background image

• Outdoor Units • R-410A • RZQS71-140C7V1B

1

10

• Split Sky Air • Outdoor Units

35

10

Installation

10 - 1 Installation method

3TW26739-4

Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit’s drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.

2. Installing multiple units (2 units or more) in lateral

connection per row

1. Obstacles exist in front of the outlet side

1. Installation of one unit per row

RZQS71~ 140C

A. Non stacked installation

2. Obstacles exist in front of the air inlet

B. Stacked installation

Legend

C. Multiple-row installation

Relation of dimensions of H, A, and L are shown in the
table below.

L

A

L

H

0 < L

1/2 H

150 (250)

1/2 H < L

200 (300)

H < L

Installation impossible

Suction side obstacle

Discharge side obstacle

Left side obstacle

Right side obstacle

Top side obstacle

Obstacle is present

In these cases, close the bottom of
the installation frame to prevent
discharged air from being
bypassed.

In these cases, only 2 units can be
installed.

This situation is not allowed.

Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.

Summary of Contents for RZQS71-140C7V1B

Page 1: ...technical data Split Sky Air air conditioning systems RZQS71 140C7V1B EEDEN08 100...

Page 2: ...the Eurovent Directory Daikin s unique position as a man ufacturer of air conditioning equip ment compressors and refrige rants has led to its close involve ment in environmental issues For several ye...

Page 3: ...technical data Split Sky Air air conditioning systems RZQS71 140C7V1B EEDEN08 100...

Page 4: ...cations 9 3 Electrical data 10 4 Options 12 5 Capacity tables 13 Combination table 13 Cooling capacity tables 15 Heating capacity tables 22 6 Dimensional drawing centre of gravity 27 Dimensional drawi...

Page 5: ...rgy efficiency and very low sound level An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures During start up the room can be...

Page 6: ...capacity Standard kW 7 1 10 0 12 5 13 4 Heating capacity Standard kW 8 0 11 2 14 0 15 5 Power Input Cooling Standard kW 2 52 3 83 4 4 4 97 Heating Standard kW 2 40 3 47 4 24 4 99 For combination indo...

Page 7: ...8 10 10 Face Area m 0 641 0 641 0 98 0 98 Nr of Stages 34 34 52 52 Tube type Hi XSS 8 Fin Type WF fin Treatment Anti corrosion treatment PE Fan Type Propeller Discharge direction Horizontal Quantity 1...

Page 8: ...ent m 40 70 70 70 Chargeless m 30 30 30 30 Additional Refrigerant Charge kg m see installation manual 4PW40416 1 see installation manual 4PW34874 1 Installation height difference Maximum m 15 30 30 0...

Page 9: ...98 198 Maximum V 264 264 264 264 Current Rsce Sse kVA Equipment complying with EN 61000 3 12 Recomended fuses A 20 20 32 32 Wiring connections For Power Supply Remark see installation manual 4PW40416...

Page 10: ...WB 2 TOCA means the total value of each OC set 3 Voltage range Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed operation range li...

Page 11: ...NOTES 1 RLA is based on the following conditions Power supply 50Hz 230V Cooling Indoor temperature 27 CDB 19 CWB Outdoor temperature 35 CDB Heating Indoor temperature 20 0 CDB Outdoor temperature 7 0...

Page 12: ...1 140C7V1B 4 Options Available options for RZQS100 140C7V1B Name of option Kit name RZQS125C7V1B RZQS140C7V1B Central drain pan kit KKPJ5F180 Refrigerant branch piping Twin KHRQ22M20TA Triple KHRQ127H...

Page 13: ...indoor units installed in same room 4 When different indoor models are used in combination designate the infrared remote controller that is equipped with the most functions as the main unit In table a...

Page 14: ...dividual indoor capacities are not given because the combinations are for simultaneous operation indoor units installed in same room 3 When different indoor models are used in combination designate th...

Page 15: ...mark Q show rated capacity and rated coefficient of power input However the max capacity is not guaranteed except at standard condition 3 On the tables Q show rated capacity and rated coefficient of...

Page 16: ...except at standard condition 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min...

Page 17: ...SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are based on following conditions Outdoor air 85 RH however th...

Page 18: ...n 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to...

Page 19: ...W NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor heat 2 On the figure the mark j show the max at standard conditions On the figure the mark Q show rated capaci...

Page 20: ...Units 20 Outdoor Units R 410A RZQS71 140C7V1B 5 Capacity tables 5 2 Cooling capacity tables 3TW29069 3 RZQS71 100C7V1B Capacity Field piping length m Cooling Heating Capacity in function of field pip...

Page 21: ...S71 140C7V1B 1 5 Split Sky Air Outdoor Units 21 5 Capacity tables 5 2 Cooling capacity tables 3TW29069 3 RZQS125 140C Capacity Field piping length m Cooling Heating Capacity in function of field pipin...

Page 22: ...of power input However the max capacity is not guaranteed except at standard condition 3 On the tables Q show rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC...

Page 23: ...rated capacity and rated coefficient of power input 4 SHC is based on each EWB and EDB SHC SHC correction for other dry bulb SHC 0 02 x AFR m 3 min x 1 BF x DB EDB Add SHC to SHC 5 Capacities are bas...

Page 24: ...r flow rate and BF are tabulated below Pair Model FCQH125C FCQ125C FBQ125 FHQ125 FAQ125 FVQ125 AFR BF 32 5 0 19 27 5 0 19 35 0 14 30 0 13 45 0 25 32 0 16 Twin Model FCQ60Cx2 FFQ60x2 FBQ60x2 FHQ60x2 AF...

Page 25: ...which include a deduction for indoor fan motor heat 2 On the figure the mark j show the max at standard conditions On the figure the mark Q show rated capacity and rated coefficient of power input Ho...

Page 26: ...point Heating capacity kW Coefficient of power input NOTES 1 Ratings shown are net capacities which include a deduction for indoor fan motor heat 2 On the figure the mark j show the max at standard c...

Page 27: ...5 Refrigerant piping intake 6 Power supply wiring intake knock out hole J34 7 Control wiring intake Knock out hole J27 8 Drain outlet RZQS71 100C Hole for anchor bolt 4 M12 3TW26364 1 1 Gas pipe conne...

Page 28: ...3 1 6 Split Sky Air Outdoor Units 28 Outdoor Units R 410A RZQS71 140C7V1B 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 4TW30469 3 RZQS71 100C7V1B 4TW29169 4 RZQS125 140C...

Page 29: ...ressure switch Filter Low pressure sensor 3TW29165 2 RZQS71 140C Twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchanger Filter Stop valve with service port 5 16 flare...

Page 30: ...e branch and the indoor units should have the same size as the indoor connections 3TW29165 4 RZQS125 140C Double twin Indoor unit Field piping J15 9 Field piping J9 5 Low pressure sensor Heat exchange...

Page 31: ...board Main A2P Printed circuit board Inverter BS1 BS4 Push button switch C1 C3 Capacitor DS1 Dip switch F1U Fuse T 6 3A 250V F6U Fuse T 3 15A 250V H1P 7P A2P Light emitting diode service monitor oran...

Page 32: ...sure level A scale according to IEC 3 Reference acoustic pressure 0dB 20 Pa 4 Data is valid at nominal operation condition Measuring location discharge side 3TW30477 1 Sound pressure level dB Octave b...

Page 33: ...peration condition 3 dB A A weighted sound pressure level A scale according to IEC 4 Reference acoustic pressure 0dB 20 Pa Measuring location discharge side 3TW29177 1 Sound pressure level dB Octave b...

Page 34: ...ZQS100C7V1B NOTES 1 dB A A weighted sound power level A scale according to IEC 2 Reference acoustic intensity 0dB 10E 6 W m_ 3 Measured according ISO3744 3TW29167 3 Sound power level dB Octave band ce...

Page 35: ...er row RZQS71 140C A Non stacked installation 2 Obstacles exist in front of the air inlet B Stacked installation Legend C Multiple row installation Relation of dimensions of H A and L are shown in the...

Page 36: ...e icing To reduce the freeze up operation indoor de icing frequency it is recommended to install the outdoor unit in a location not exposed to wind 3TW29063 1A RZQS125 140C Model name RZQS125C7V1B RZQ...

Reviews: