background image

RZQ71~125B7V3B
Split System air conditioners
4PW16864-1A

Installation manual

8

Cautions for flare connection

Please refer to the table for the dimensions for processing flares
and for the tightening torques. (Too much tightening will end up
in splitting of the flare.)

When connecting the flare nut, apply refrigerating machine oil to
the flare (inside and outside) and first screw the nut 3 or 4 turns
by hand.
Coat here with ether or ester oil.

After completing the installation, carry out a gas leak inspection
of the piping connections with nitrogen and such.

Cautions for necessity of a trap

Since there is fear of the oil held inside the riser piping flowing back into
the compressor when stopped and causing liquid compression
phenomenon, or cases of deterioration of oil return, it will be necessary
to provide a trap at an appropriate place in the riser gas piping.

Trap installation spacing. 

(See figure 6)

A

Outdoor unit

B

Indoor unit

C

Gas piping

D

Liquid piping

E

Oiltrap

H

Install trap at each difference in height of 15 m.

A trap is not necessary when the outdoor unit is installed in a
higher position than the indoor unit.

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

E

VACUATING

Do not purge the air with refrigerants. Use a vacuum pump to
vacuum the installation. No additional refrigerant is provided for
air purging.

Pipes inside the units were checked for leaks by the
manufacturer. The refrigerant pipes fit on site are to be checked
for leaks by the installer.

Confirm that the valves are firmly closed before leak test or
vacuuming.

Set up for vacuuming and leak test: 

see 

figure 8

Procedure for leak test

Leak test must satisfy EN378-2.

1

Evacuate the pipes and check vacuum

(1)

. (No pressure increase

for 1 minute.)

2

Break the vacuum with a minimum of 2 bar of nitrogen. (Never
pressurize more than 4.0 MPa.)

Piping 

size

Flare nut 

tightening torque

A dimensions 

for processing 

flares (mm)

Flare shape

Ø6.4

14.2~17.2 N•m 

(144~176 kgf•cm)

8.7~9.1

Ø9.5

32.7~39.9 N•m 

(333~407 kgf•cm)

12.8~13.2

Ø12.7

49.5~60.3 N•m 

(504~616 kgf•cm)

16.2~16.6

Ø15.9

61.8~75.4 N•m 

(630~770 kgf•cm)

19.3~19.7

Ø19.1

97.2~118.6 N•m 

(989.8~1208 kgf•cm)

23.6~24.0

2

1

3

5

5

A

4

4

6

1

Compressor

2

Terminal cover

3

Indoor and outdoor 
field piping

4

Corking, etc.

5

Insulation material

6

Bolts

A

Be careful with pipe, 
bolt and outer panel 
connections

R=0.4~0.8

45

° ±

2

90

°±

0.5

A

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

A

Pair system

B

Simultaneous operation system

1

Pressure gauge

2

Nitrogen

3

Refrigerant

4

Weighing machine

5

Vacuum pump

6

Stop valve

7

Main pipe

8

Branched pipes

9

Pipe branching kit (optional)

(1) Use a 2-stage vacuum pump with a non return valve which 

can evacuate to –100.7 kPa (5 Torr, –755 mm Hg).
Evacuate the system from the liquid and gas pipes by using 
a vacuum pump for more than 2 hours and bring the system 
to –100.7 kPa. After keeping the system under that condition 
for more than one hour, check if the vacuum gauge rises or 
not. If it rises, the system may either contain moisture inside 
or have leaks.

1

2

3

4

5

6

6

Summary of Contents for RZQ100B7V3B

Page 1: ...INSTALLATION MANUAL RZQ71B7V3B RZQ100B7V3B RZQ125B7V3B Split System air conditioners...

Page 2: ...6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C...

Page 3: ...ni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid ka...

Page 4: ...may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire When a...

Page 5: ...ete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conductor or telephone ground wire Ele...

Page 6: ...inage of the unit is not easy please build up the unit on a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install...

Page 7: ...he table below REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE LENGTH Suction side obstacle Obstacle is present Discharge side obstacle 1 In these cases close the bottom of the installation frame to prevent...

Page 8: ...0 15 9 O 1 19 1 1 2H 1 Refrigerant pipe size In case of twin triple and double twin applications the listed refrigerant pipe sizes relate to the main pipes only L1 the pipes between the outdoor unit a...

Page 9: ...s through walls In case of simultaneous operating system Upward and downward piping should be performed at the main piping line Use branch piping kit optional for branching refrigerant pipes Precautio...

Page 10: ...Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service port After the wor...

Page 11: ...the air with refrigerants Use a vacuum pump to vacuum the installation No additional refrigerant is provided for air purging Pipes inside the units were checked for leaks by the manufacturer The refr...

Page 12: ...1 0 5 kg b G2 12 m 6 4 R2 0 6 kg 3 Refrigerant charge amount R R1 R2 0 5 0 6 1 1 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0 kg b G1 G2 30 5 54 30 29 6 4 R2 0 9 kg 3 R...

Page 13: ...may cause capacitor abnormal heating accident due to high frequency waves Therefore never install a phase advancing capacitor Secure the wiring in the order shown below 1 Secure the ground wire to th...

Page 14: ...ning torques for the terminal screws Refer to the installation manual attached to the indoor unit for wiring of indoor units etc Attach an earth leak detector and fuse to the power supply line See fig...

Page 15: ...is not starting and stopping during the test run by listening If it is starting and stopping immediately stop the machine using the remote control and check the refrigerant level etc There may be som...

Page 16: ...r R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high TC Signal tra...

Page 17: ...NOTES NOTES...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN16864 1A...

Reviews: