1-15

Dry Mode

When the air humidity is high, the unit can operate in dry 
mode. Press <MODE> button and choose <DRY>.
If the room temperature is 2°C/3.6°F higher than the 
set temperature, the air conditioner will operate under  
cooling mode until it reaches within the 2°C/3.6°F range 
of difference compared to the set temperature before it 
converts to dry mode.
If the room temperature is within the 2°C/3.6°F range of 
difference compared to the set temperature, it will directly 
operate under dry mode.
The unit will operate at LOW speed under dry mode.

Heat Mode (for heat pump unit only)

When the unit is switched on from cold start or defrosting 
cycle, the indoor fan will start to operate only after the coil 
reaches the desired temperature.
When the set temperature is achieved, the indoor fan will 
operate until the coil cannot provide anymore additional 
heat.

Air Flow Control

For more effective air circulation, you can manually adjust 
the air discharge grille to the left or right.
During cool mode operation and dry mode operation, do 
not direct the air discharge louver downwards for too long. 
If operating continues in this way, condensation may occur 
on the louver, thus resulting in drippings.

Overheating Protection (for heat pump unit only)

In case the internal and/or the external temperature is too 
high, or that the 

fi

 lter is dirty and clogged up, the  refrigerant 

may be overheated. The compressor will cut out when the 
condensing temperature reaches 62°C/143.6°F.

Frost Prevention

When the air 

fi

 lter is dirty, the evaporating temperature will 

decrease and eventually cause frosting.
If the evaporating temperature reaches -1°C/33.8°F, the 
unit will trip.

Fan Speed And Rated Cooling Capacity

The rated cooling capacity is provided at the HIGH fan 
speed.
The cooling capacity is lower when the unit is operating at 
MEDIUM and LOW fan speed.

Notes On Flaps And Louvers Angles

When “

SWING button

” is selected, the flaps swinging 

range depends on the operation mode. (See the figure.)

ATTENTION

Always use a remote controller to adjust the flaps angle. 
If you attempt to move it forcibly with hand when it is 
swinging, the mechanism may be broken.
Be careful when adjusting the louvers. Inside the air outlet, 
a fan is rotating at a high speed.

NOTE :  When the option is selected, the power supply of 

the unit need to be reset in order to activate the 
function.

AIR CONDITIONER UNIT OPERATION

OPERATING RANGE

HOT KEEP

OFF

INTERVAL

ON

ON/OFF switch

COOLING

Indoor WB (

˚

C)

DB: Dry bulb 
WB: Wet bulb

HEATING

Outdoor DB 

(

˚

C)

46

43

19

14

19

23

Indoor DB (

˚

C)

15

20

27

Outdoor WB 

(

˚

C)

18

10

-9

1 IM-5WMJR-0515(0)-DAIKIN SIESTA15   15

1 IM-5WMJR-0515(0)-DAIKIN SIESTA15   15

6/3/15   3:49:21 PM

6/3/15   3:49:21 PM

Summary of Contents for Siesta ATYN20LV1

Page 1: ...1 ATYN25LV1 ARYN25LV1 ATYN35LV1 ARYN35LV1 ATYN50LV1 ARYN50LV1 ATYN60LV1 ARYN60LV1 WALL MOUNTED R410A SPLIT TYPE AIR CONDITIONER IM 5WMJR 0515 0 DAIKIN SIESTA Part No R08019043338 Installation Manual R...

Page 2: ......

Page 3: ...WS INSIDE LOUVER SIGNAL RECEIVER INDOOR UNIT ON OFF SWITCH ROOM TEMPERATURE THERMISTOR INSIDE NAME PLATE TERMINAL BLOCK WITH EARTH TERMINAL F E J G G L D B K M A Gas pipe end INSTALLATION PLATE 20 25...

Page 4: ...1065 310 224 190 173 61 40 45 48 91 219 580 45 Recommended mounting plate retention spots 7 spots in all Dimension Model A B C D E F G H I J K L M 20 25 35J 800 288 206 104 141 30 46 55 56 153 181 20...

Page 5: ...C G H I J Dimension Model O P Q R S T 20C 22 3 19 65 80 30 25 35C 18 3 19 65 80 30 T All dimensions are in mm B A Q P R S D O K L L M N F E C G H I J N Dimension Model A B C D E F G H I J K L 50C 855...

Page 6: ...om TVs and radios to prevent distorted pictures and static Depending on the type and source of the electrical waves static may be heard even when more than 1m away Please take note of the following im...

Page 7: ...crews 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down INSTALLATION DIAGRAM Indoor unit Service lid Cut thermal insulation pipe to an appropriate length and wrap it...

Page 8: ...age Please remove side plate when connecting the piping and connecting cord PUSH PULL UP BASE A DRAIN ELBOW DRAIN ELBOW PLUG INSTALLATION OF THE OUTDOOR UNIT The outdoor unit must be installed in such...

Page 9: ...ace for performance Required space Right back piping All dimensions are in mm Right bottom piping Right side piping Remove pipe port cover here for right side piping Left back piping Left side piping...

Page 10: ...or Unit Push up the marked area at the lower part of the front grille to release the claws Mounting plate Interconnecting wires Hang indoor unit s hook here Wire guide When stripping the ends of inter...

Page 11: ...m 12 12 12 20 20 Max Allowable Elevation E m 5 5 5 15 15 Gas Pipe Size mm in 9 52 3 8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 Liquid Pipe Size mm in 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 Heat P...

Page 12: ...firmly on the swaging block Match the centers of both the swaging block and the flaring punch then tighten the flaring punch fully Piping Connection To The Units Align the center of the piping and tig...

Page 13: ...Supply Cable Attach insulation sleeve Round crimp style terminal Electric wire All wires must be firmly connected All wires must not touch the refrigerant piping compressor or any moving parts of the...

Page 14: ...pressor Remove the caps from the valve and the service port Connect the center of the charging gauge to the vacuum pump Connect the charging gauge to the service port of the 3 way valve Start the vacu...

Page 15: ...h an auto mode sensor whereby it will provide reasonable room temperature by switching automatically to either cool or heat mode according to the temperature set by the user ON OFF Cool Heat Timer Sle...

Page 16: ...1 time Room air sensor contact Loose Short Call your dealer Blink E1 3 times Outdoor coil sensor open Call your dealer Blink E3 2 times Indoor coil sensor open Call your dealer Blink E2 1 time Compre...

Page 17: ...ulting in drippings Overheating Protection for heat pump unit only In case the internal and or the external temperature is too high or that the filter is dirty and clogged up the refrigerant may be ov...

Page 18: ...ing shaft is detached Slide the right rotating shaft to the left and pull it to the front side to remove it 2 Attach the front panel Align the right and left rotating shafts of the front panel with th...

Page 19: ...erature is not high enough Discharge air flow has bad odour 4 Odours may be caused by cigarettes smoke particles perfume etc which might have adhered onto the coil Condensation on the front air grille...

Page 20: ...MEMO...

Page 21: ...2 1 XEMA A MEP 20 25 35J 1 2 A B C D E F G H I J K L M 20 25 35J 800 288 206 166 184 42 46 55 56 154 182 263 52 K ATYN A B C H I B F E J G G L D B K M A 20 25 35J 65 F 5...

Page 22: ...L M 20 25 35J 800 288 206 104 141 30 46 55 56 153 181 207 52 A B C D E F G H I J K L M 50 60J 1065 310 224 190 173 61 40 45 48 91 219 580 45 D B G H J L M A K F I G F E 50 60J 7 5 65 E F G I K M L J...

Page 23: ...521 250 485 175 36 95 93 86 68 441 130 111 15 O P Q R S T 20C 22 3 19 65 80 30 25 35C 18 3 19 65 80 30 T B A Q P R S D O K L L M N F E C G H I J N A B C D E F G H I J K L 50C 855 628 328 520 179 46 9...

Page 24: ...2 4 H MAH E CTOPO HO 1 1 OFF...

Page 25: ...2 5 M4 x 12L e 75 50 1 2 3 500...

Page 26: ...2 6 2 A A H A B C D acc o e 300 1000 300 500 A B H 2 H pe c C D pe c...

Page 27: ...2 7 50 50 75 c y ox K K 50 60J 20 25 35J K 20 25 35J 20 25 35J 50 60J 65...

Page 28: ...173 61 310 61 48 45 580 1065 219 40 40 91 45 65 166 184 181 7 55 5 54 5 153 8 263 51 9 800 45 9 42 2 288 42 2 45 9 poc ep e ec ep o 50 60J 20 25 35J 5 65 7 65 5 104 141 30 46 56 181 800 55 207 52 153...

Page 29: ...2 9 7 5 ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C M L 3 Ma L 12 12 12 20 20 E 5 5 5 15 15 9 52 3 8 9 52 3 8 12 70 1 2 12 70 1 2 15 88 5 8 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 6 35 1 4 L E...

Page 30: ...2 3 8 42 31 0 12 70 1 2 55 40 6 15 88 5 8 65 48 0 19 05 3 4 78 57 6 C D A 1 4 6 35 1 3 0 7 3 8 9 52 1 6 1 0 1 2 12 70 1 9 1 3 5 8 15 88 2 2 1 7 3 4 19 05 2 5 2 0 II III IV L 3 8 OD9 52 0 18 1 3 1 2 OD...

Page 31: ...2 11 N OF 4WV N1 L COMP N OF 4WV COMP ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C 220 240V 50 2 1 5 3 2 5 3 2 1 5 5 2 5 5 A 15 20 8 N L2 L L1 3 H07RN F...

Page 32: ...2 12 R410A R410A 1 6 R22 R410A POE PVE R410A R22 R410A POE PVE R22 R410A R410A R410A R22 C 3 30 760 760 3 2 4 o 3 760 760 3 3...

Page 33: ...2 13 ATYN 20 25 35 50 60J ON OFF 7 5 7 5 1 2 1 ATYN35J ARYN35C 12 4 5 4 5 x 9 40 5 1 R410A ATYN 20J 25J 35J 50J 60J ARYN 20C 25C 35C 50C 60C 20 16 16 19 16...

Page 34: ...2 14 1 E1 3 E3 2 E2 1 E4 3 E5 6 E8 4 E9...

Page 35: ...2 15 2 C 3 6 F 2 C 3 6 F 2 C 3 6 F 62 C 143 6 F 1 C 33 8 F HIGH HOT KEEP OFF INTERVAL ON X DB WB WB C DB C 46 43 19 14 19 23 DB C 15 20 27 WB C 18 10 9...

Page 36: ...2 16 FRONT 2 1 3 4 2 2 1 2 c 3 CTOPO HO 40 104 F 1 2 3 1 2 40 104 F 1 2 1 2...

Page 37: ...2 17 CTOPO HO 40 C 3 1 3 4 2 3 4 5 6 2 30 C 86 F...

Page 38: ......

Page 39: ......

Page 40: ...contain herein at any time without prior notification P O Box 18674 Galleries 4 11th Floor Downtown Jebel Ali Dubai UAE Zandvoordestraat 300 B 8400 Oostende Belgium Importer for Turkey Allianz Plaza K...

Reviews: