![background image](http://html2.mh-extra.com/html/daikin/rzqsg-ly1/rzqsg-ly1_technical-data-manual_5690933009.webp)
3
2
• Split - Sky Air • RZQSG-L(8)Y1
7
• Outdoor Unit • RZQSG-L(8)Y1
2
Specifications
Notes
(1) PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
(2) See separate drawing for electrical data
Piping connections
Liquid
Quantity
1
Type
Flare connection
OD
mm
9.52
Gas
Quantity
1
Type
Flare connection
OD
mm
15.9
Drain
Quantity
5
Type
Hole
ID
mm
-
OD
mm
26
Piping length
OU - IU Min.
m
5
Max.
m
50
System Equival
ent
m
70
Chargel
ess
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU Max.
m
30
IU - IU
Max.
m
0.5
Heat insulation
Both liquid and gas pipes
Defrost method
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan driver overload protector
03
Fuse
2-9 Electrical Specifications
RZQSG100L8Y1
RZQSG125L8Y1
RZQSG140LY1
Power supply
Name
Y1
Phase
3N~
Frequency
Hz
50
Voltage
V
380-415
Voltage range
Min.
%
10
Max.
%
10
Current
Zmax
List
Complies to EN61000-3-11
Recommended fuses
A
20
25
Current - 50Hz
Maximum fuse amps (MFA)
A
20
Current - 60Hz
Maximum fuse amps (MFA)
A
-
Wiring connections
For power supply
Remark
See installation manual outdoor unit
For connection with
indoor
Remark
See installation manual outdoor unit
Power supply intake
Outdoor unit only
2-8 Technical Specifications
RZQSG100L8Y1
RZQSG125L8Y1
RZQSG140LY1
Summary of Contents for RZQSG-LY1