background image

MODELS

RZR36PVJU
RZR42PVJU
RZQ30PVJU9
RZQ36PVJU9
RZQ42PVJU9

Read these instructions carefully before installation.
Keep this manual in a handy place for future reference.
This manual should be left with the equipment owner.

Lire soigneusement ces instructions avant l’installation.
Conserver ce manuel à portée de main pour référence ultérieure.
Ce manuel doit être donné au propriétaire de l’équipement.

Lea cuidadosamente estas instrucciones antes de instalar.
Guarde este manual en un lugar a mano para leer en caso de 
tener alguna duda.
Este manual debe permanecer con el propietario del equipo.

SPLIT SYSTEM Air Conditioners

INSTALLATION MANUAL

English

Français

Español

 

00_CV_3PN07193-7H.fm  Page 1  Saturday, December 25, 2010  1:03 PM

Summary of Contents for RZR36PVJU

Page 1: ...t l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde est...

Page 2: ...t in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant lea...

Page 3: ...the air or where volatile flammables such as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used...

Page 4: ...ind whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following...

Page 5: ...onduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pres...

Page 6: ...door unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 Whe...

Page 7: ...Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in...

Page 8: ...nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If the...

Page 9: ...efrigerant other than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table...

Page 10: ...acuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture or have leakage If there is a possibility of moisture remaining in the p...

Page 11: ...a hexagon wrench into the valve stem and turn the valve stem clockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is closed The valve is sealed in the arrow area Take c...

Page 12: ...upply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmissio...

Page 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU9 60Hz 208 230V 30A 27A RZQ36PVJU9 RZR36PVJU RZQ42PV...

Page 14: ...K 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas li...

Page 15: ...utdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis played...

Page 16: ...op valves in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based o...

Page 17: ...ns in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximum...

Page 18: ...1101 HT 3PN07193 7H EM10A070 00_CV_3PN07193 7H fm Page 2 Saturday December 25 2010 1 03 PM...

Reviews: