01_EN_3P281953-1B.fm Page 5 Tuesday, January 25, 2011 3:35 PM
5
English
(2) When installing the unit in a place exposed to strong wind, pay special attention to the following.
5 m/sec or more strong wind blown against the outdoor unit’s air outlet causes the outdoor unit to
deteriorate in air capacity and suck in the air blown out of its air outlet (short circuit), and the following
effects may result.
•
Drop in performance.
•
Increased frost formation in heating mode.
•
Shutting down due to increase in pressure.
If a very high fan strength is used continuously from the front of the outdoor unit outlet side, the fan might
turn in reverse at high speed, and become damaged.
•
Turn the air outlet side toward the building’s wall, fence or windbreak screen.
Air inlet grille
Ensuring there is enough
space for installing the unit.
Fig. 4
〈
CAUTION
〉
•
Inverter air conditioners may cause noise
to occur in electrical appliances.
As shown in the right drawing, select an
installation site well away from radios, PCs,
and stereos.
•
Especially in the areas where the incoming
signal strength is weak, keep the indoor
remote controller 3 m or more from
electrical appliances. Put the power cord
and connecting wires in a metal pipe and
ground the metal pipe.
Indoor unit
Branch switch,
over current
breaker
Indoor
remote
controller
1.5 m or more
1.5 m or more
1 m or more
1 m or more
3. SELECTING INSTALLATION SITE
(1) Select an installation site where the following conditions are satisfied and that meets with your
customer’s approval.
•
Places where there is no possibility of flammable gas leak.
•
Places where the unit does not bother next-door neighbors.
•
Safe places which can withstand the unit’s weight and vibration and where the unit can be installed level.
•
Places which are well-ventilated.
•
Places where servicing space can be well ensured.
The minimum required space is shown in chapter
4. INSTALLATION SERVICING SPACE
.
•
Places where the indoor and outdoor unit’s piping and wiring lengths come within the allowable ranges.
(Please refer to chapter
6. REFRIGERANT PIPING WORK
.)
•
Set the outlet side at a right angle to the direction of the wind.
Fig. 5
Strong wind
Strong wind
Blown air
Summary of Contents for RZQ20LCVAK
Page 30: ...MEMO...
Page 31: ...FBQ20EAVAK FBQ24EAVAK FBQ36EAVAK FBQ45EAVAK FBQ48EAVAK FBQ48EAVMK...
Page 32: ......
Page 33: ...R410A SUNISO R410A R410A R407C R410A R410A...
Page 34: ...R410A M5 16 24 20 48 45 36 M4 8...
Page 35: ...BRC1E62 BRC1D61 BRC1C61 BRC4C62 BRC4C64 FBQ48EAVMK BRC4C62...
Page 36: ......
Page 37: ...A 1 A 2...
Page 38: ...M10 A 1 A 2 B D B C D 24 20 48 45 36...
Page 39: ......
Page 40: ...C RH C R410A R410A...
Page 41: ...A...
Page 42: ......
Page 43: ...BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677...
Page 44: ......
Page 45: ......
Page 46: ...ASSY...
Page 47: ...X2M...
Page 48: ...X1M X2M...
Page 49: ......
Page 50: ...36 24 20 48 45 FBQ48EAVMK...
Page 51: ...P1 P2 2 P 1 P 2 P 1 P...
Page 52: ...S M P1 P2...
Page 53: ...L H...
Page 54: ...Daikin LCD...
Page 55: ......
Page 56: ...A1 A3 A6 A8 AF AH AJ C1 C4 C6 C9 CC CJ E0 E1...
Page 58: ...U4 UF UF U5 U8 UA UC UJ...
Page 59: ......
Page 91: ...English 30 MEMO...
Page 92: ...31 English MEMO...
Page 94: ...2 1...
Page 95: ...3 1 1 1 2 3 4 5 R410A SUNISO R410A R410A 33 3 3 R407C 40 4 0 R410A R410A...
Page 96: ...4 2 1 2 48 2 2 1 1 2 1 2 3 1 3 3 71 PP 2 1...
Page 97: ...5 3 1 4 6 3 2 5 5 4 1 1 1 5 1 5...
Page 103: ...11 4 2 1 3 1 B 1 2 40 D C 2 2 1 3 1 25 3 A 4 4 A D 5 4 4 4 1 3 2...
Page 104: ...12 100 M12 6 20 6 1 6 R410A BCuP 11 8 6...
Page 105: ...13 2 6 3 6 5 6 6 6 5 6 4 6 Suniso R407C R410A R410A 755 0 1...
Page 107: ...15 10 7 11 16 10 11...
Page 108: ...16 12 13 6 4 1 2 1 2 14 13 12 16 5 13 5 27 5 22 5...
Page 109: ...17 15 15 75 C 30 20 80 C 30 C 120 13 9 11 5 14...
Page 110: ...18 1 4 3 1 1 15 9 5 39 9 32 7 13 2 12 8 15 9 75 4 61 8 19 7 19 3...
Page 111: ...19 Daikin 0 02 7 4 0 9 5 90 60 200 15 9 60 30 300...
Page 113: ...21 0 011 0 09 1 2 3 R410A 4 8 R410A RZQ 20 24 RZQ 36 45 RZ Q R 48...
Page 114: ...22 9 230 500...
Page 115: ...V L N Y...
Page 116: ...24 M4 1 8 1 2 M5 3 0 2 0 M4 1 9 1 4 M5 2 9 2 4...
Page 117: ...Y V RZ Q R V Y 20 24 36 45 45 48 MCA A RZR48MUYMK...
Page 118: ......
Page 119: ...27 11 1 01 2 88 3 4 10 03 04 05 6 10 8 10 8 8 01 02 26 16 0 1...
Page 122: ...30...
Page 123: ......