5
English
The inverter type air conditioner may cause noise in
(5)
electric products.
When selecting an installation location, keep suffi -
cient distance from the air conditioner units and
wiring to radios, personal computers, stereos, etc. as
shown in the fi gure below.
In areas with weak electric waves, keep a distance of
120 in. or more from the indoor remote controller, etc.,
put the power cables and connection cables in con-
duit tubes, and ground the conduit tubes.
40 or more
Branch switch
and overcurrent
protective device
Indoor remote
controller
60 or more
60 or more
40 or more
Branch switch
and overcurrent
protective device
60 or more
Indoor unit
(in.)
DANGER
Do not install unit in an area where fl ammable materials are
•
present due to risk of explosion resulting in serious injury or
death.
Refrigerant is heavier than air and replaces oxygen. A
•
massive leak could lead to oxygen depletion , especially in
basements, and an asphyxiation hazard could occur leading
to serious injury or death.
Installation place (unit: inch)
〈
Cautions on continuous installation
〉
The connection piping outlet direction in the continuous
•
installation shown in the fi gures below is frontward or down-
ward.
When routing the piping rearward, secure space of 10 in. or
•
more on the right side of the outdoor unit. (The unit of nu-
meric values below is “inch”.)
Make some space for wiring with conduit and servicing
•
between the units.
(A) When an obstruction is present on the air inlet side
When the upward area is open
•
When one outdoor unit is installed individually
(1)
When an obstruction is present only on the air inlet
•
side
4 or more
When an obstruction is present on the both sides
•
4 or more
4 or more
4 or more
When two or more outdoor units are installed side
(2)
by side
When an obstruction is present on the both sides
•
40 or more
12 or more
8 or more
When an obstruction is present also in the upward area
•
When one outdoor unit is installed individually
(1)
When an obstruction is present also on the air inlet
•
side
20 or less
40 or more
4 or more
When an obstruction is present also on the air inlet
•
side and both sides
6 or more
6 or more
20 or less
6 or more
40 or more
01_EN_3P281953-4G.indd 5
01_EN_3P281953-4G.indd 5
2/21/2017 9:57:55 AM
2/21/2017 9:57:55 AM