V1 models only R5T Thermistor power module for W1 models only R5T Thermistor coil middle for V1 models only R6T Thermistor liquid R10T Thermistor fin RC Signal receiver circuit S1NPL Pressure sensor lo...

Page 18: ......

Page 19: ......

Page 20: ...4PW68422 1 03 2011 Copyright 2011 Daikin ...

Reviews: