6. REFRIGERANT PIPING WORK
〈
For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
〉
〈
Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a
water leakage can result sometimes.
〉
(
When using a heat pump, the temperature of the gas piping can reach up to approximately 120°C, so use
insulation which is sufficiently resistant.)
〈
Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 30°C or
RH80%, reinforce the refrigerant insulation. (20mm or thicker) Condensate may form on the surface of the
insulating material.
〉
〈
Be sure to check the type of R410A refrigerant to be used before doing any work. (Using an incorrect
refrigerant will prevent normal operation of the unit.)
〉
CAUTION
This product is designed to be used with new refrigerant (R410A). Always observe the precautions on the
following when installing.
•
Use a pipe cutter and flare suitable for the type of refrigerant.
•
Apply ester oil or ether oil around the flare section before connecting.
•
Use the flare nut provided to the unit. Do not use a different flare nut (class 1), or otherwise refrigerant
leakage may result.
•
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end or cover
it with tape.
•
Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, such
as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
•
The outdoor unit is charged with refrigerant.
•
Be sure to use both a spanner and torque wrench
together, as shown in the drawing, when connecting
or disconnecting pipes to/from the unit.
(Refer to Fig. 6)
•
Refer to “Table 1” for the dimensions of flare nut
spaces.
•
Use the flare nut included with the unit main body.
•
When connecting the flare nut, apply ester oil or
ether oil to the flare section (inside only), and spin
3-4 times before screwing in.
(Refer to Fig. 7)
CAUTION
•
Do not let oil get on the screw holders on the dressing board. Oil can weaken the screw holders.
•
Refer to “Table 1” to determine the proper tightening torque.
•
Be careful not to damage the flare section.
Torque wrench
Spanner
Piping union
Flare nut
Fig. 6
Fig. 7
Coat here with ester or ether oil.
01_EN_3PN06583-10W.fm Page 9
Thursday, March 24, 2011 9:03 AM
Summary of Contents for RZQ20LCVAK
Page 30: ...MEMO...
Page 31: ...FBQ20EAVAK FBQ24EAVAK FBQ36EAVAK FBQ45EAVAK FBQ48EAVAK FBQ48EAVMK...
Page 32: ......
Page 33: ...R410A SUNISO R410A R410A R407C R410A R410A...
Page 34: ...R410A M5 16 24 20 48 45 36 M4 8...
Page 35: ...BRC1E62 BRC1D61 BRC1C61 BRC4C62 BRC4C64 FBQ48EAVMK BRC4C62...
Page 36: ......
Page 37: ...A 1 A 2...
Page 38: ...M10 A 1 A 2 B D B C D 24 20 48 45 36...
Page 39: ......
Page 40: ...C RH C R410A R410A...
Page 41: ...A...
Page 42: ......
Page 43: ...BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677...
Page 44: ......
Page 45: ......
Page 46: ...ASSY...
Page 47: ...X2M...
Page 48: ...X1M X2M...
Page 49: ......
Page 50: ...36 24 20 48 45 FBQ48EAVMK...
Page 51: ...P1 P2 2 P 1 P 2 P 1 P...
Page 52: ...S M P1 P2...
Page 53: ...L H...
Page 54: ...Daikin LCD...
Page 55: ......
Page 56: ...A1 A3 A6 A8 AF AH AJ C1 C4 C6 C9 CC CJ E0 E1...
Page 58: ...U4 UF UF U5 U8 UA UC UJ...
Page 59: ......
Page 91: ...English 30 MEMO...
Page 92: ...31 English MEMO...
Page 94: ...2 1...
Page 95: ...3 1 1 1 2 3 4 5 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...
Page 96: ...4 2 1 2 48 2 2 1 1 2 1 2 3 1 3 3 71 PP 2 1...
Page 97: ...5 3 1 4 6 3 2 5 5 4 1 1 1 5 1 5...
Page 103: ...11 4 2 1 3 1 B 1 2 40 D C 2 2 1 3 1 25 3 A 4 4 A D 5 4 4 4 1 3 2...
Page 104: ...12 100 M12 6 20 6 1 6 R410A BCuP 11 8 6...
Page 105: ...13 2 6 3 6 5 6 6 6 5 6 4 6 Suniso R407C R410A R410A 755 0 1...
Page 107: ...15 10 7 11 16 10 11...
Page 108: ...16 12 13 6 4 1 2 1 2 14 13 12 16 5 13 5 27 5 22 5...
Page 109: ...17 15 15 75 C 30 20 80 C 30 C 120 13 9 11 5 14...
Page 110: ...18 1 4 3 1 1 15 9 5 39 9 32 7 13 2 12 8 15 9 75 4 61 8 19 7 19 3...
Page 111: ...19 Daikin 0 02 7 4 0 9 5 90 60 200 15 9 60 30 300...
Page 113: ...21 0 011 0 09 1 2 3 R410A 4 8 R410A RZQ 20 24 RZQ 36 45 RZ Q R 48...
Page 114: ...22 9 230 500...
Page 115: ...V L N Y...
Page 116: ...24 M4 1 8 1 2 M5 3 0 2 0 M4 1 9 1 4 M5 2 9 2 4...
Page 117: ...Y V RZ Q R V Y 20 24 36 45 45 48 MCA A RZR48MUYMK...
Page 118: ......
Page 119: ...27 11 1 01 2 88 3 4 10 03 04 05 6 10 8 10 8 8 01 02 26 16 0 1...
Page 122: ...30...
Page 123: ......