background image

Si281314E

Procedure to Remove Propeller Fan and Fan Motor

Removal Procedure

3

2. Procedure to Remove Propeller Fan and Fan 

Motor

Procedure

Warning      Be sure to wait for 10 minutes or more after turning off all power 

supplies before disassembling work. 

Step

Procedure

Points

„

Remove the front panel 2, 
following the procedure 
indicated at "Removal of 
Outside Panels and 
Related Parts".

1. Remove the propeller fan

1

Remove the 4 screws 
that fix the discharge 
grille. Remove from 4 
hooks at upper and 
lower side and then 
remove the discharge 
grille. 

2

Remove the fan setting 
nut that fixes the 
propeller fan.

3

Remove the top 
panel, following the 
procedure indicated 
at "Removal of 
Outside Panels and 
Related Parts".

2. Remove the fan motor

„

In case of removing the 
connector, do not pull the 
lead wire. Hold the 
connector part and press the 
hook.

„

Precaution for the motor 
installation: 
Be sure to fix the lead wire of 
the motor. Otherwise the 
lead wire might be entangled 
with the motor and causes 
failure.

1

Remove the connector 
for the fan motor from 
the printed wiring board 
(PWB). (Refer to 

1)

2

Remove the 3 clamps 
which fix the lead wire. 
(3 hooks of partition 
plate)

3

Remove the 3 screws 
of the front panel and 
then pull lead wire 
frontward.

4

Pull out the fan motor, 
after removing the 4 
fixing bolts.

Propeller fan

Fan setting nut

Hooks

Hooks

Discharge grille

Connector for fan motor (X106A)

4 bolts

Clamp

Lead wire

Propeller fan

Summary of Contents for RZQ71KAVLT

Page 1: ...REMOVAL PROCEDURE S E R V I C E M A N U A L Outdoor Unit Inverter Pair Type 3 HP Class Si281314E...

Page 2: ...Service Manual Removal Procedure Outdoor Unit Applicable Models zHeat Pump RZQ71KAVLT...

Page 3: ...d Fan Motor 3 3 Procedure to Remove Switch Box 4 4 Procedure to Remove PCB Assy 1 5 5 Procedure to Remove Assy 2 6 6 Procedure to Remove Assy 3 7 7 Procedure to Remove Low Pressure Thermistor Electron...

Page 4: ...Remove the top panel after removing the 8 screws 3 Remove the front panel 1 after removing the 7 screws 4 Remove the right side panel after removing the 5 screws 5 Remove the front panel of the pipin...

Page 5: ...ve the top panel following the procedure indicated at Removal of Outside Panels and Related Parts 2 Remove the fan motor In case of removing the connector do not pull the lead wire Hold the connector...

Page 6: ...he switch box and the related parts Remove the connectors below Fan motor X106A Pressure thermistor X17A Coil of four way valve X25A Compressor relay X502A Remove the parts below Coil of motor operate...

Page 7: ...ing the procedure indicated at Removing Outside Panels and Related Parts Remove the switch box following the procedure indicated at Removing switch box 1 Remove the PCB for the display A2P 1 Remove th...

Page 8: ...electric component 1 Remove the mounting plate for the terminal block after removing the 1 screw 2 Remove the 2 connectors on the reactor 3 Cut 3 clamps that fix the wiring 4 Remove the mounting plate...

Page 9: ...ts 3 Remove the assembly of the PCB AIP Assembly of the PCB Retrieved 1 Remove the connectors on the PCB 2 Remove the 1 screw that fixes the electric component to the mounting plate 3 Pull out the ass...

Page 10: ...ated valve Precaution for the mounting of the coil of the motor operated valve 1 Remove the pressure thermistor 1 Remove the connector for the pressure thermistor X17A 2 Remove the pressure thermistor...

Page 11: ...have to replace all 4 thermistors at once 1 Remove the outdoor air thermistor pulling forward and then sliding it to the right 2 Pull out the discharge pipe thermistor 1 by picking and pulling out the...

Page 12: ...s and RelatedParts and other instructions Be sure to confirm that the refrigerant is completely collected before starting the work Protect other pipings using a protective sheet for the welding or ste...

Page 13: ...erminal One of the fixing nuts of the compressor is located at the outer side of the partition plate 1 Remove the fixing plate for the stop valve after removing the 5 screws 2 Remove the sound insulat...

Page 14: ...Revision History Month Year Version Revised contents 06 2013 Si281314E First edition...

Page 15: ...oduct The User s Manual provides important safety instructions and warnings Be sure to follow these instructions and warnings If you have any enquiries please contact your local importer distributor a...

Reviews: