5 Commissioning

Installation manual

9

RZQG7 RZQG71~12 RZQG140L7Y1L
Split system air conditioners
4P473073-1A – 2019.04

4

Choose  a  knockout  hole  and  remove  the  knockout  hole  by
tapping  on  the  attachment  points  with  a  flat  head  screwdriver
and a hammer.

5

Route  the  wiring  through  the  frame  and  connect  the  wiring  to
the frame at the knockout hole.

Routing through
the frame

Choose one of the 3 possibilities:

a

b

a

b

a

b

2

3

1

a

 Power supply cable

b

 Interconnection cable

Connecting to the
frame

When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.

When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.

a b c

d

e

A B

A

 Inside of the outdoor unit

B

 Outside of the outdoor unit

a

 Wire

b

 Bush

c

 Nut

d

 Frame

e

 Hose

6

Reattach the service cover.

7

Connect an earth leakage circuit breaker and fuse to the power
supply line.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

4.6.2

To check the insulation resistance of the
compressor

NOTICE

If,  after  installation,  refrigerant  accumulates  in  the
compressor,  the  insulation  resistance  over  the  poles  can
drop,  but  if  it  is  at  least  1  MΩ,  then  the  unit  will  not  break
down.

▪ Use a 500 V mega-tester when measuring insulation.

▪ Do not use a mega-tester for low-voltage circuits.

1

Measure the insulation resistance over the poles.

If

Then

≥1 MΩ

Insulation resistance is OK. This procedure
is finished.

<1 MΩ

Insulation resistance is not OK. Go to the
next step.

2

Turn ON the power and leave it on for 6 hours.

Result: 

The  compressor  will  heat  up  and  evaporate  any

refrigerant in the compressor.

3

Measure the insulation resistance again.

5

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

5.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

Summary of Contents for RZQG71L9V1L

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners RZQG71L9V1L RZQG71L8Y1L RZQG100L8Y1L RZQG125L8Y1L RZQG140L7Y1L...

Page 2: ...1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB H...

Page 3: ...or 9 5 Commissioning 9 5 1 Checklist before commissioning 9 5 2 To perform a test run 10 5 3 Error codes when performing a test run 11 6 Disposal 11 7 Technical data 12 7 1 Service space Outdoor unit...

Page 4: ...a Make sure not to cover the drain holes of the bottom plate of the unit INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the fou...

Page 5: ...DANGER RISK OF BURNING 4 2 1 To connect the refrigerant piping to the outdoor unit 1 Do the following Remove the service cover a with screw b Remove the piping intake plate c with screw d c a b d 2 C...

Page 6: ...ng machine e Vacuum pump f Stop valve 4 3 2 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High on the unit name plate NOTICE Make sure to use a recommended bubble...

Page 7: ...ecking refrigerant piping Setup on page 6 4 4 4 To charge additional refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated gr...

Page 8: ...an or equal to the minimum Ssc value Model Minimum Ssc value RZQG71_V1 RZQG100 140_Y1 1170 kVA 4 5 2 Specifications of standard wiring components Component V1 Y1 71 71 100 125 140 Power supply cable M...

Page 9: ...ection cable d Liquid pipe e Liquid pipe insulation f Finishing tape 2 Install the service cover 4 6 2 To check the insulation resistance of the compressor NOTICE If after installation refrigerant acc...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 user interface When using BRC1E51 see the installation manual of the user interface When using BRC1D see the service manual of the user...

Page 11: ...ween outdoor unit and indoor units between indoor unit and user interface The fuse on the outdoor unit PCB has blown out E3 E4 or L8 The stop valves are closed The air inlet or air outlet is blocked E...

Page 12: ...prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the fr...

Page 13: ...citor DS1 DIP switch F1U F8U RZQG71_V1 F1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG_Y1 F1U F2U Fuse 31 5 A 250 V F1U A2P Fuse T 5 0 A 250 V F3U F6U Fuse T 6 3 A 250 V F...

Page 14: ......

Page 15: ......

Page 16: ...4P473073 1A 2019 04 Copyright 2017 Daikin 4P473073 1 A 0000000...

Reviews: