Installation manual

5

RZQ71~125B7V3B

Split System air conditioners

4PW16864-1A

Selection of piping material

Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R-410A piping must be in accordance with the
table below.

O = Annealed
1/2H = Half hard

Refrigerant pipe size

Pair system 

(See figure 2)

Simultaneous operation system (twin: see 

figure 3

, triple: see

figure 4

, double twin: see 

figure 5

)

 

The pipes between the outdoor unit and the branch (L1) should have
the same size as the outdoor connections. The pipes between the
branch and the indoor units (L2~L5) should have the same size as
the indoor connections. Branch: see marking '

' on figures 

3

4

and 

5

.

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to figures

2

3

4

 and 

5

Assume that the longest line in the figure corresponds

with the actual longest pipe, and the highest unit in the figure
corresponds with the actual highest unit.

Pipe Ø

Temper grade of piping 

material

Minimal thickness t(mm)

6.4 / 9.5 / 12.7

O

0.80

15.9

O

1

19.1

1/2H

1

Refrigerant pipe size

(*)

(*)

In case of twin, triple and double twin applications, the listed refrigerant pipe 
sizes relate to the main pipes only. (L1 = the pipes between the outdoor unit and 
the branch in figures 

3

~

5

).

Gas pipe

Model

Size-down

Standard size

Size-up

RZQ71

Ø12.7

Ø15.9

125

Ø19.1

Liquid pipe

Model

Size-down

Standard size

Size-up

RZQ71~125

Ø6.4

Ø9.5

Ø12.7

NOTE

Not using the standard pipe size may result in capacity
decrease. It is up to the installer to judge on this
phenomena carefully in function of the complete
installation.

Allowable pipe length

Liquid pipe 

size

Model RZQ

71

100

125

Maximum allowable piping length

(*)

(*)

Parenthesized figure represents the equivalent length.

Pair

L1

size-down

10 m (15 m)

standard

50 m 

(70 m)

75 m 

(95 m)

75 m 

(95 m)

size-up

25 m 

(35 m)

35 m 

(45 m)

35 m 

(45 m)

• Twin and triple
• Double twin

• L1+L2
• L1+L2+

L4

size-down

10 m (15 m)

standard

50 m 

(70 m)

75 m 

(95 m)

75 m 

(95 m)

size-up

25 m 

(35 m)

35 m 

(45 m)

35 m 

(45 m)

Maximum total one-way piping length

Twin

L1+L2+L3

60 m

75 m

75 m

Triple

L1+L2+L3
+L4

Double twin

L1+L2+L3
+L4+L5+
L6+L7

Maximum branch piping length

• Twin and triple
• Double twin

• L2
• L2+L4

20 m

Maximum difference between branch lengths

Twin

L2–L3

10 m

10 m

10 m

Triple

L2–L4

Double twin

• L2–L3
• L4–L5
• L6–L7
• (L2+L4)–

(L3+L7)

Maximum height between indoor and outdoor

All

H1

30 m

Maximum height between indoors

Twin, triple and 
double twin

H2

0.5 m

Chargeless length

All

L1+L2+L3
+L4+L5+
L6+L7

size-down

10 m

standard

30 m

size-up

15 m

Summary of Contents for RZQ100B7V3B

Page 1: ...INSTALLATION MANUAL RZQ71B7V3B RZQ100B7V3B RZQ125B7V3B Split System air conditioners...

Page 2: ...6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C...

Page 3: ...ni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid ka...

Page 4: ...may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire When a...

Page 5: ...ete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conductor or telephone ground wire Ele...

Page 6: ...inage of the unit is not easy please build up the unit on a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install...

Page 7: ...he table below REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH Suction side obstacle Obstacle is present Discharge side obstacle 1 In these cases close the bottom of the installation frame to prevent...

Page 8: ...0 15 9 O 1 19 1 1 2H 1 Refrigerant pipe size In case of twin triple and double twin applications the listed refrigerant pipe sizes relate to the main pipes only L1 the pipes between the outdoor unit a...

Page 9: ...s through walls In case of simultaneous operating system Upward and downward piping should be performed at the main piping line Use branch piping kit optional for branching refrigerant pipes Precautio...

Page 10: ...Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service port After the wor...

Page 11: ...the air with refrigerants Use a vacuum pump to vacuum the installation No additional refrigerant is provided for air purging Pipes inside the units were checked for leaks by the manufacturer The refr...

Page 12: ...1 0 5 kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0 kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 R...

Page 13: ...may cause capacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to th...

Page 14: ...ning torques for the terminal screws Refer to the installation manual attached to the indoor unit for wiring of indoor units etc Attach an earth leak detector and fuse to the power supply line See fig...

Page 15: ...is not starting and stopping during the test run by listening If it is starting and stopping immediately stop the machine using the remote control and check the refrigerant level etc There may be som...

Page 16: ...r R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high TC Signal tra...

Page 17: ...NOTES NOTES...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN16864 1A...

Reviews: