• Outdoor Unit • Optimized for seasonal efficiency • RZQG-L7V1
1
2
• Split - Sky Air
®
• Outdoor Unit
4
2
Specifications
Notes
(1) Energy label: scale from A (most efficient) to G (less efficient)
(2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions)
(3) Cooling: indoor temp. 27ºCDB, 19ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m; level difference: 0m
(4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m; level difference: 0m
(5) Annual energy consumption is according to Energy labeling directive 2002/31/EC
(6) SEER and SCOP are according to EN 14825
Notes
(1) Energy label: scale from A (most efficient) to G (less efficient)
(2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions)
(3) Cooling: indoor temp. 27ºCDB, 19.0ºCWB; outdoor temp. 35ºCDB; equivalent piping length: 5m
(4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m
(5) Annual energy consumption is according to Energy labeling directive 2002/31/EC
(6) SEER and SCOP are according to EN 14825
2-1 Nominal Capacity And Nominal Input
FDQ125C7VEB / RZQG125L7V1B
Cooling capacity
Nom.
kW
12.0 (3)
Heating capacity
Nom.
kW
13.5 (4)
Power input
Cooling
Nom.
kW
3.20
Heating
Nom.
kW
3.53
EER
3.75
COP
3.83
SEER
5.61 (6)
SCOP
4.05 (6)
Annual energy consumption
kWh
1,600
Energy label
Cooling
A
Heating
A
2-1 Nominal Capacity And Nominal Input
FAQ71CVEB / RZQG71L7V1B
FAQ100CVEB / RZQG100L7V1B
Cooling capacity
Nom.
kW
6.8 (3)
9.5 (3)
Heating capacity
Nom.
kW
7.5 (4)
10.8 (4)
Power input
Cooling
Nom.
kW
2.00
2.63
Heating
Nom.
kW
2.03
3.00
EER
3.40
3.62
COP
3.70
3.61
SEER
5.21 (6)
5.11 (6)
SCOP
3.9 (6)
4.01 (6)
Annual energy consumption
kWh
1,000
1,315
Energy label
Cooling
A
A
Heating
A
A