![background image](http://html1.mh-extra.com/html/daikin/siesta-atyn20lv1/siesta-atyn20lv1_installation-manual_4705551011.webp)
English
1-9
*
Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
Remark:
The refrigerant pre-charged in the outdoor unit is for piping length up to 7.5m.
Outdoor Unit
L
E
Indoor unit
Model
Indoor (ATYN)
20J
25J
35J
50J
60J
Outdoor (ARYN)
20C
25C
35C
50C
60C
Min. Allowable Length (L), m
3
Max. Allowable Length (L), m
12
12
12
20
20
Max. Allowable Elevation (E), m
5
5
5
15
15
Gas Pipe Size, mm/(in)
9.52
(3/8")
9.52
(3/8")
12.70
(1/2")
12.70
(1/2")
15.88
(5/8")
Liquid Pipe Size, mm/(in)
6.35
(1/4")
6.35
(1/4")
6.35
(1/4")
6.35
(1/4")
6.35
(1/4")
Heat Pump Model
If the pipe is too long, both the capacity and reliability of the unit will drop. As the number of bends increases, resistance to
the flow of refrigerant system increases, thus lowering cooling capacity. As a result, the compressor may become defective.
Always choose the shortest path and follow the recommendations as tabulated below:
REFRIGERANT PIPING
1 IM-5WMJR-0515(0)-DAIKIN SIESTA9 9
1 IM-5WMJR-0515(0)-DAIKIN SIESTA9 9
6/1/15 3:20:42 PM
6/1/15 3:20:42 PM
Summary of Contents for Siesta ATYN20LV1
Page 2: ......
Page 20: ...MEMO...
Page 24: ...2 4 H MAH E CTOPO HO 1 1 OFF...
Page 25: ...2 5 M4 x 12L e 75 50 1 2 3 500...
Page 26: ...2 6 2 A A H A B C D acc o e 300 1000 300 500 A B H 2 H pe c C D pe c...
Page 27: ...2 7 50 50 75 c y ox K K 50 60J 20 25 35J K 20 25 35J 20 25 35J 50 60J 65...
Page 34: ...2 14 1 E1 3 E3 2 E2 1 E4 3 E5 6 E8 4 E9...
Page 36: ...2 16 FRONT 2 1 3 4 2 2 1 2 c 3 CTOPO HO 40 104 F 1 2 3 1 2 40 104 F 1 2 1 2...
Page 37: ...2 17 CTOPO HO 40 C 3 1 3 4 2 3 4 5 6 2 30 C 86 F...
Page 38: ......
Page 39: ......