Connection information on power supply wiring, earth wiring, and transmission wiring
〉
For the indoor unit wiring and transmission wiring (dash lines in the drawing), follow the instructions in the
indoor unit’s installation manual.
〈
Specification of standard wiring components
〉
NOTES
1.
Order appropriate power wire while following national laws and standards for the insulating sheath,
thickness, and length.
2.
When installing wiring in a location that can easily come in contact with people, be sure to install an earth
leakage breaker to prevent electric shock.
3.
The earth leakage breaker must be a high-speed type breaker of 30mA(<0.1S).
4.
Use an earth leakage breaker that can also be used as earth leakage, overload, short-circuit protection.
Be sure to use earth leakage breakers dedicated for earth leakage protection in combination with the load
break switch with fuse or breaker for wiring.
5.
RZR48
MUYMK
is only 50Hz model.
〈
CAUTION
〉
To the electrician
Do not run the unit until the refrigerant piping is complete, as not waiting could break the compressor.
POWER SUPPLY
50Hz/60Hz
1 2 3
1 2 3
L N
N
L
T
I
N
U
R
O
O
D
T
U
O
T
I
N
U
R
O
O
D
T
U
O
Earth leakage
breaker
Branch switch,
Power supply wire
(60245 IEC 57)
overcurrent
breaker
INDOOR UNIT
Remote Controller
INDOOR UNIT
Remote Controller
POWER SUPPLY
380-415V/400V
50Hz/60Hz
3N~
220-2
4
0V/230V
1~
brea
1 2 3
1 2 3
L1 L2 L3 N
L1 L2 L3
N
Earth leakage
breaker
Branch switch,
overcurrent
breaker
RZ(Q/R)
Y
V
20
Minimum circuit amps (MCA)
18.8
28.2
16.7
Recommended field fuse (A)
Power supply wire
diameter(mm²)
32
20
14.9
16
20
4.0 or more
2.5 or
more
2.5 or more
24
36
45
45
48
V
Y
Power supply wire
(60245 IEC 57)
Summary of Contents for RZQ20LCVAK
Page 30: ...MEMO...
Page 31: ...FBQ20EAVAK FBQ24EAVAK FBQ36EAVAK FBQ45EAVAK FBQ48EAVAK FBQ48EAVMK...
Page 32: ......
Page 33: ...R410A SUNISO R410A R410A R407C R410A R410A...
Page 34: ...R410A M5 16 24 20 48 45 36 M4 8...
Page 35: ...BRC1E62 BRC1D61 BRC1C61 BRC4C62 BRC4C64 FBQ48EAVMK BRC4C62...
Page 36: ......
Page 37: ...A 1 A 2...
Page 38: ...M10 A 1 A 2 B D B C D 24 20 48 45 36...
Page 39: ......
Page 40: ...C RH C R410A R410A...
Page 41: ...A...
Page 42: ......
Page 43: ...BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677...
Page 44: ......
Page 45: ......
Page 46: ...ASSY...
Page 47: ...X2M...
Page 48: ...X1M X2M...
Page 49: ......
Page 50: ...36 24 20 48 45 FBQ48EAVMK...
Page 51: ...P1 P2 2 P 1 P 2 P 1 P...
Page 52: ...S M P1 P2...
Page 53: ...L H...
Page 54: ...Daikin LCD...
Page 55: ......
Page 56: ...A1 A3 A6 A8 AF AH AJ C1 C4 C6 C9 CC CJ E0 E1...
Page 58: ...U4 UF UF U5 U8 UA UC UJ...
Page 59: ......
Page 91: ...English 30 MEMO...
Page 92: ...31 English MEMO...
Page 94: ...2 1...
Page 95: ...3 1 1 1 2 3 4 5 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...
Page 96: ...4 2 1 2 48 2 2 1 1 2 1 2 3 1 3 3 71 PP 2 1...
Page 97: ...5 3 1 4 6 3 2 5 5 4 1 1 1 5 1 5...
Page 103: ...11 4 2 1 3 1 B 1 2 40 D C 2 2 1 3 1 25 3 A 4 4 A D 5 4 4 4 1 3 2...
Page 104: ...12 100 M12 6 20 6 1 6 R410A BCuP 11 8 6...
Page 105: ...13 2 6 3 6 5 6 6 6 5 6 4 6 Suniso R407C R410A R410A 755 0 1...
Page 107: ...15 10 7 11 16 10 11...
Page 108: ...16 12 13 6 4 1 2 1 2 14 13 12 16 5 13 5 27 5 22 5...
Page 109: ...17 15 15 75 C 30 20 80 C 30 C 120 13 9 11 5 14...
Page 110: ...18 1 4 3 1 1 15 9 5 39 9 32 7 13 2 12 8 15 9 75 4 61 8 19 7 19 3...
Page 111: ...19 Daikin 0 02 7 4 0 9 5 90 60 200 15 9 60 30 300...
Page 113: ...21 0 011 0 09 1 2 3 R410A 4 8 R410A RZQ 20 24 RZQ 36 45 RZ Q R 48...
Page 114: ...22 9 230 500...
Page 115: ...V L N Y...
Page 116: ...24 M4 1 8 1 2 M5 3 0 2 0 M4 1 9 1 4 M5 2 9 2 4...
Page 117: ...Y V RZ Q R V Y 20 24 36 45 45 48 MCA A RZR48MUYMK...
Page 118: ......
Page 119: ...27 11 1 01 2 88 3 4 10 03 04 05 6 10 8 10 8 8 01 02 26 16 0 1...
Page 122: ...30...
Page 123: ......