• Outdoor Unit • Optimized for seasonal efficiency • RZQG-L7V1
1
10
• Split - Sky Air
®
• Outdoor Unit
28
10
Wiring diagrams
10 - 1 Wiring Diagrams - Single Phase
∼
∼
∼
∼
∼
∼
2D074931A
RZQ 100-140L7V1
A1P
: Printed circuit board (Main)
A2P
: Printed circuit board
A3P
: Printed circuit board
A4P
: Printed circuit board
A5P
: Printed circuit board
BS1
∼
BS4
: Push button switch
C1
∼
C4
: Capacitor
DS1
: Dip switch
E1H
: Bottomplate heater (Option)
F1U,F3U, F4U
: Fuse (T 6.3A / 250V)
F6U
: Fuse (T 5A / 250V)
F7U,F8U
: Fuse (F 1.0A / 250V)
F11U
: Fuse (56A / 250V)
H1P
∼
H7P (A2P) : Light emitting diode (service monitor orange)
[H2P] Prepare, Test --------- Flickering
Malfunction Detection -- Light up
HAP (A1P)
: Light emitting diode (service monitor green)
K1M
: Magnetic contactor
K1R
: Magnetic relay (Y1S)
K4R
: Magnetic relay (E1H)(Option)
K10R
: Magnetic relay
L1R
: Reactor
M1C
: Motor (compressor)
M1F
: Motor (fan)(upper)
M2F
: Motor (fan)(lower)
PS
: Switching power supply
Q1DI
: Earth leakage circuit breaker(30mA)
R1
: Resistor
R2
: Resistor
R1T
: Thermistor (air)
R2T
: Thermistor (discharge)
R3T
: Thermistor (Suction)
R4T
: Thermistor (Heat exchanger)
R5T
: Thermistor (heat exchanger middle)
R6T
: Thermistor (liquid)
R10T
: Thermistor (fin)
RC
: Signal receiver circuit
S1PH
: Pressure switch (High)
TC
: Signal transmission circuit
V1R
: IGBT Power module
V2R,V3R
: Diode module
V1T
: IGBT
X1M
: Terminal strip (Power supply)
Y1E
: Electronic expansion valve
Y1S
: Solenoid valve (4 way valve)
Z1C
∼
Z3C
: Noise filter (ferrite core)
Z1F
∼
Z4F
: Noise filter
Optional connector
X1Y
: Connector
Notes:
1. This wiring diagram only applies to the outdoor unit.
2. L: Live, N: Neutral,
: Field wiring
3.
: Terminal strip
: Connector
: Connection
: Protective earth (screw)
: Relay connector
: Noiseless earth
: Terminal
: Option
4. Refer to the combination table and option manual, for connecting wiring to X6A and X28A.
5. Refer to the ’’Wiring diagram sticker’’ (on back of front plate) on how to use BS1
∼
BS4 and DS1 switch.
6. Do not operate the unit by short-circuiting protection device S1PH.
7. Colours: WHT=White, RED=Red, BLU=Blue, ORG=Orange,
BRN=Brown, GRN=Green, YLW=Yellow, BLK=Black
8. Confirm the method of setting the selector switches (DS1) by service manual.
Factory setting of all switches: ’’OFF’’.
Indoor
El. comp. Assy
(Position of
elements)
(Front)
Position of
compressor
terminal
(Back)
Outdoor
(Note 4)
1N
∼
50Hz
220-240V
G