![background image](http://html2.mh-extra.com/html/daikin/rzqsg-ly1/rzqsg-ly1_technical-data-manual_5690933005.webp)
3
2
• Split - Sky Air • RZQSG-L(8)Y1
3
• Outdoor Unit • RZQSG-L(8)Y1
2
Specifications
Notes
(1) EER/COP according to Eurovent 2012, for use outside EU only
Notes
(1) EER/COP according to Eurovent 2012, for use outside EU only
2-1 Nominal Capacity And Nominal Input
FCQHG100F/RZQSG100L8Y1
FCQHG125F/RZQSG125L8Y1
FCQHG140F/RZQSG140LY1
Cooling capacity
Nom.
kW
9.5
12.0
13.4
Heating capacity
Nom.
kW
10.8
13.5
15.5
Power input
Cooling
Nom.
kW
2.57
3.71
4.17
Heating
Nom.
kW
2.51
3.60
4.29
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
A++
A
-
Pdesign
kW
9.50
12.00
-
SEER
6.70
5.40
-
Annual energy
consumption
kWh
496
778
-
Heating (Average
climate)
Energy label
A+
-
Pdesign
kW
8.03
-
SCOP
4.30
4.10
-
Annual energy
consumption
kWh
2,614
2,741
-
Nominal efficiency
(cooling at 35°/27°
nominal load, heating
at 7°/20° nominal
load)
EER
3.70
3.23
3.21
COP
4.30
3.75
3.61
Annual energy consumption
kWh
1,285
1,855
2,085
Energy label
Cooling
A
-
Heating
A
-
2-2 Nominal Capacity And Nominal Input
FCQG100F/RZQSG100L8Y1
FCQG125F/RZQSG125L8Y1
FCQG140F/RZQSG140LY1
Cooling capacity
Nom.
kW
9.5
12.0
13.4
Heating capacity
Nom.
kW
10.8
13.5
15.5
Power input
Cooling
Nom.
kW
2.88
3.74
4.45
Heating
Nom.
kW
3.05
3.96
4.54
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
A++
A
-
Pdesign
kW
9.50
12.00
-
SEER
6.50
5.30
-
Annual energy
consumption
kWh
512
792
-
Heating (Average
climate)
Energy label
A+
-
Pdesign
kW
7.60
8.03
-
SCOP
4.10
4.01
-
Annual energy
consumption
kWh
2,595
2,803
-
Nominal efficiency
(cooling at 35°/27°
nominal load, heating
at 7°/20° nominal
load)
EER
3.30
3.21
3.01
COP
3.54
3.41
Annual energy consumption
kWh
1,440
1,870
2,225
Energy label
Cooling
A
-
Heating
B
-
2-3 Nominal Capacity And Nominal Input
FAQ100C/RZQSG100L8Y1
Cooling capacity
Nom.
kW
9.5
Heating capacity
Nom.
kW
10.8
Power input
Cooling
Nom.
kW
3.16
Heating
Nom.
kW
3.17
Summary of Contents for RZQSG-LY1