![Daikin RZQS71-140C7V1B Technical Data Manual Download Page 8](http://html1.mh-extra.com/html/daikin/rzqs71-140c7v1b/rzqs71-140c7v1b_technical-data-manual_2460035008.webp)
3
1
2
• Split Sky Air • Outdoor Units
8
• Outdoor Units • R-410A • RZQS71-140C7V1B
2
Specifications
Sound Level
(nominal)
Cooling
Sound
Power
dBA
65
67
67
68
Sound
Pressure
(Standard)
dBA
49
51
51
52
Heating
Sound
Pressure
(Standard)
dBA
51
55
53
54
Sound Level
(Night quiet)
Sound Pressure
dBA
47
49
49
50
Refrigerant
Type
R-410A
Charge
kg
2.75
2.75
3.7
3.7
Control
Expansion valve (electronic type)
Nr of Circuits
1
1
1
1
Refrigerant Oil Type
FVC50K
FVC50K
Daphne FVC68D
Daphne FVC68D
Charged Volume
l
0.75
0.75
1.0
1.0
Piping
connections
Liquid (OD)
Quantity
1
1
1
1
Type
Flare connection
Diameter
(OD)
mm
9.52
9.52
9.52
9.52
Gas
Quantity
1
1
1
1
Type
Flare connection
Diameter
(OD)
mm
15.9
15.9
15.9
15.9
Drain
Quantity
3
3
3
3
Type
Hole
Diameter
(OD)
mm
26
26
26
26
Piping Length
Minimum m
5
5
5
5
Maximum m
30
50
50
50
Equivalent m
40
70
70
70
Chargeless m
30
30
30
30
Additional Refrigerant Charge kg/m
see installation manual 4PW40416-1
see installation manual 4PW34874-1
Installation
height
difference
Maximum m
15
30
30.0
30.0
Max. internunit level
difference
m
0.5
0.5
0.5
0.5
Heat Insulation
Both liquid and gas pipes
Defrost Method
Pressure equalising
Defrost Control
Temperature
Sensor for outdoor heat exchanger temperature
Capacity Control Method
Inverter controlled
Safety Devices
High pressure switch
Fan motor thermal protector
Fuse
Standard
Accessories
Item
Tie-wraps
Quantity
2
2
2
2
Item
Installation manual
Quantity
1
1
1
1
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 5m, level difference : 0m
2-2 TECHNICAL SPECIFICATIONS
RZQS71C7V1B
RZQS100C7V1B
RZQS125C7V1B
RZQS140C7V1B