Installation manual

12

Precautions on wiring of power supply and inter-unit 
wiring

Use a round crimp-style terminal for connection to the power
supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following
instruction.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them 
according to the below figure.

Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.

Over-tightening the terminal screws can damage the screws.

See the table below for tightening torques for the terminal
screws.

Refer to the installation manual attached to the indoor unit for
wiring of indoor units, etc.

Attach an earth leakage breaker and fuse to the power supply
line. 

(See figure 9)

In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.

Specifications of standard wiring components

Equipment complying with EN/IEC 61000-3-12

(1)

T

EST

 

OPERATION

Pre-run checks

Be sure to perform a test run.

Be sure to fully open the liquid-side and gas-side stop valves. If
you operate the unit with stop valves closed, the compressor will
break down.

Be sure to execute the first test run of the installation in cooling
mode operation.

Never leave the unit unattended with an open front panel during
test run.

Tightening torque (N•m)

M4 (X1M)

1.2~1.8

M4 (EARTH)

1.2~1.4

M5 (X1M)

2.0~3.0

M5 (EARTH)

2.4~2.9

I

Pair

M

Master

II

Twin

S

Slave

III

Triple

1

Earth leakage breaker

IV

Double twin

2

Fuse

3

Remote controller

1

2 3

1

Round pressure terminal

2

Cut out section

3

Cup washer

RZQSG71

RZQS71

RZQS100

RZQS125

RZQS140

Minimum circuit 
amps (MCA)

(a)

(a) Stated values are maximum values (see electrical data of combination with 

indoor units for exact values).

21.2

18.9

27.6

28.8

Recommended field 
fuse (A)

25

20

32

Wire type

(b)

(b) Only in protected pipes, use H07RN-F when protected pipes are not used.

H05VV-U3G

Size

Wiring size must comply with the applicable local and 

national code

Wire type of wiring 
between the units

H05VV-U4G2.5

NOTE

The earth leakage breaker must be a high-speed type
breaker of 30 mA (<0.1 s).

(1) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

WARNING

Live parts can be easily touched by accident.

Never leave the unit unattended during installation or
servicing when the service panel is removed.

NOTE

Note that during the first running period of the unit,
required power input may be higher. This phenomenon
originates from the compressor that requires a 50-hour
run-in period before reaching smooth operation and
stable power consumption.

Items to check

Electrical wiring
Inter-unit wiring
Ground wire

Is the wiring as mentioned on the wiring
diagram?
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.

Is the unit properly grounded?

Is the wiring between units connected in series
correct?

Are any of the wiring attachment screws loose?

Is the insulation resistance at least 1 M

Ω

?

-

Use a 500 V mega-tester when measuring 
insulation.

-

Do not use a mega-tester for low-voltage 
circuits.

Refrigerant piping

Is the size of the piping appropriate?

Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?

Are the stop valves for both the liquid side and
the gas side open?

Extra refrigerant

Did you write down the extra refrigerant and the
refrigerant piping length?

Summary of Contents for RZQSG71L3V1B

Page 1: ...INSTALLATION MANUAL RZQSG71L3V1B RZQS71D7V1B RZQS71D2V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B Split System air conditioners...

Page 2: ...6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2...

Page 3: ...omo se establece en A y es valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabele...

Page 4: ...al como estabelecido em A e com o parecer positivo de B de acordo com o Certi cado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certi kat C 11 Information enligt A och g...

Page 5: ...pment Make certain that all electrical work is carried out by quali ed personnel according to the local laws and regulations and this installation manual using a separate circuit Insuf cient capacity...

Page 6: ...ine vapour is present This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Sound level is less than 70 dB A Pro...

Page 7: ...to rise of high pressure When a strong wind blows continuously on the face of the unit the fan can start rotating very fast until it breaks Refer to the gures for installation of this unit in a place...

Page 8: ...piping using a drain socket optional Make sure the drain works properly INSTALLATION SERVICING SPACE The numerical gures used in here represent the dimensions for the 71 100 125 140 class models Figur...

Page 9: ...L4 L7 for double twin These pipe sizes must have the same size as the connected indoor units pipe sizes Branch see marking on gures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L...

Page 10: ...or vertically Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed...

Page 11: ...now closed Cautions for handling the valve cover The valve cover is sealed where indicated by the arrow Refer to the gure Take care not to damage it After operating the valve be sure to tighten the v...

Page 12: ...easing nitrogen into the piping will create large quantities of oxidised lm on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal oper...

Page 13: ...frigerant unit kg 1 Use a 2 stage vacuum pump with a non return valve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg Evacuate the system from the liquid and gas pipes by using a vacuum pump for more...

Page 14: ...t a malfunction After nishing the pumping down operation make sure to have removed the insulation sheet that was placed in the switch box as a protective measure like in chapter Preliminary measures o...

Page 15: ...Secure the ground wire to the stop valve attachment plate one more time along with the electric wiring and the inter unit wiring Lay the electrical wiring so that the front cover does not rise up whe...

Page 16: ...2 Cut out section 3 Cup washer RZQSG71 RZQS71 RZQS100 RZQS125 RZQS140 Minimum circuit amps MCA a a Stated values are maximum values see electrical data of combination with indoor units for exact value...

Page 17: ...panel with infra red receiver rst 5 In case the panels of indoor units are not yet installed to the indoor units make sure to shut off the power supply after nishing the complete test run 6 A complete...

Page 18: ...4T Thermistor coil R5T Thermistor coil middle R6T Thermistor liquid R10T Thermistor n RC Signal receiver circuit S1NPH Pressure sensor high S1PH Pressure switch high TC Signal transmission circuit V1R...

Page 19: ......

Page 20: ...4P342104 1 Copyright 2013 Daikin...

Reviews: