![Daikin RZQSG-LY1 Technical Data Manual Download Page 8](http://html2.mh-extra.com/html/daikin/rzqsg-ly1/rzqsg-ly1_technical-data-manual_5690933008.webp)
• Outdoor Unit • RZQSG-L(8)Y1
2
• Split - Sky Air • RZQSG-L(8)Y1
6
2
Specifications
2-8 Technical Specifications
RZQSG100L8Y1
RZQSG125L8Y1
RZQSG140LY1
Capacity control
Method
Inverter controlled
Casing
Colour
Ivory white
Material
Painted galvanized steel plate
Dimensions
Unit
Height
mm
990
1,430
Width
mm
940
Depth
mm
320
Packed unit
Height
mm
1,170
1,610
Width
mm
1,015
Depth
mm
422
Weight
Unit
kg
82
101
Packed unit
kg
94
114
Heat exchanger
Fin
Type
WF fin
Treatment
Anti-corrosion treatment (PE)
Compressor
Quantity
1
Type
Hermetically sealed swing compressor
Starting method
Inverter driven
Fan
Type
Propeller fan
Discharge direction
Horizontal
Quantity
1
2
Air flow rate
Cooling Nom.
m³/min
76
77
83
Super
low
m³/min
-
cfm
-
Heating Nom.
m³/min
83
62
Super
low
m³/min
-
cfm
-
Fan motor
Quantity
1
2
Model
Brushless DC motor
Output
W
200
94
Drive
Direct drive
Speed
Cooling Super
low
rpm
-
Heating Super
low
rpm
-
Sound power level
Cooling
dBA
69
70
69
Heating
dBA
-
Sound pressure level
Cooling
Nom.
dBA
53
54
53
Heating
Nom.
dBA
57
58
54
Night quiet mode
Level 1
dBA
49
Operation range
Cooling
Ambien
t
Min.
°CDB
-15
Max.
°CDB
46
Heating
Ambien
t
Min.
°CWB
-15
Max.
°CWB
15.5
Refrigerant
Type
R-410A
Charge
kg
2.9
4.0
Control
Expansion valve (electronic type)
GWP
1,975
Circuits
Quantity
1
Refrigerant oil
Type
FVC50K
Charged volume
l
0.9
1.35